Rheem Furnace: Furnace no heat – sequence troubleshooting
Furnace no heat - sequence troubleshooting on a Rheem furnace: Step through the normal heat sequence: pressure switch check, 30-second prepurge, 8-second ignition trial on low fire, blower on about 20 seconds after ignition, staging, 10-second post-purge.
Applies to: (-)802PA050314MSA, (-)802PA075417MSA, (-)802PA100521MSA, (-)802PA125524MSA, (-)802PA150524MSA and matching (-)(-)80MDP models
Common causes of furnace no heat - sequence troubleshooting
- No 24V on W
- Inducer or pressure switch problem
- No spark
- No gas / low gas pressure
- Weak flame sense
- Limit or roll-out open
- Blower not starting
How to fix furnace no heat - sequence troubleshooting: step by step
- Set fan to AUTO and call for low heat. If a fault code shows, follow that code.
- Confirm 24V on W at the IFC; if none, check thermostat, batteries and wiring.
- Inducer should run 30-second prepurge; if it runs 60 seconds then stops for 5 minutes, the pressure switch did not close - check hoses, vent, inducer.
- Check spark during the trial; check igniter, wires and placement.
- If burners light but drop out, clean flame sensor, check polarity and ground, check gas pressure.
- Blower should start about 20 seconds after ignition; if not, check HEAT-NEUTRAL voltage, wiring, capacitor and motor.
- For high heat, check 24VAC on W2 and that the high gas valve is energized.
- Most failures are not the IFC - check wiring and ground before replacing it.
If the unit shows an error code, look it up: Rheem Furnace codes
Models
96V
(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100
Rheem 90RJ/90TJ 90 Plus
90RJ0490RJ0690RJ0790RJ0990RJ1090RJ1290TJ0490TJ0690TJ0790TJ0990TJ1090TJ12
96MDV
96MDV06096MDV07096MDV08596MDV100
R96V/96MDV
R95P
R95PA0401317MSAR95PA0601317MSAR95PA0701317MSAR95PA0851521MSAR95PA1001521MSAR95PA1151524MSA
Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)
R802PA050314MSAR802PA075417MSAR802PA100521MSAR802PA125524MSAR802PA150524MSA
RGPE/RGLE
RGLE-05(-)BMKRRGLE-07(-)AMKRRGLE-07(-)BRQRRGLE-10(-)BRMRRGLE-12(-)ARMRRGPE-05(-)BMKRRGPE-07(-)AMKRRGPE-07(-)BRQRRGPE-10(-)BRMRRGPE-12(-)ARMR
Rheem (-)GRC/(-)GTC 90 Plus
RGRC-04EMAESRGRC-06EMAESRGRC-07EMAESRGRC-07ERBGSRGRC-09EZAJSRGRC-10EZAJSRGTC-04EMAESRGTC-06EMAESRGTC-07ERBGSRGTC-09EZAJSRGTC-10ERBJS
Rheem RGRM/RGTM 90 Plus
RGRM-04RGRM-06RGRM-07RGRM-09RGRM-10RGRM-12RGTM-06RGTM-07RGTM-09RGTM-10
Source: Rheem (-)802P/(-)(-)80MDP Installation Instructions 92-24161-146-02, Sequence of Operation / Diagnostics Flowchart (Figure 33), p.39, 51. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.