KeepRite Error Code Amber LED off: Standby – no call (2-wire hookup or indoor unit unpowered) (Heat Pump)
KeepRite error code Amber LED off on a heat pump means: Standby - no call (2-wire hookup or indoor unit unpowered). It is also called KeepRite diagnostic code Amber LED off.
Homeowner? What KeepRite code Amber LED off means for you
Usually minor Your heat pump is reporting: Standby - no call (2-wire hookup or indoor unit unpowered). This code is usually informational or minor. The safe checks below often clear it; call us if it keeps showing up.
Safe things you can check yourself
- Check the thermostat: right mode (Heat or Cool), set a few degrees past room temperature, and fresh batteries if it uses them.
- Check both breakers and the outdoor disconnect box beside the outdoor unit; all should be ON.
- Look at the air filter. If it is grey and clogged, replace it; a blocked filter causes many shutdowns.
- In winter, keep snow and ice off and away from the outdoor unit. A short defrost cycle with steam is normal.
- Try one reset: turn the power off for 30 seconds, then back on. If the code comes back, stop resetting and call a technician.
Call (647) 657-2977Book a service call
Licensed technicians serving Vaughan, Toronto and the GTA.
What does KeepRite error code Amber LED off mean?
The amber status LED is dark. With only two thermostat wires the board loses power whenever there is no call, so no flash codes can be shown. It also looks like this if the indoor unit has no power. Normally nothing is wrong.
Applies to: *SA/*SH single-stage communicating board
KeepRite models that use code Amber LED off
Other KeepRite Heat Pump codes
All KeepRite Heat Pump error codes →
KeepRite code Amber LED off: homeowner questions
What does KeepRite code Amber LED off mean?
Standby - no call (2-wire hookup or indoor unit unpowered). The amber status LED is dark. With only two thermostat wires the board loses power whenever there is no call, so no flash codes can be shown. It also looks like this if the indoor unit has no power. Normally nothing is wrong.
Is it safe to keep using my heat pump with code Amber LED off?
Usually yes. Code Amber LED off is normally minor, but if it keeps coming back have it checked.
Can I reset KeepRite code Amber LED off myself?
You can try one reset (power off for 30 seconds, then on). If KeepRite code Amber LED off comes back, the cause is still there and a licensed technician should check it.
Who can fix KeepRite code Amber LED off near me?
Aurora Star Tech Inc. repairs KeepRite heat pumps in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.
Homeowner help: AC Running But Not Cooling: What to Check · Heat Pump Not Heating or Blowing Cold Air
Troubleshooting guides
- 2 flashes: HPS open ≥6 s; 3: discharge >263°F; 4: discharge <90°F after 1 h; 5: defrost failure; 6: discharge sensor short; 7: outdoor sensor open/short; 9: bonnet sensor fail All brands · Heat Pump
- Excess ice on outdoor coil All brands · Heat Pump
- Extremely high head pressure in heating (dual fuel) All brands · Heat Pump
- Insufficient heat in cold weather All brands · Heat Pump
- Liquid slugging / compressor damage in heating All brands · Heat Pump
- No mode change / wrong mode All brands · Heat Pump
- Odour at registers (dirty sock) All brands · Heat Pump
- Poor heating but OK cooling (or vice-versa) All brands · Heat Pump
- Service problem analysis (Amana chart excerpt) All brands · Heat Pump
- Subcooling too high All brands · Heat Pump
- Subcooling too low vs mfr target All brands · Heat Pump
- TXV bulb/diaphragm failure All brands · Heat Pump
- Water-source: coil freezing All brands · Heat Pump
- Won't change mode / both coils same temperature All brands · Heat Pump
- Wrong superheat after line-set change; poor capacity All brands · Heat Pump
- Force a defrost cycle or skip the 5-minute delay KeepRite · Heat Pump
- Forcing a defrost to test the board - KeepRite N4H4/R4H4/WCH4/NXH5 KeepRite · Heat Pump
- Outdoor unit will not run or will not defrost - KeepRite heat pump defrost board (FAST 1173636/1177927/1190281) KeepRite · Heat Pump
- Speed up the defrost timer for testing (J1 speed-up pins) KeepRite · Heat Pump
- Switch the post-defrost outdoor fan delay off or on KeepRite · Heat Pump
- Turn 230 V brown-out protection off or on KeepRite · Heat Pump
Source: KeepRite ICP split A-C + HP (R-410A & R-22) Application Guideline and Service Manual 421 08 5400 04, Table 13 Status Codes, p.46-47. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.