Carrier 59TP6A060-14 error codes list

CodeMeaningSeverity
11No previous codeLow
12Blower on after power-up (normal)Low
13Limit circuit lockoutCritical
14Ignition lockoutCritical
15Blower motor lockoutHigh
21Gas heating lockoutCritical
22Abnormal flame-proving signalCritical
23Pressure switch did not openMedium
24Secondary (24 V) fuse openMedium
25Invalid model selection or setup errorMedium
31High-heat pressure switch or relay did not close or reopenedHigh
32Low-heat pressure switch did not close or reopenedHigh
33Limit circuit faultHigh
34Ignition proving failureHigh
43Low-heat pressure switch open while high-heat switch closedHigh
45Control circuitry lockoutHigh
LED OFFNo amber LED - no power to controlHigh
Rapid FlashReversed 115-V polarity (or twinning phasing)High

Troubleshooting the 59TP6A060-14

Carrier 59TP6A060-14 specs and setup data

All Carrier Furnace error codes →

Homeowner help: Furnace Not Turning On: What to Check · Furnace Blinking Light: What the Flash Codes Mean

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.