Lennox Error Code Green OFF / Red SLOW flash: Low pressure fault (Heat Pump)
Lennox error code Green OFF / Red SLOW flash on a heat pump means: Low pressure fault. It is also called Lennox diagnostic code Green OFF / Red SLOW flash.
Homeowner? What Lennox code Green OFF / Red SLOW flash means for you
Check, then call Your heat pump is reporting: Low pressure fault. This is often caused by something simple. Try the safe checks below; if the code returns, book a service call before it turns into a no-heat or no-hot-water emergency.
Safe things you can check yourself
- Check the thermostat: right mode (Heat or Cool), set a few degrees past room temperature, and fresh batteries if it uses them.
- Check both breakers and the outdoor disconnect box beside the outdoor unit; all should be ON.
- Look at the air filter. If it is grey and clogged, replace it; a blocked filter causes many shutdowns.
- In winter, keep snow and ice off and away from the outdoor unit. A short defrost cycle with steam is normal.
- Try one reset: turn the power off for 30 seconds, then back on. If the code comes back, stop resetting and call a technician.
Call (647) 657-2977Book a service call
Licensed technicians serving Vaughan, Toronto and the GTA.
What does Lennox error code Green OFF / Red SLOW flash mean?
The low pressure switch (S87, opens at 25 +/- 5 psig, closes at 40 +/- 5 psig) opened and the control stopped the compressor and counted one strike. It is ignored during defrost, for 90 s after defrost, for 90 s after compressor start in TEST mode, and for 10 minutes of compressor run when ambient is below 15°F. Two LP trips in a row in heating start a defrost.
Applies to: Lennox EL16KP1 (Elite) and ML14KP1 (Merit) R-454B heat pumps, sizes -018 to -060, demand defrost control A108 (CMC1)
Common causes of Lennox code Green OFF / Red SLOW flash
- Restricted airflow over the indoor or outdoor coil (dirty coil, filter, blocked fan)
- Wrong refrigerant charge
- Wrong metering device installed or expansion valve not working properly
A technician checks these and 1 other possible causes on site before replacing any part.
Lennox models that use code Green OFF / Red SLOW flash
EL16KP1-018EL16KP1-024EL16KP1-030EL16KP1-036EL16KP1-042EL16KP1-048EL16KP1-060ML14KP1-018ML14KP1-024ML14KP1-030ML14KP1-036ML14KP1-042ML14KP1-048ML14KP1-060
Other Lennox Heat Pump codes
All Lennox Heat Pump error codes →
Lennox code Green OFF / Red SLOW flash: homeowner questions
What does Lennox code Green OFF / Red SLOW flash mean?
Low pressure fault. The low pressure switch (S87, opens at 25 +/- 5 psig, closes at 40 +/- 5 psig) opened and the control stopped the compressor and counted one strike. It is ignored during defrost, for 90 s after defrost, for 90 s after compressor start in…
Is it safe to keep using my heat pump with code Green OFF / Red SLOW flash?
It depends on the cause. This is often caused by something simple. Try the safe checks below; if the code returns, book a service call before it turns into a no-heat or no-hot-water emergency.
Can I reset Lennox code Green OFF / Red SLOW flash myself?
You can try one reset (power off for 30 seconds, then on). If Lennox code Green OFF / Red SLOW flash comes back, the cause is still there and a licensed technician should check it.
Who can fix Lennox code Green OFF / Red SLOW flash near me?
Aurora Star Tech Inc. repairs Lennox heat pumps in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.
Homeowner help: AC Running But Not Cooling: What to Check · Heat Pump Not Heating or Blowing Cold Air
Troubleshooting guides
- 2 flashes: HPS open ≥6 s; 3: discharge >263°F; 4: discharge <90°F after 1 h; 5: defrost failure; 6: discharge sensor short; 7: outdoor sensor open/short; 9: bonnet sensor fail All brands · Heat Pump
- Auxiliary heat indicator light is on All brands · Heat Pump
- Cleaning the outdoor unit finish All brands · Heat Pump
- Excess ice on outdoor coil All brands · Heat Pump
- Extremely high head pressure in heating (dual fuel) All brands · Heat Pump
- Insufficient heat in cold weather All brands · Heat Pump
- Liquid slugging / compressor damage in heating All brands · Heat Pump
- No mode change / wrong mode All brands · Heat Pump
Source: Lennox EL16KP1 Unit Information 100195 / ML14KP1 Unit Information 100108, Table 4 Demand Defrost Control (A108) Diagnostic LEDs, p.32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.