Daikin Heat Pump: No cooling: heat pump (1 stage) check order
No cooling: heat pump (1 stage) check order on a Daikin heat pump: Same checks as a straight AC, plus the reversing valve.
Applies to: DH4SQA, DH4SEA, DH5SEA (single stage R-32 heat pumps with CoreSense module)
How to fix no cooling: heat pump (1 stage) check order: step by step
- Kill power at the disconnect before working in the unit. There can be more than one power source.
- Check 230 V at the unit and at the transformer, 24 V out of the transformer, 24 V on Y and at the contactor coil.
- Contactor, wiring to compressor, run capacitor, overload and windings, same as an AC.
- Check the thermostat is in cool and puts 24 V on O.
- Check 24 V at the reversing valve solenoid. With 24 V there, check the coil. A good coil and a valve that will not shift, or a valve stuck half way: replace the valve.
- Check the reversing valve is piped the right way.
- Check the indoor blower relay, control wiring and motor.
- Then check the metering device and the charge (subcooling / superheat).
If the unit shows an error code, look it up: Daikin Heat Pump codes
Models
DH4SEA**10AADH4SQA**10AADH5SEA**10AA
Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Troubleshooting chart Heat Pump - Cooling (1 Stage) p.49-50. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.