Daikin Mini-Split: Check compressor and inverter with the analyzer
Check compressor and inverter with the analyzer on a Daikin mini-split: Tell a bad compressor from a bad board. Tool is analyzer RSUK0917C.
Applies to: FTX30/36WVJU9 with RX30/36WMVJU9 or RK30/36WMVJU9
How to fix check compressor and inverter with the analyzer: step by step
- Power off and wait for the DC bus capacitor to drop to 10 VDC or less.
- Unplug the compressor leads and connect them to the analyzer. Keep U, V, W from touching.
- Power on, set FAN mode, press Temp up, Temp down and Mode together, pick T, press Mode.
- All six LEDs even: compressor is bad. Uneven: check the power module.
- Re-crimp the FASTON terminals afterward.
If the unit shows an error code, look it up: Daikin Mini-Split codes
Models
FTX30WVJU9FTX36WVJU9RK30WMVJU9RK36WMVJU9RX30WMVJU9RX36WMVJU9
Source: Daikin FTX-W service manual SiUS042228E, Inverter analyzer check 5.7, p.116. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.