Icon
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Gree Error Code n7: Running parameter query (Heat Pump)

Updated · by Aurora Star Tech Inc.

Gree error code n7 on a heat pump means: Running parameter query. It is also called Gree diagnostic code n7.

Low severityHeat PumpGree GMV6 Mini VRF

Homeowner? What Gree code n7 means for you

Usually minor Your heat pump is reporting: Running parameter query. This code is usually informational or minor. The safe checks below often clear it; call us if it keeps showing up.

Safe things you can check yourself

  • Check the thermostat: right mode (Heat or Cool), set a few degrees past room temperature, and fresh batteries if it uses them.
  • Check both breakers and the outdoor disconnect box beside the outdoor unit; all should be ON.
  • Look at the air filter. If it is grey and clogged, replace it; a blocked filter causes many shutdowns.
  • In winter, keep snow and ice off and away from the outdoor unit. A short defrost cycle with steam is normal.
  • Try one reset: turn the power off for 30 seconds, then back on. If the code comes back, stop resetting and call a technician.

Call (647) 657-2977Book a service call

Licensed technicians serving Vaughan, Toronto and the GTA.

What does Gree error code n7 mean?

n7 shows live running parameters of a chosen outdoor module on the display, as a two-digit parameter code and its value. The list is: 01 outdoor ambient, 02 compressor 1 frequency, 03 compressor 2 frequency, 04 outdoor fan frequency, 05 module high pressure, 06 module low pressure, 07 to 12 discharge temperatures of compressors 1 to 6, 13 compressor 3 frequency, 14 to 19 compressor currents, 21 to 24 drive module temperatures, 25 to 27 outdoor heating EEV 1, EEV 2 and subcooler EEV, 28 defrost temperature, 29 subcooler liquid outlet, 30 accumulator outlet, 31 oil return, 32 condenser inlet pipe, 33 condenser outlet pipe. Outdoor ambient is shown first.

Applies to: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V..WL/C-T(U))

Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Gree models that use code n7

GMV-V36WL/C-T(U)GMV-V48WL/C-T(U)GMV-V60WL/C-T(U)

Other Gree Heat Pump codes

CodeMeaning
n0Auto energy saving (menu)
n1Defrost cycle K1 setting
n3Forced defrost (menu)
n4Maximum output limit (forced energy saving)
n5Indoor engineering number offset
n6Fault history query
n8Indoor engineering number query
n9Online indoor unit count
nASystem mode: cooling and heating
nbOutdoor and controller barcode query
nCSystem mode: cooling only
nENegative number prefix

All Gree Heat Pump error codes →

Gree code n7: homeowner questions

What does Gree code n7 mean?

Running parameter query. n7 shows live running parameters of a chosen outdoor module on the display, as a two-digit parameter code and its value. The list is: 01 outdoor ambient, 02 compressor 1 frequency, 03 compressor 2 frequency, 04 outdoor fan frequency, 05…

Is it safe to keep using my heat pump with code n7?

Usually yes. Code n7 is normally minor, but if it keeps coming back have it checked.

Can I reset Gree code n7 myself?

You can try one reset (power off for 30 seconds, then on). If Gree code n7 comes back, the cause is still there and a licensed technician should check it.

Who can fix Gree code n7 near me?

Aurora Star Tech Inc. repairs Gree heat pumps in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.

Homeowner help: AC Running But Not Cooling: What to Check · Heat Pump Not Heating or Blowing Cold Air

Troubleshooting guides

Source: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V36-48-60WL-C-T(U)) service.pdf - section 4.2.4.2 and Chapter 3 Faults, 4.1 Error Indication. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency HVAC Service

647-657-2977