Rheem Furnace: Inducer runs 60 seconds then off for 5 minutes
Inducer runs 60 seconds then off for 5 minutes on a Rheem furnace: R95P: pressure switch not proving.
Applies to: Rheem/Ruud (-)95P series 95% single-stage condensing gas furnace (R95PA)
Common causes of inducer runs 60 seconds then off for 5 minutes
- Blocked vent/intake
- Water in hoses
- Wind
- Bad pressure switch
How to fix inducer runs 60 seconds then off for 5 minutes: step by step
- Check pressure switch, hoses and wires.
- Check for blocked vent, excess vent length/elbows, blocked heat exchanger.
- Check switches/hoses for water.
- Check inducer is wired correctly.
- Look for wind opening the switch or intermittent switch operation.
If the unit shows an error code, look it up: Rheem Furnace codes
Models
Rheem 90RJ/90TJ 90 Plus
90RJ0490RJ0690RJ0790RJ0990RJ1090RJ1290TJ0490TJ0690TJ0790TJ0990TJ1090TJ12
R95P
R95PA0401317MSAR95PA0601317MSAR95PA0701317MSAR95PA0851521MSAR95PA1001521MSAR95PA1151524MSA
Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)
R802PA050314MSAR802PA075417MSAR802PA100521MSAR802PA125524MSAR802PA150524MSA
RGPE/RGLE
RGLE-05(-)BMKRRGLE-07(-)AMKRRGLE-07(-)BRQRRGLE-10(-)BRMRRGLE-12(-)ARMRRGPE-05(-)BMKRRGPE-07(-)AMKRRGPE-07(-)BRQRRGPE-10(-)BRMRRGPE-12(-)ARMR
Rheem (-)GRC/(-)GTC 90 Plus
RGRC-04EMAESRGRC-06EMAESRGRC-07EMAESRGRC-07ERBGSRGRC-09EZAJSRGRC-10EZAJSRGTC-04EMAESRGTC-06EMAESRGTC-07ERBGSRGTC-09EZAJSRGTC-10ERBJS
Rheem RGRM/RGTM 90 Plus
RGRM-04RGRM-06RGRM-07RGRM-09RGRM-10RGRM-12RGTM-06RGTM-07RGTM-09RGTM-10
Source: Rheem R95P Installation Instructions (ManualsLib 989115), Figure 49 IFC Troubleshooting Guide, p.96 (PDF p.100). Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.