Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Daikin Mini-Split: Check compressor and inverter with the analyzer

Updated · by Aurora Star Tech Inc.

Check compressor and inverter with the analyzer on a Daikin mini-split: Tell a bad compressor from a bad board. Tool is analyzer RSUK0917C.

Homeowner with a ductless mini-split problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9

How to fix check compressor and inverter with the analyzer: step by step

  1. Power off and wait for the DC bus capacitor to drop to 10 VDC or less.
  2. Unplug the compressor leads and connect them to the analyzer. Keep U, V, W from touching.
  3. Power on, set FAN mode, press Temp up, Temp down and Mode together, pick T, press Mode.
  4. All six LEDs even: compressor is bad. Uneven: check the power module.
  5. Re-crimp the FASTON terminals afterward.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Mini-Split codes

Models

FTX30WVJU9FTX36WVJU9RK30WMVJU9RK36WMVJU9RX30WMVJU9RX36WMVJU9

Source: Daikin FTX-W service manual SiUS042228E, Inverter analyzer check 5.7, p.116. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency HVAC Service

647-657-2977