Daikin Error Code 14: Repeated high pressure faults (minor) (Heat Pump)
Daikin error code 14 on a heat pump means: Repeated high pressure faults (minor). It is also called Daikin diagnostic code 14.
Homeowner? What Daikin code 14 means for you
Check, then call Your heat pump is reporting: Repeated high pressure faults (minor). This is often caused by something simple. Try the safe checks below; if the code returns, book a service call before it turns into a no-heat or no-hot-water emergency.
Safe things you can check yourself
- Check the thermostat: right mode (Heat or Cool), set a few degrees past room temperature, and fresh batteries if it uses them.
- Check both breakers and the outdoor disconnect box beside the outdoor unit; all should be ON.
- Look at the air filter. If it is grey and clogged, replace it; a blocked filter causes many shutdowns.
- In winter, keep snow and ice off and away from the outdoor unit. A short defrost cycle with steam is normal.
- Try one reset: turn the power off for 30 seconds, then back on. If the code comes back, stop resetting and call a technician.
Call (647) 657-2977Book a service call
Licensed technicians serving Vaughan, Toronto and the GTA.
What does Daikin error code 14 mean?
The thermostat shows 14; the board shows nothing. The unit has had several high pressure trips but the control lets it keep running. Something is still wrong and should be found.
Applies to: DH6VS***1*A*, DH7VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)
Common causes of Daikin code 14
- Stop valve not fully open
- Dirty or blocked outdoor coil, or a restriction in the lines
- Too much refrigerant
A technician checks these and 4 other possible causes on site before replacing any part.
Daikin models that use code 14
DH6VS*181DH6VS*241DH6VS*301DH6VS*361DH6VS*421DH6VS*481DH6VS*601DH7VSA2410DH7VSA3610DH7VSA4210DH7VSA4810
Other Daikin Heat Pump codes
All Daikin Heat Pump error codes →
Daikin code 14: homeowner questions
What does Daikin code 14 mean?
Repeated high pressure faults (minor). The thermostat shows 14; the board shows nothing. The unit has had several high pressure trips but the control lets it keep running. Something is still wrong and should be found.
Is it safe to keep using my heat pump with code 14?
It depends on the cause. This is often caused by something simple. Try the safe checks below; if the code returns, book a service call before it turns into a no-heat or no-hot-water emergency.
Can I reset Daikin code 14 myself?
You can try one reset (power off for 30 seconds, then on). If Daikin code 14 comes back, the cause is still there and a licensed technician should check it.
Who can fix Daikin code 14 near me?
Aurora Star Tech Inc. repairs Daikin heat pumps in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.
Homeowner help: AC Running But Not Cooling: What to Check · Heat Pump Not Heating or Blowing Cold Air
Troubleshooting guides
- 2 flashes: HPS open ≥6 s; 3: discharge >263°F; 4: discharge <90°F after 1 h; 5: defrost failure; 6: discharge sensor short; 7: outdoor sensor open/short; 9: bonnet sensor fail All brands · Heat Pump
- Excess ice on outdoor coil All brands · Heat Pump
- Extremely high head pressure in heating (dual fuel) All brands · Heat Pump
- Insufficient heat in cold weather All brands · Heat Pump
- Liquid slugging / compressor damage in heating All brands · Heat Pump
- No mode change / wrong mode All brands · Heat Pump
- Odour at registers (dirty sock) All brands · Heat Pump
- Poor heating but OK cooling (or vice-versa) All brands · Heat Pump
- Service problem analysis (Amana chart excerpt) All brands · Heat Pump
- Subcooling too high All brands · Heat Pump
- Subcooling too low vs mfr target All brands · Heat Pump
- TXV bulb/diaphragm failure All brands · Heat Pump
- Water-source: coil freezing All brands · Heat Pump
- Won't change mode / both coils same temperature All brands · Heat Pump
- Wrong superheat after line-set change; poor capacity All brands · Heat Pump
- FIT communication error: network check Daikin · Heat Pump
- FIT: reading the fault code and fault history Daikin · Heat Pump
- No cooling: heat pump (1 stage) check order Daikin · Heat Pump
- No heat: heat pump (1 stage) check order Daikin · Heat Pump
- Reversing valve will not shift Daikin · Heat Pump
- Testing the run capacitor Daikin · Heat Pump
Source: Daikin 3P761829-1B FIT outdoor unit DC6VS/DH6VS/DC9VSA/DH7VSA installation & service reference, Troubleshooting table p.43 (printed page). Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.