Daikin Heat Pump: No heat: heat pump (1 stage) check order
No heat: heat pump (1 stage) check order on a Daikin heat pump: Check order when the heat pump will not heat.
Applies to: DH4SQA, DH4SEA, DH5SEA (single stage R-32 heat pumps with CoreSense module)
How to fix no heat: heat pump (1 stage) check order: step by step
- Kill power at the disconnect before working in the unit. There can be more than one power source.
- Check 230 V at the unit and transformer, 24 V out, 24 V on Y and at the contactor coil.
- Check the contactor, compressor wiring, run capacitor, overload and windings.
- Make sure the thermostat is in heat. These units energize the reversing valve in cooling (O), so in heat the valve should be off.
- If the valve is stuck in the cool position or half way, check its wiring and solenoid, then replace the valve if needed.
- Check the indoor blower relay, wiring and motor.
- Then check the metering device and the charge.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Models
DH4SEA**10AADH4SQA**10AADH5SEA**10AA
Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Troubleshooting chart Heat Pump - Heating (1 Stage) p.51-52; System Operation p.12-13. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.