Lennox Error Code E429: Inverter DC link low voltage (inverter code 23) (AC)

Updated · by Aurora Star Tech Inc.

Lennox error code E429 on a air conditioner means: Inverter DC link low voltage (inverter code 23). It is also called Lennox diagnostic code E429.

High severityAir ConditionerAlso Heat Pump

Homeowner? What Lennox code E429 means for you

Call a technician Your air conditioner is reporting: Inverter DC link low voltage (inverter code 23). The air conditioner has locked out or cannot run properly. One reset is fine; if the code comes back, it needs a licensed technician to find the cause.

Safe things you can check yourself

  • Check the thermostat: right mode (Heat or Cool), set a few degrees past room temperature, and fresh batteries if it uses them.
  • Check both breakers and the outdoor disconnect box beside the outdoor unit; all should be ON.
  • Look at the air filter. If it is grey and clogged, replace it; a blocked filter causes many shutdowns.
  • Keep about 2 feet around the outdoor unit clear of leaves, grass and debris.
  • If you see ice on the pipes or the indoor coil, turn the system off and run only the fan for a few hours, then call a technician.
  • Try one reset: turn the power off for 30 seconds, then back on. If the code comes back, stop resetting and call a technician.

Call (647) 657-2977Book a service call

Licensed technicians serving Vaughan, Toronto and the GTA.

What does Lennox error code E429 mean?

On a compressor call the DC link did not rise above 180 VDC (2- and 3-ton) or 250 VDC (4- and 5-ton) within 30 seconds; unit stops. 10 times in 60 minutes = lockout. Inverter LED flash code 23 (red 2 flashes, green 3 flashes). S30/S40 thermostat alert code 429 (shown as E429 on the unit control display).

Applies to: Lennox communicating air conditioners incl. variable-capacity inverter units in S30/S40 smart thermostat systems

Common causes of Lennox code E429

  • Low input voltage
  • Loose U/V/W connections
  • Failed inverter, filter board or reactor

A technician checks these and 1 other possible causes on site before replacing any part.

Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Lennox models that use code E429

EL16KC1-018-230AEL16KC1-024-230AEL16KC1-030-230AEL16KC1-036-230AEL16KC1-041-230AEL16KC1-042-230AEL16KC1-047-230AEL16KC1-048-230AEL16KC1-060-230A

Other Lennox AC codes

CodeMeaning
E422Compressor top cap switch open
E423Inverter CT circuit fault (inverter code 40)
E424Liquid line sensor faulty
E426Excessive inverter alarms
E427Inverter DC peak fault (inverter code 21)
E428Inverter high main input current (inverter code 22)
E430Inverter compressor startup fail (inverter code 26)
E431Inverter PFC fault (inverter code 27)
E432Inverter DC link high voltage (inverter code 28)
E433Inverter compressor over-current (inverter code 29)
E434Inverter communication error to main control (inverter code 53)
E435Inverter EEPROM checksum fault (inverter code 60)

All Lennox Air Conditioner error codes →

Lennox code E429: homeowner questions

What does Lennox code E429 mean?

Inverter DC link low voltage (inverter code 23). On a compressor call the DC link did not rise above 180 VDC (2- and 3-ton) or 250 VDC (4- and 5-ton) within 30 seconds; unit stops. 10 times in 60 minutes = lockout. Inverter LED flash code 23 (red 2 flashes, green 3 flashes). S30/S40…

Is it safe to keep using my air conditioner with code E429?

It depends on the cause. The air conditioner has locked out or cannot run properly. One reset is fine; if the code comes back, it needs a licensed technician to find the cause.

Can I reset Lennox code E429 myself?

You can try one reset (power off for 30 seconds, then on). If Lennox code E429 comes back, the cause is still there and a licensed technician should check it.

Who can fix Lennox code E429 near me?

Aurora Star Tech Inc. repairs Lennox air conditioners in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.

Homeowner help: AC Running But Not Cooling: What to Check

Troubleshooting guides

Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.35. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency HVAC Service