Rheem Furnace: No heat – inducer (IDM) does not start

Updated · by Aurora Star Tech Inc.

No heat - inducer (IDM) does not start on a Rheem furnace: POWER LED on, thermostat calling, but the induced draft motor never starts.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Rheem (-)GRC/(-)GTC and 90RJ/90TJ 90 Plus condensing gas furnaces

Common causes of no heat - inducer (idm) does not start

  • No 24 V on W
  • Thermostat not in heat / dead batteries / wiring
  • Lockout or fault code present
  • No line voltage to IDM, bad wiring, bad capacitor

How to fix no heat - inducer (idm) does not start: step by step

  1. Set FAN to AUTO and call for heat with the setpoint more than 10°F above room temperature.
  2. Check for 24 V from W to C at the IFC; if none, check thermostat mode, batteries, wires and connections.
  3. Check the STATUS LED: if blinking, follow the blink code; if steady on, check the pressure switch is not stuck closed (contacts, short, water) then the IFC.
  4. If W is present and no code: check line voltage at the IDM, the wiring between IDM and IFC, line voltage on the IDM pins of the IFC connector, and the IDM capacitor (90+ only).
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Rheem Furnace codes

Models

Rheem 90RJ/90TJ 90 Plus

90RJ0490RJ0690RJ0790RJ0990RJ1090RJ1290TJ0490TJ0690TJ0790TJ0990TJ1090TJ12

R95P

R95PA0401317MSAR95PA0601317MSAR95PA0701317MSAR95PA0851521MSAR95PA1001521MSAR95PA1151524MSA

Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)

R802PA050314MSAR802PA075417MSAR802PA100521MSAR802PA125524MSAR802PA150524MSA

RGPE/RGLE

RGLE-05(-)BMKRRGLE-07(-)AMKRRGLE-07(-)BRQRRGLE-10(-)BRMRRGLE-12(-)ARMRRGPE-05(-)BMKRRGPE-07(-)AMKRRGPE-07(-)BRQRRGPE-10(-)BRMRRGPE-12(-)ARMR

Rheem (-)GRC/(-)GTC 90 Plus

RGRC-04EMAESRGRC-06EMAESRGRC-07EMAESRGRC-07ERBGSRGRC-09EZAJSRGRC-10EZAJSRGTC-04EMAESRGTC-06EMAESRGTC-07ERBGSRGTC-09EZAJSRGTC-10ERBJS

Rheem RGRM/RGTM 90 Plus

RGRM-04RGRM-06RGRM-07RGRM-09RGRM-10RGRM-12RGTM-06RGTM-07RGTM-09RGTM-10

Source: Rheem (-)GRC/(-)GTC Installation Instructions 92-24161-88-00, Figure 56 IFC Troubleshooting Guide, p.54 (printed); Rheem 90RJ/90TJ Installation Instructions 92-24161-32-08, Figure 53, p.54. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.