Rheem Furnace: No heat – POWER LED off

Updated · by Aurora Star Tech Inc.

No heat - POWER LED off on a Rheem furnace: When a Rheem 90 Plus condensing furnace (the (-)GRC/(-)GTC and 90RJ/90TJ) is dead on a heat call and the POWER LED on the integrated furnace control is dark, what I usually find is simply no power getting in, most often a tripped breaker or a door switch not made. Less often it is a bad transformer or a blown fuse on the board. Start at the panel and work toward the board.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Rheem (-)GRC/(-)GTC and 90RJ/90TJ 90 Plus condensing gas furnaces

Common causes of no heat - power led off

  • Breaker off or tripped
  • Blower door switch open because the door is off or not seated
  • No line power to the furnace
  • Failed transformer or blown IFC fuse

How to fix no heat - power led off: step by step

  1. WARNING: hazardous line voltage. Disconnect power before servicing; the work must be done by a trained, qualified service technician.
  2. Check the breaker and line power to the furnace, and the service switch if one is fitted
  3. Check the blower door switch is closed with the door installed properly; never defeat it
  4. Check the transformer and measure for 24 V at the IFC
  5. Check the IFC fuse, and if it blew, look for a shorted thermostat wire or accessory before replacing it
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Rheem Furnace codes

Models

96V

(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100

Rheem 90RJ/90TJ 90 Plus

90RJ0490RJ0690RJ0790RJ0990RJ1090RJ1290TJ0490TJ0690TJ0790TJ0990TJ1090TJ12

96MDV

96MDV06096MDV07096MDV08596MDV100

R96V/96MDV

96MDV115D50A

R95P

R95PA0401317MSAR95PA0601317MSAR95PA0701317MSAR95PA0851521MSAR95PA1001521MSAR95PA1151524MSA

Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)

R802PA050314MSAR802PA075417MSAR802PA100521MSAR802PA125524MSAR802PA150524MSA

RGPE/RGLE

RGLE-05(-)BMKRRGLE-07(-)AMKRRGLE-07(-)BRQRRGLE-10(-)BRMRRGLE-12(-)ARMRRGPE-05(-)BMKRRGPE-07(-)AMKRRGPE-07(-)BRQRRGPE-10(-)BRMRRGPE-12(-)ARMR

Rheem (-)GRC/(-)GTC 90 Plus

RGRC-04EMAESRGRC-06EMAESRGRC-07EMAESRGRC-07ERBGSRGRC-09EZAJSRGRC-10EZAJSRGTC-04EMAESRGTC-06EMAESRGTC-07ERBGSRGTC-09EZAJSRGTC-10ERBJS

Rheem RGRM/RGTM 90 Plus

RGRM-04RGRM-06RGRM-07RGRM-09RGRM-10RGRM-12RGTM-06RGTM-07RGTM-09RGTM-10

Source: Rheem (-)GRC/(-)GTC Installation Instructions 92-24161-88-00, Figure 56 IFC Troubleshooting Guide, p.54 (printed); Rheem 90RJ/90TJ Installation Instructions 92-24161-32-08, Figure 53, p.54. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.