| Alert 1 | Alert PCB was restored from factory defaults | Low |
| Alert 1 | Alert PCB was restored from factory defaults | Low |
| Alert 2 | Safety configuration parameters were restored from factory defaults | Low |
| Alert 2 | Safety configuration parameters were restored from factory defaults | Low |
| Alert 3 | Configuration parameters were restored from factory defaults | Low |
| Alert 3 | Configuration parameters were restored from factory defaults | Low |
| Alert 4 | Invalid Factory Invisibility PCB was detected | Low |
| Alert 4 | Invalid Factory Invisibility PCB was detected | Low |
| Alert 5 | Invalid Factory Range PCB was detected | Low |
| Alert 5 | Invalid Factory Range PCB was detected | Low |
| Alert 6 | Invalid range PCB record has been dropped | Low |
| Alert 6 | Invalid range PCB record has been dropped | Low |
| Alert 7 | EEPROM lockout history was initialized | Low |
| Alert 7 | EEPROM lockout history was initialized | Low |
| Alert 8 | Switched application annunciation data blocks | Low |
| Alert 8 | Switched application annunciation data blocks | Low |
| Alert 9 | Switched application configuration data blocks | Low |
| Alert 9 | Switched application configuration data blocks | Low |
| Alert 10 | Configuration was restored from factory defaults | Low |
| Alert 10 | Configuration was restored from factory defaults | Low |
| Alert 11 | Backup configuration settings was restored from active configuration | Low |
| Alert 11 | Backup configuration settings was restored from active configuration | Low |
| Alert 12 | Annunciation configuration was restored from factory defaults | Low |
| Alert 12 | Annunciation configuration was restored from factory defaults | Low |
| Alert 13 | Annunciation configuration was restored from backup | Low |
| Alert 13 | Annunciation configuration was restored from backup | Low |
| Alert 14 | Safety group verification table was restored from factory defaults | Low |
| Alert 14 | Safety group verification table was restored from factory defaults | Low |
| Alert 15 | Safety group verification table was updated | Low |
| Alert 15 | Safety group verification table was updated | Low |
| Alert 16 | Invalid Parameter PCB was detected | Low |
| Alert 16 | Invalid Parameter PCB was detected | Low |
| Alert 17 | Invalid Range PCB was detected | Low |
| Alert 17 | Invalid Range PCB was detected | Low |
| Alert 18 | Alarm silence time exceeded maximum | Low |
| Alert 18 | Alarm silence time exceeded maximum | Low |
| Alert 19 | Invalid safety group verification table was detected | Low |
| Alert 19 | Invalid safety group verification table was detected | Low |
| Alert 20 | Backdoor password could not be determined | Low |
| Alert 21 | Invalid safety group verification table was not accepted | Low |
| Alert 22 | CRC errors were found in application configuration data blocks | Low |
| Alert 23 | Backup Alert PCB was restored from active one | Low |
| Alert 25 | Lead Lag operation switch was turned OFF | Low |
| Alert 26 | Lead Lag operation switch was turned ON | Low |
| Alert 27 | Safety processor was reset | Low |
| Alert 27 | Safety processor was reset | Low |
| Alert 28 | Application processor was reset | Low |
| Alert 28 | Application processor was reset | Low |
| Alert 29 | Burner switch was turned OFF | Low |
| Alert 29 | Burner switch was turned OFF | Low |
| Alert 30 | Burner switch was turned ON | Low |
| Alert 30 | Burner switch was turned ON | Low |
| Alert 31 | Program Module (PM) was inserted into socket | Low |
| Alert 31 | Program Module (PM) was inserted into socket | Low |
| Alert 32 | Program Module (PM) was removed from socket | Low |
| Alert 32 | Program Module (PM) was removed from socket | Low |
| Alert 33 | Alert PCB was configured | Low |
| Alert 33 | Alert PCB was configured | Low |
| Alert 34 | Parameter PCB was configured | Low |
| Alert 34 | Parameter PCB was configured | Low |
| Alert 35 | Range PCB was configured | Low |
| Alert 35 | Range PCB was configured | Low |
| Alert 36 | Program Module (PM) incompatible with product was inserted into socket | Low |
| Alert 36 | Program Module (PM) incompatible with product was inserted into socket | Low |
| Alert 37 | Program Module application parameter revision differs from application processor | Low |
| Alert 37 | Program Module application parameter revision differs from application processor | Low |
| Alert 38 | Program Module safety parameter revision differs from safety processor | Low |
| Alert 38 | Program Module safety parameter revision differs from safety processor | Low |
| Alert 39 | PCB incompatible with product contained in Program Module | Low |
| Alert 39 | PCB incompatible with product contained in Program Module | Low |
| Alert 40 | Parameter PCB in Program Module is too large for product | Low |
| Alert 40 | Parameter PCB in Program Module is too large for product | Low |
| Alert 41 | Range PCB in Program Module was too large for product | Low |
| Alert 41 | Range PCB in Program Module was too large for product | Low |
| Alert 42 | Alert PCB in Program Module was too large for product | Low |
| Alert 42 | Alert PCB in Program Module was too large for product | Low |
| Alert 43 | IAS start check was forced on due to IAS enabled | Low |
| Alert 43 | IAS start check was forced on due to IAS enabled | Low |
| Alert 44 | Low voltage was detected in safety processor | Low |
| Alert 44 | Low voltage was detected in safety processor | Low |
| Alert 45 | High line frequency occurred | Low |
| Alert 45 | High line frequency occurred | Low |
| Alert 46 | Low line frequency occurred | Low |
| Alert 46 | Low line frequency occurred | Low |
| Alert 47 | Invalid subsystem reset request occurred | Low |
| Alert 47 | Invalid subsystem reset request occurred | Low |
| Alert 48 | Write large enumerated Modbus register value was not allowed | Low |
| Alert 48 | Write large enumerated Modbus register value was not allowed | Low |
| Alert 49 | Maximum cycle count was reached | Low |
| Alert 49 | Maximum cycle count was reached | Low |
| Alert 50 | Maximum hours count was reached | Low |
| Alert 50 | Maximum hours count was reached | Low |
| Alert 51 | Illegal Modbus write was attempted | Low |
| Alert 51 | Illegal Modbus write was attempted | Low |
| Alert 52 | Modbus write attempt was rejected (NOT ALLOWED) | Low |
| Alert 52 | Modbus write attempt was rejected (NOT ALLOWED) | Low |
| Alert 53 | Illegal Modbus read was attempted | Low |
| Alert 53 | Illegal Modbus read was attempted | Low |
| Alert 54 | Safety processor brown-out reset occurred | Low |
| Alert 54 | Safety processor brown-out reset occurred | Low |
| Alert 55 | Application processor watchdog reset occurred | Low |
| Alert 55 | Application processor watchdog reset occurred | Low |
| Alert 56 | Application processor brown-out reset occurred | Low |
| Alert 56 | Application processor brown-out reset occurred | Low |
| Alert 57 | Safety processor watchdog reset occurred | Low |
| Alert 57 | Safety processor watchdog reset occurred | Low |
| Alert 58 | Alarm was reset by the user at the control | Low |
| Alert 58 | Alarm was reset by the user at the control | Low |
| Alert 59 | Burner control firing rate was > absolute max rate | Low |
| Alert 59 | Burner control firing rate was > absolute max rate | Low |
| Alert 60 | Burner control firing rate was < absolute min rate | Low |
| Alert 60 | Burner control firing rate was < absolute min rate | Low |
| Alert 61 | Burner control firing rate was invalid, % vs. RPM | Low |
| Alert 61 | Burner control firing rate was invalid, % vs. RPM | Low |
| Alert 62 | Burner control was firing with no fan request | Low |
| Alert 62 | Burner control was firing with no fan request | Low |
| Alert 63 | Burner control rate (non-firing) was > absolute max rate | Low |
| Alert 63 | Burner control rate (non-firing) was > absolute max rate | Low |
| Alert 64 | Burner control rate (non-firing) was < absolute min rate | Low |
| Alert 64 | Burner control rate (non-firing) was < absolute min rate | Low |
| Alert 65 | Burner control rate (non-firing) was absent | Low |
| Alert 65 | Burner control rate (non-firing) was absent | Low |
| Alert 66 | Burner control rate (non-firing) was invalid, % vs. RPM | Low |
| Alert 66 | Burner control rate (non-firing) was invalid, % vs. RPM | Low |
| Alert 67 | Fan off cycle rate was invalid, % vs. RPM | Low |
| Alert 67 | Fan off cycle rate was invalid, % vs. RPM | Low |
| Alert 68 | Set point was over ridden due to sensor fault | Low |
| Alert 68 | Set point was over ridden due to sensor fault | Low |
| Alert 69 | Modulation was over ridden due to sensor fault | Low |
| Alert 69 | Modulation was over ridden due to sensor fault | Low |
| Alert 70 | No demand source was set due to demand priority conflicts | Low |
| Alert 70 | No demand source was set due to demand priority conflicts | Low |
| Alert 71 | CH 4-20mA signal was invalid. | Low |
| Alert 71 | CH 4-20mA signal was invalid. | Low |
| Alert 72 | Flame strength rate differential was invalid | Low |
| Alert 73 | Flame strength step rate was invalid | Low |
| Alert 74 | Periodic forced recycle | Low |
| Alert 74 | Periodic forced recycle | Low |
| Alert 75 | Absolute max fan speed was out of range | Low |
| Alert 75 | Absolute max fan speed was out of range | Low |
| Alert 76 | Absolute min fan speed was out of range | Low |
| Alert 76 | Absolute min fan speed was out of range | Low |
| Alert 77 | Fan gain down was invalid | Low |
| Alert 77 | Fan gain down was invalid | Low |
| Alert 78 | Fan gain up was invalid | Low |
| Alert 78 | Fan gain up was invalid | Low |
| Alert 79 | Fan minimum duty cycle was invalid | Low |
| Alert 79 | Fan minimum duty cycle was invalid | Low |
| Alert 80 | Fan pulses per revolution was invalid | Low |
| Alert 80 | Fan pulses per revolution was invalid | Low |
| Alert 81 | Fan PWM frequency was invalid | Low |
| Alert 81 | Fan PWM frequency was invalid | Low |
| Alert 84 | Lead Lag CH 4-20mA water temperature setting was invalid | Low |
| Alert 85 | No Lead Lag add stage error threshold was configured | Low |
| Alert 86 | No Lead Lag add stage detection time was configured | Low |
| Alert 87 | No Lead Lag drop stage error threshold was configured | Low |
| Alert 88 | No Lead Lag drop stage detection time was configured | Low |
| Alert 89 | Lead Lag all boiler off threshold was invalid | Low |
| Alert 90 | Modulation output type was invalid | Low |
| Alert 90 | Modulation output type was invalid | Low |
| Alert 91 | Firing rate control parameter was invalid | Low |
| Alert 91 | Firing rate control parameter was invalid | Low |
| Alert 92 | Forced rate was out of range vs. min/max modulation | Low |
| Alert 92 | Forced rate was out of range vs. min/max modulation | Low |
| Alert 93 | Forced rate was invalid, % vs. RPM | Low |
| Alert 93 | Forced rate was invalid, % vs. RPM | Low |
| Alert 94 | Slow start ramp value was invalid | Low |
| Alert 94 | Slow start ramp value was invalid | Low |
| Alert 95 | Slow start degrees value was invalid | Low |
| Alert 95 | Slow start degrees value was invalid | Low |
| Alert 96 | Slow start was ended due to outlet sensor fault | Low |
| Alert 96 | Slow start was ended due to outlet sensor fault | Low |
| Alert 97 | Slow start was end due to reference set point fault | Low |
| Alert 97 | Slow start was end due to reference set point fault | Low |
| Alert 98 | CH max modulation rate was invalid, % vs. RPM | Low |
| Alert 98 | CH max modulation rate was invalid, % vs. RPM | Low |
| Alert 99 | CH max modulation rate was > absolute max rate | Low |
| Alert 99 | CH max modulation rate was > absolute max rate | Low |
| Alert 100 | CH modulation range (max minus min) was too small (< 4% or 40 RPM) | Low |
| Alert 100 | CH modulation range (max minus min) was too small (< 4% or 40 RPM) | Low |
| Alert 101 | DHW max modulation rate was invalid, % vs. RPM | Low |
| Alert 101 | DHW max modulation rate was invalid, % vs. RPM | Low |
| Alert 102 | DHW max modulation rate was > absolute max rate | Low |
| Alert 102 | DHW max modulation rate was > absolute max rate | Low |
| Alert 103 | DHW modulation range (max minus min) was too small (< 4% or 40 RPM) | Low |
| Alert 103 | DHW modulation range (max minus min) was too small (< 4% or 40 RPM) | Low |
| Alert 104 | Min modulation rate was < absolute min rate | Low |
| Alert 104 | Min modulation rate was < absolute min rate | Low |
| Alert 105 | Min modulation rate was invalid, % vs. RPM | Low |
| Alert 105 | Min modulation rate was invalid, % vs. RPM | Low |
| Alert 106 | Manual rate was invalid, % vs. RPM | Low |
| Alert 106 | Manual rate was invalid, % vs. RPM | Low |
| Alert 107 | Slow start enabled, but forced rate was invalid | Low |
| Alert 107 | Slow start enabled, but forced rate was invalid | Low |
| Alert 108 | Analog output hysteresis was invalid | Low |
| Alert 108 | Analog output hysteresis was invalid | Low |
| Alert 109 | Analog modulation output type was invalid | Low |
| Alert 109 | Analog modulation output type was invalid | Low |
| Alert 110 | IAS open rate differential was invalid | Low |
| Alert 110 | IAS open rate differential was invalid | Low |
| Alert 111 | IAS open step rate was invalid | Low |
| Alert 111 | IAS open step rate was invalid | Low |
| Alert 112 | Mix max modulation rate was invalid, % vs. RPM | Low |
| Alert 113 | Mix max modulation rate was > absolute max or < absolute min rates | Low |
| Alert 114 | Mix modulation range (max minus min) was too small (< 4% or 40 RPM) | Low |
| Alert 115 | Fan was limited to its minimum duty cycle | Low |
| Alert 115 | Fan was limited to its minimum duty cycle | Low |
| Alert 116 | Manual rate was > CH max modulation rate | Low |
| Alert 116 | Manual rate was > CH max modulation rate | Low |
| Alert 117 | Manual rate was > DHW max modulation rate | Low |
| Alert 117 | Manual rate was > DHW max modulation rate | Low |
| Alert 118 | Manual rate was < min modulation rate | Low |
| Alert 118 | Manual rate was < min modulation rate | Low |
| Alert 119 | Manual rate in Standby was > absolute max rate | Low |
| Alert 119 | Manual rate in Standby was > absolute max rate | Low |
| Alert 120 | Modulation commanded rate was > CH max modulation rate | Low |
| Alert 120 | Modulation commanded rate was > CH max modulation rate | Low |
| Alert 121 | Modulation commanded rate was > DHW max modulation rate | Low |
| Alert 121 | Modulation commanded rate was > DHW max modulation rate | Low |
| Alert 122 | Modulation commanded rate was < min modulation rate | Low |
| Alert 122 | Modulation commanded rate was < min modulation rate | Low |
| Alert 123 | Modulation rate was limited due to outlet limit | Low |
| Alert 123 | Modulation rate was limited due to outlet limit | Low |
| Alert 124 | Modulation rate was limited due to Delta-T limit | Low |
| Alert 124 | Modulation rate was limited due to Delta-T limit | Low |
| Alert 125 | Modulation rate was limited due to stack limit | Low |
| Alert 125 | Modulation rate was limited due to stack limit | Low |
| Alert 126 | Modulation rate was limited due to anti-condensation | Low |
| Alert 126 | Modulation rate was limited due to anti-condensation | Low |
| Alert 127 | Fan Speed out of range in RUN | Low |
| Alert 127 | Fan Speed out of range in RUN | Low |
| Alert 128 | Modulation limited - air switch open | Low |
| Alert 128 | Modulation limited - air switch open | Low |
| Alert 129 | Slow start ramp setting of zero will result in no modulation rate change | Low |
| Alert 129 | Slow start ramp setting of zero will result in no modulation rate change | Low |
| Alert 130 | No forced rate was configured for slow start ramp | Low |
| Alert 130 | No forced rate was configured for slow start ramp | Low |
| Alert 131 | CH demand source was invalid | Low |
| Alert 131 | CH demand source was invalid | Low |
| Alert 132 | CH P-gain was invalid | Low |
| Alert 132 | CH P-gain was invalid | Low |
| Alert 133 | CH I-gain was invalid | Low |
| Alert 133 | CH I-gain was invalid | Low |
| Alert 134 | CH D-gain was invalid | Low |
| Alert 134 | CH D-gain was invalid | Low |
| Alert 135 | CH OFF hysteresis was invalid | Low |
| Alert 135 | CH OFF hysteresis was invalid | Low |
| Alert 136 | CH ON hysteresis was invalid | Low |
| Alert 136 | CH ON hysteresis was invalid | Low |
| Alert 137 | CH sensor type was invalid | Low |
| Alert 137 | CH sensor type was invalid | Low |
| Alert 138 | CH hysteresis step time was invalid | Low |
| Alert 138 | CH hysteresis step time was invalid | Low |
| Alert 139 | CH remote control parameter was invalid | Low |
| Alert 139 | CH remote control parameter was invalid | Low |
| Alert 140 | CH ODR not allowed with remote control | Low |
| Alert 140 | CH ODR not allowed with remote control | Low |
| Alert 146 | CH control was suspended due to fault | Low |
| Alert 146 | CH control was suspended due to fault | Low |
| Alert 147 | CH header temperature was invalid | Low |
| Alert 147 | CH header temperature was invalid | Low |
| Alert 148 | CH outlet temperature was invalid | Low |
| Alert 148 | CH outlet temperature was invalid | Low |
| Alert 149 | CH steam pressure was invalid | Low |
| Alert 149 | CH steam pressure was invalid | Low |
| Alert 151 | Minimum water temperature parameter was greater than setpoint | Low |
| Alert 152 | Minimum water temperature parameter was greater than time of day setpoint | Low |
| Alert 155 | CH modulation rate source parameter was invalid | Low |
| Alert 157 | DHW demand source was invalid | Low |
| Alert 157 | DHW demand source was invalid | Low |
| Alert 158 | DHW P-gain was invalid | Low |
| Alert 158 | DHW P-gain was invalid | Low |
| Alert 159 | DHW I-gain was invalid | Low |
| Alert 159 | DHW I-gain was invalid | Low |
| Alert 160 | DHW D-gain was invalid | Low |
| Alert 160 | DHW D-gain was invalid | Low |
| Alert 161 | DHW OFF hysteresis was invalid | Low |
| Alert 161 | DHW OFF hysteresis was invalid | Low |
| Alert 162 | DHW ON hysteresis was invalid | Low |
| Alert 162 | DHW ON hysteresis was invalid | Low |
| Alert 163 | DHW hysteresis step time was invalid | Low |
| Alert 163 | DHW hysteresis step time was invalid | Low |
| Alert 164 | DHW sensor type was invalid | Low |
| Alert 164 | DHW sensor type was invalid | Low |
| Alert 165 | Inlet sensor type was invalid for DHW | Low |
| Alert 165 | Inlet sensor type was invalid for DHW | Low |
| Alert 166 | Outlet sensor type was invalid for DHW | Low |
| Alert 166 | Outlet sensor type was invalid for DHW | Low |
| Alert 167 | DHW storage OFF hysteresis was invalid | Low |
| Alert 168 | DHW storage ON hysteresis was invalid | Low |
| Alert 169 | DHW modulation sensor type was invalid | Low |
| Alert 170 | DHW modulation sensor was not compatible for Auto mode | Low |
| Alert 171 | DHW control was suspended due to fault | Low |
| Alert 171 | DHW control was suspended due to fault | Low |
| Alert 172 | DHW temperature was invalid | Low |
| Alert 172 | DHW temperature was invalid | Low |
| Alert 173 | DHW inlet temperature was invalid | Low |
| Alert 173 | DHW inlet temperature was invalid | Low |
| Alert 174 | DHW outlet temperature was invalid | Low |
| Alert 174 | DHW outlet temperature was invalid | Low |
| Alert 175 | DHW high limit must be disabled for Auto mode | Low |
| Alert 176 | DHW sensor type was not compatible for Auto mode | Low |
| Alert 177 | DHW priority source setting was invalid | Low |
| Alert 178 | DHW priority method setting was invalid | Low |
| Alert 179 | CH S5 (J8-11) sensor was invalid | Low |
| Alert 180 | CH Inlet temperature was invalid | Low |
| Alert 181 | CH S10 (J10-7) sensor was invalid | Low |
| Alert 182 | Lead Lag CH setpoint source was invalid | Low |
| Alert 183 | Lead Lag P-gain was invalid | Low |
| Alert 183 | Lead Lag P-gain was invalid | Low |
| Alert 184 | Lead Lag I-gain was invalid | Low |
| Alert 184 | Lead Lag I-gain was invalid | Low |
| Alert 185 | Lead Lag D-gain was invalid | Low |
| Alert 185 | Lead Lag D-gain was invalid | Low |
| Alert 186 | Lead Lag OFF hysteresis was invalid | Low |
| Alert 186 | Lead Lag OFF hysteresis was invalid | Low |
| Alert 187 | Lead Lag ON hysteresis was invalid | Low |
| Alert 187 | Lead Lag ON hysteresis was invalid | Low |
| Alert 188 | Lead Lag slave enable was invalid | Low |
| Alert 188 | Lead Lag slave enable was invalid | Low |
| Alert 189 | Lead Lag hysteresis step time was invalid | Low |
| Alert 189 | Lead Lag hysteresis step time was invalid | Low |
| Alert 190 | No Lead Lag Modbus port was assigned | Low |
| Alert 191 | Lead Lag base load common setting was invalid | Low |
| Alert 192 | Lead Lag DHW demand switch setting was invalid | Low |
| Alert 193 | Lead Lag Mix demand switch setting was invalid | Low |
| Alert 194 | Lead Lag modulation sensor setting was invalid | Low |
| Alert 195 | Lead Lag backup modulation sensor setting was invalid | Low |
| Alert 196 | Lead Lag slave mode setting was invalid | Low |
| Alert 197 | Lead Lag rate allocation setting was invalid | Low |
| Alert 198 | Lead selection setting was invalid | Low |
| Alert 204 | Lead Lag master was suspended due to fault | Low |
| Alert 205 | Lead Lag slave was suspended due to fault | Low |
| Alert 206 | Lead-lag header temperature invalid | Low |
| Alert 206 | Lead-lag header temperature invalid | Low |
| Alert 207 | Lead Lag was suspended due to no enabled Program Module installed | Low |
| Alert 208 | Lead Lag slave session has timed out | Low |
| Alert 222 | CH frost protection temperature was invalid | Low |
| Alert 223 | CH frost protection inlet temperature was invalid | Low |
| Alert 224 | DHW frost protection temperature was invalid | Low |
| Alert 231 | LL set point was invalid | Low |
| Alert 232 | LL time of day set point was invalid | Low |
| Alert 233 | Lead-lag outdoor temperature invalid | Low |
| Alert 233 | Lead-lag outdoor temperature invalid | Low |
| Alert 234 | LL ODR time of day set point was invalid | Low |
| Alert 235 | LL ODR time of day set point exceeded normal set point | Low |
| Alert 236 | LL max outdoor set point was invalid | Low |
| Alert 237 | LL min outdoor set point was invalid | Low |
| Alert 238 | LL min water set point was invalid | Low |
| Alert 239 | LL outdoor temperature range was too small (minimum 12 C / 22 F) | Low |
| Alert 240 | LL water temperature range was too small (minimum 12 C / 22 F) | Low |
| Alert 246 | CH set point was invalid | Low |
| Alert 247 | CH time of day set point was invalid | Low |
| Alert 248 | CH outdoor temperature invalid | Low |
| Alert 248 | CH outdoor temperature invalid | Low |
| Alert 249 | CH ODR time of day setpoint was invalid | Low |
| Alert 250 | CH ODR time of day set point exceeds normal set point | Low |
| Alert 251 | CH max outdoor set point was invalid | Low |
| Alert 252 | CH min outdoor setp oint was invalid | Low |
| Alert 253 | CH min water set point was invalid | Low |
| Alert 254 | CH outdoor temperature range was too small (minimum 12 C / 22 F) | Low |
| Alert 255 | CH water temperature range was too small (minimum 12 C / 22 F) | Low |
| Alert 261 | DHW set point was invalid | Low |
| Alert 262 | DHW time of day set point was invalid | Low |
| Alert 272 | Abnormal Recycle: Pressure sensor fault | Low |
| Alert 273 | Abnormal Recycle: Safety relay drive test failed | Low |
| Alert 274 | Abnormal Recycle: Demand off during Pilot Flame Establishing Period | Low |
| Alert 275 | Abnormal Recycle: LCI off during Drive to Purge Rate | Low |
| Alert 276 | Abnormal Recycle: LCI off during Measured Purge Time | Low |
| Alert 277 | Abnormal Recycle: LCI off during Drive to Light off Rate | Low |
| Alert 278 | Abnormal Recycle: LCI off during Pre-Ignition test | Low |
| Alert 279 | Abnormal Recycle: LCI off during Pre-Ignition time | Low |
| Alert 280 | Abnormal Recycle: LCI off during Main Flame Establishing Period | Low |
| Alert 281 | Abnormal Recycle: LCI off during Ignition period | Low |
| Alert 282 | Abnormal Recycle: Demand off during Drive to Purge Rate | Low |
| Alert 283 | Abnormal Recycle: Demand off during Measured Purge Time | Low |
| Alert 284 | Abnormal Recycle: Demand off during Drive to Light off Rate | Low |
| Alert 285 | Abnormal Recycle: Demand off during Pre-Ignition test | Low |
| Alert 286 | Abnormal Recycle: Demand off during Pre-Ignition time | Low |
| Alert 287 | Abnormal Recycle: Flame was on during Safe Start check | Low |
| Alert 288 | Abnormal Recycle: Flame was on during Drive to Purge Rate | Low |
| Alert 289 | Abnormal Recycle: Flame was on during Measured Purge Time | Low |
| Alert 290 | Abnormal Recycle: Flame was on during Drive to Light off Rate | Low |
| Alert 291 | Abnormal Recycle: Flame was not on at end of Ignition period | Low |
| Alert 292 | Abnormal Recycle: Flame was lost during Main Flame Establishing Period | Low |
| Alert 293 | Abnormal Recycle: Flame was lost early in Run | Low |
| Alert 294 | Abnormal Recycle: Flame was lost during Run | Low |
| Alert 295 | Abnormal Recycle: Leakage test failed | Low |
| Alert 296 | Abnormal Recycle: Interrupted air flow switch was off during Drive to Purge Rate | Low |
| Alert 297 | Abnormal Recycle: Interrupted air flow switch was off during Measured Purge Time | Low |
| Alert 298 | Abnormal Recycle: Interrupted air flow switch was off during Drive to Light off Rate | Low |
| Alert 299 | Abnormal Recycle: Interrupted air flow switch was off during Pre-Ignition test | Low |
| Alert 300 | Abnormal Recycle: Interrupted air flow switch was off during Pre-Ignition time | Low |
| Alert 301 | Abnormal Recycle: Interrupted air flow switch was off during Main Flame Establishing Period | Low |
| Alert 302 | Abnormal Recycle: Ignition failed due to interrupted air flow switch was off | Low |
| Alert 303 | Abnormal Recycle: ILK off during Drive to Purge Rate | Low |
| Alert 304 | Abnormal Recycle: ILK off during Measured Purge Time | Low |
| Alert 305 | Abnormal Recycle: ILK off during Drive to Light off Rate | Low |
| Alert 306 | Abnormal Recycle: ILK off during Pre-Ignition test | Low |
| Alert 307 | Abnormal Recycle: ILK off during Pre-Ignition time | Low |
| Alert 308 | Abnormal Recycle: ILK off during Main Flame Establishing Period | Low |
| Alert 309 | Abnormal Recycle: ILK off during Ignition period | Low |
| Alert 310 | Run was terminated due to ILK was off | Low |
| Alert 311 | Run was terminated due to interrupted air flow switch was off | Low |
| Alert 312 | Stuck reset switch | Low |
| Alert 313 | Run was terminated due to fan failure | Low |
| Alert 314 | Abnormal Recycle: Fan failed during Drive to Purge Rate | Low |
| Alert 315 | Abnormal Recycle: Fan failed during Measured Purge Time | Low |
| Alert 316 | Abnormal Recycle: Fan failed during Drive to Light off Rate | Low |
| Alert 317 | Abnormal Recycle: Fan failed during Pre-Ignition test | Low |
| Alert 318 | Abnormal Recycle: Fan failed during Pre-Ignition time | Low |
| Alert 319 | Abnormal Recycle: Fan failed during Ignition period | Low |
| Alert 320 | Abnormal Recycle: Fan failed during Main Flame Establishing Period | Low |
| Alert 321 | Abnormal Recycle: Main Valve off after 10 seconds of RUN | Low |
| Alert 322 | Abnormal Recycle: Pilot Valve off after 10 seconds of RUN | Low |
| Alert 323 | Abnormal Recycle: Safety Relay off after 10 seconds of RUN | Low |
| Alert 324 | Abnormal Recycle: Hardware flame bias | Low |
| Alert 325 | Abnormal Recycle: Hardware static flame | Low |
| Alert 326 | Abnormal Recycle: Hardware flame current invalid | Low |
| Alert 327 | Abnormal Recycle: Hardware flame rod short | Low |
| Alert 328 | Abnormal Recycle: Hardware invalid power | Low |
| Alert 329 | Abnormal Recycle: Hardware invalid AC line | Low |
| Alert 330 | Abnormal Recycle: Hardware SLO flame ripple | Low |
| Alert 331 | Abnormal Recycle: Hardware SLO flame sample | Low |
| Alert 332 | Abnormal Recycle: Hardware SLO flame bias range | Low |
| Alert 333 | Abnormal Recycle: Hardware SLO flame bias heat | Low |
| Alert 334 | Abnormal Recycle: Hardware SLO spark stuck | Low |
| Alert 335 | Abnormal Recycle: Hardware SLO spark changed | Low |
| Alert 336 | Abnormal Recycle: Hardware SLO static flame | Low |
| Alert 337 | Abnormal Recycle: Hardware SLO rod shorted | Low |
| Alert 338 | Abnormal Recycle: Hardware SLO AD linearity | Low |
| Alert 339 | Abnormal Recycle: Hardware SLO bias not set | Low |
| Alert 340 | Abnormal Recycle: Hardware SLO bias shorted | Low |
| Alert 341 | Abnormal Recycle: Hardware SLO electronics | Low |
| Alert 342 | Abnormal Recycle: Hardware processor clock | Low |
| Alert 343 | Abnormal Recycle: Hardware AC phase | Low |
| Alert 344 | Abnormal Recycle: Hardware A2D mismatch | Low |
| Alert 345 | Abnormal Recycle: Hardware VSNSR A2D | Low |
| Alert 346 | Abnormal Recycle: Hardware 28V A2D | Low |
| Alert 347 | Abnormal Recycle: Hardware HFS IAS shorted | Low |
| Alert 348 | Abnormal Recycle: Hardware PII INTLK shorted | Low |
| Alert 349 | Abnormal Recycle: Hardware HFS LCI shorted | Low |
| Alert 350 | Abnormal Recycle: Hardware HFS LFS shorted | Low |
| Alert 351 | Abnormal Recycle: Invalid zero crossing | Low |
| Alert 352 | Abnormal Recycle: fault stack sensor | Low |
| Alert 353 | Abnormal Recycle: stack limit | Low |
| Alert 354 | Abnormal Recycle: delta T limit | Low |
| Alert 355 | Abnormal Recycle: fault outlet sensor | Low |
| Alert 356 | Abnormal Recycle: outlet high limit | Low |
| Alert 357 | Abnormal Recycle: fault DHW sensor | Low |
| Alert 358 | Abnormal Recycle: DHW high limit | Low |
| Alert 359 | Abnormal Recycle: fault inlet sensor | Low |
| Alert 360 | Abnormal Recycle: Check Parameters Failed | Low |
| Alert 361 | Internal error: No factory parameters were detected in control | Low |
| Alert 362 | Internal error: PID iteration frequency was invalid | Low |
| Alert 363 | Internal error: Demand-Rate interval time was invalid | Low |
| Alert 364 | Internal error: Factory calibration parameter for modulation was invalid | Low |
| Alert 365 | Internal error: CH PID P-scaler was invalid | Low |
| Alert 366 | Internal error: CH PID I-scaler was invalid | Low |
| Alert 367 | Internal error: CH PID D-scaler was invalid | Low |
| Alert 368 | Internal error: DHW PID P-scaler was invalid | Low |
| Alert 369 | Internal error: DHW PID I-scaler was invalid | Low |
| Alert 370 | Internal error: DHW PID D-scaler was invalid | Low |
| Alert 371 | Internal error: Lead Lag master PID P-scaler was invalid | Low |
| Alert 372 | Internal error: Lead Lag master PID I-scaler was invalid | Low |
| Alert 373 | Internal error: Lead Lag master PID D-scaler was invalid | Low |
| Alert 448 | Flame too low - burner shut down | Medium |
| Alert 449 | Modulation limited by flame strength | Low |
| Alert 449 | Modulation limited by flame strength | Low |
| Alert 460 | LCI demand lost in run | Low |
| Alert 461 | Demand lost in run | Low |
| Alert 462 | STAT demand lost in run | Low |
| Alert 463 | Demand lost in run due to no flame | Low |
| Alert 467 | Internal error: EEPROM write was attempted before EEPROM was initialized | Low |
| Alert 468 | Internal error: EEPROM cycle count address was invalid | Low |
| Alert 469 | Internal error: EEPROM days count address was invalid | Low |
| Alert 470 | Internal error: EEPROM hours count address was invalid | Low |
| Alert 471 | Internal error: Lockout record EEPROM index was invalid | Low |
| Alert 472 | Internal error: Request to write PM status was invalid | Low |
| Alert 473 | Internal error: PM parameter address was invalid | Low |
| Alert 474 | Internal error: PM safety parameter address was invalid | Low |
| Alert 475 | Internal error: Invalid record in lockout history was removed | Low |
| Alert 476 | Internal error: EEPROM write buffer was full | Low |
| Alert 477 | Internal error: Data too large was not written to EEPROM | Low |
| Alert 478 | Internal error: Safety key bit 0 was incorrect | Low |
| Alert 479 | Internal error: Safety key bit 1 was incorrect | Low |
| Alert 480 | Internal error: Safety key bit 2 was incorrect | Low |
| Alert 481 | Internal error: Safety key bit 3 was incorrect | Low |
| Alert 482 | Internal error: Safety key bit 4 was incorrect | Low |
| Alert 483 | Internal error: Safety key bit 5 was incorrect | Low |
| Alert 484 | Internal error: Safety key bit 6 was incorrect | Low |
| Alert 485 | Internal error: Safety key bit 7 was incorrect | Low |
| Alert 486 | Internal error: Safety key bit 8 was incorrect | Low |
| Alert 487 | Internal error: Safety key bit 9 was incorrect | Low |
| Alert 488 | Internal error: Safety key bit 10 was incorrect | Low |
| Alert 489 | Internal error: Safety key bit 11 was incorrect | Low |
| Alert 490 | Internal error: Safety key bit 12 was incorrect | Low |
| Alert 491 | Internal error: Safety key bit 13 was incorrect | Low |
| Alert 492 | Internal error: Safety key bit 14 was incorrect | Low |
| Alert 493 | Internal error: Safety key bit 15 was incorrect | Low |
| Alert 494 | Internal error: Safety relay timeout | Low |
| Alert 495 | Internal error: Safety relay commanded off | Low |
| Alert 496 | Internal error: Unknown safety error occurred | Low |
| Alert 497 | Internal error: Safety timer was corrupt | Low |
| Alert 498 | Internal error: Safety timer was expired | Low |
| Alert 499 | Internal error: Safety timings | Low |
| Alert 500 | Internal error: Safety shutdown | Low |
| Hold / Lockout 9 | Flame bias out of range | High |
| Hold / Lockout 9 | Flame bias out of range | High |
| Hold / Lockout 13 | Internal fault: PII shorted to ILK | High |
| Hold / Lockout 13 | Internal fault: PII shorted to ILK | High |
| Hold / Lockout 14 | Internal fault: HFS shorted to LCI | High |
| Hold / Lockout 14 | Internal fault: HFS shorted to LCI | High |
| Hold / Lockout 67 | ILK off - interlock string open | Critical |
| Hold / Lockout 67 | ILK off - interlock string open | Critical |
| Hold / Lockout 79 | Outlet high limit | Critical |
| Hold / Lockout 79 | Outlet high limit | Critical |
| Hold / Lockout 81 | Delta T limit | High |
| Hold / Lockout 81 | Delta T limit | High |
| Hold / Lockout 85 | Inlet/outlet inversion limit | High |
| Hold / Lockout 85 | Inlet/outlet inversion limit | High |
| Hold / Lockout 88 | Outlet temperature rise limit | High |
| Hold / Lockout 88 | Outlet temperature rise limit | High |
| Hold / Lockout 105 | Flame detected out of sequence | High |
| Hold / Lockout 105 | Flame detected out of sequence | High |
| Hold / Lockout 128 | Fan speed failed during pre-purge | High |
| Hold / Lockout 128 | Fan speed failed during pre-purge | High |
| Hold / Lockout 129 | Fan speed failed during pre-ignition | High |
| Hold / Lockout 129 | Fan speed failed during pre-ignition | High |
| Hold / Lockout 130 | Fan speed failed during ignition | High |
| Hold / Lockout 130 | Fan speed failed during ignition | High |
| Hold / Lockout 149 | Flame detected | High |
| Hold / Lockout 149 | Flame detected | High |
| Hold / Lockout 151 | High fire switch ON | High |
| Hold / Lockout 151 | High fire switch ON | High |
| Hold / Lockout 152 | Combustion pressure ON | High |
| Hold / Lockout 152 | Combustion pressure ON | High |
| Hold / Lockout 153 | Combustion pressure OFF | High |
| Hold / Lockout 153 | Combustion pressure OFF | High |
| Hold / Lockout 154 | Purge fan switch ON | High |
| Hold / Lockout 154 | Purge fan switch ON | High |
| Hold / Lockout 155 | Purge fan switch OFF | High |
| Hold / Lockout 155 | Purge fan switch OFF | High |
| Hold / Lockout 156 | Combustion pressure and Flame ON | High |
| Hold / Lockout 156 | Combustion pressure and Flame ON | High |
| Hold / Lockout 240 | Invalid Outdoor connector type setting | High |
| Hold / Lockout 243 | Invalid UV with spark interference not compatible with Igniter on throughout | High |
| Hold 3 | Internal fault: Hardware fault | Medium |
| Hold 3 | Internal fault: Hardware fault | Medium |
| Hold 4 | Internal fault: Safety Relay key feedback error | Medium |
| Hold 4 | Internal fault: Safety Relay key feedback error | Medium |
| Hold 5 | Internal fault: Unstable power (DCDC) output | Medium |
| Hold 5 | Internal fault: Unstable power (DCDC) output | Medium |
| Hold 6 | Internal fault: Invalid processor clock | Medium |
| Hold 6 | Internal fault: Invalid processor clock | Medium |
| Hold 7 | Internal fault: Safety relay drive error | Medium |
| Hold 7 | Internal fault: Safety relay drive error | Medium |
| Hold 8 | Internal fault: Zero crossing not detected | Medium |
| Hold 8 | Internal fault: Zero crossing not detected | Medium |
| Hold 12 | Internal fault: Safety relay drive cap short | Medium |
| Hold 12 | Internal fault: Safety relay drive cap short | Medium |
| Hold 20 | Internal fault: Flame ripple and overflow | Medium |
| Hold 20 | Internal fault: Flame ripple and overflow | Medium |
| Hold 21 | Internal fault: Flame number of sample mismatch | Medium |
| Hold 21 | Internal fault: Flame number of sample mismatch | Medium |
| Hold 22 | Internal fault: Flame bias out of range | Medium |
| Hold 22 | Internal fault: Flame bias out of range | Medium |
| Hold 23 | Internal fault: Bias changed since heating cycle starts | Medium |
| Hold 23 | Internal fault: Bias changed since heating cycle starts | Medium |
| Hold 24 | Internal fault: Spark voltage stuck low or high | Medium |
| Hold 24 | Internal fault: Spark voltage stuck low or high | Medium |
| Hold 25 | Internal fault: Spark voltage changed too much during flame sensing time | Medium |
| Hold 25 | Internal fault: Spark voltage changed too much during flame sensing time | Medium |
| Hold 26 | Internal fault: Static flame ripple | Medium |
| Hold 26 | Internal fault: Static flame ripple | Medium |
| Hold 27 | Flame rod shorted to ground | Medium |
| Hold 27 | Flame rod shorted to ground | Medium |
| Hold 28 | Internal fault: A/D linearity test fails | Medium |
| Hold 28 | Internal fault: A/D linearity test fails | Medium |
| Hold 29 | Internal fault: Flame bias cannot be set in range | Medium |
| Hold 29 | Internal fault: Flame bias cannot be set in range | Medium |
| Hold 30 | Internal fault: Flame bias shorted to adjacent pin | Medium |
| Hold 30 | Internal fault: Flame bias shorted to adjacent pin | Medium |
| Hold 31 | Internal fault: SLO electronics unknown error | Medium |
| Hold 31 | Internal fault: SLO electronics unknown error | Medium |
| Hold 47 | Flame rod to ground leakage | Medium |
| Hold 47 | Flame rod to ground leakage | Medium |
| Hold 48 | Static flame (not flickering) | Medium |
| Hold 48 | Static flame (not flickering) | Medium |
| Hold 49 | 24VAC voltage low/high | Medium |
| Hold 49 | 24VAC voltage low/high | Medium |
| Hold 50 | Modulation fault | Medium |
| Hold 50 | Modulation fault | Medium |
| Hold 51 | Pump fault | Medium |
| Hold 51 | Pump fault | Medium |
| Hold 52 | Motor tachometer fault | Medium |
| Hold 52 | Motor tachometer fault | Medium |
| Hold 61 | Anti short-cycle delay | Low |
| Hold 61 | Anti short-cycle delay | Low |
| Hold 62 | Fan speed not proved | Medium |
| Hold 62 | Fan speed not proved | Medium |
| Hold 63 | LCI off (limit control input) | Medium |
| Hold 63 | LCI off (limit control input) | Medium |
| Hold 65 | Interrupted air switch off | Medium |
| Hold 65 | Interrupted air switch off | Medium |
| Hold 66 | Interrupted air switch on | Medium |
| Hold 66 | Interrupted air switch on | Medium |
| Hold 69 | Pilot test hold | Medium |
| Hold 69 | Pilot test hold | Medium |
| Hold 70 | Wait for leakage test completion | Medium |
| Hold 70 | Wait for leakage test completion | Medium |
| Hold 78 | Demand lost in run | Medium |
| Hold 78 | Demand lost in run | Medium |
| Hold 91 | Inlet sensor fault | Medium |
| Hold 91 | Inlet sensor fault | Medium |
| Hold 92 | Outlet sensor fault | Medium |
| Hold 92 | Outlet sensor fault | Medium |
| Hold 93 | DHW sensor fault | Medium |
| Hold 93 | DHW sensor fault | Medium |
| Hold 94 | Header sensor fault | Medium |
| Hold 94 | Header sensor fault | Medium |
| Hold 95 | Stack sensor fault | Medium |
| Hold 95 | Stack sensor fault | Medium |
| Hold 96 | Outdoor sensor fault | Medium |
| Hold 96 | Outdoor sensor fault | Medium |
| Hold 100 | Pressure sensor fault | Medium |
| Hold 100 | Pressure sensor fault | Medium |
| Hold 110 | Ignition failure occurred | Critical |
| Hold 110 | Ignition failure occurred | Critical |
| Hold 111 | Flame current lower than WEAK threshold | Medium |
| Hold 111 | Flame current lower than WEAK threshold | Medium |
| Hold 118 | Controller interaction system fault | Medium |
| Hold 119 | Controller interaction communications fault | Medium |
| Hold 124 | High fire switch OFF | Medium |
| Hold 124 | High fire switch OFF | Medium |
| Hold 125 | High fire switch stuck ON | Medium |
| Hold 125 | High fire switch stuck ON | Medium |
| Hold 126 | Low fire switch OFF | Medium |
| Hold 126 | Low fire switch OFF | Medium |
| Hold 127 | Low fire switch stuck ON | Medium |
| Hold 127 | Low fire switch stuck ON | Medium |
| Hold 131 | Fan movement detected during standby | Medium |
| Hold 131 | Fan movement detected during standby | Medium |
| Hold 132 | Fan speed failed during run | Medium |
| Hold 132 | Fan speed failed during run | Medium |
| Hold 136 | Interrupted Airflow Switch failed to close | Medium |
| Hold 136 | Interrupted Airflow Switch failed to close | Medium |
| Hold 137 | ILK failed to close | Medium |
| Hold 137 | ILK failed to close | High |
| Hold 150 | Flame not detected | Medium |
| Hold 150 | Flame not detected | Medium |
| Lockout 1 | Unconfigured safety data | High |
| Lockout 1 | Unconfigured safety data | High |
| Lockout 2 | Waiting for safety data verification | High |
| Lockout 2 | Waiting for safety data verification | High |
| Lockout 10 | Internal fault: Invalid Burner control state | High |
| Lockout 10 | Internal fault: Invalid Burner control state | High |
| Lockout 11 | Internal fault: Invalid Burner control state flag | High |
| Lockout 11 | Internal fault: Invalid Burner control state flag | High |
| Lockout 15 | Internal fault: Safety relay test failed due to feedback ON | High |
| Lockout 15 | Internal fault: Safety relay test failed due to feedback ON | High |
| Lockout 16 | Internal fault: Safety relay test failed due to safety relay OFF | High |
| Lockout 16 | Internal fault: Safety relay test failed due to safety relay OFF | High |
| Lockout 17 | Internal fault: Safety relay test failed due to safety relay not OFF | High |
| Lockout 17 | Internal fault: Safety relay test failed due to safety relay not OFF | High |
| Lockout 18 | Internal fault: Safety relay test failed due to feedback not ON | High |
| Lockout 18 | Internal fault: Safety relay test failed due to feedback not ON | High |
| Lockout 19 | Internal fault: Safety RAM write | High |
| Lockout 19 | Internal fault: Safety RAM write | High |
| Lockout 32 | Internal fault: Safety Key 0 | High |
| Lockout 32 | Internal fault: Safety Key 0 | High |
| Lockout 33 | Internal fault: Safety Key 1 | High |
| Lockout 33 | Internal fault: Safety Key 1 | High |
| Lockout 34 | Internal fault: Safety Key 2 | High |
| Lockout 34 | Internal fault: Safety Key 2 | High |
| Lockout 35 | Internal fault: Safety Key 3 | High |
| Lockout 35 | Internal fault: Safety Key 3 | High |
| Lockout 36 | Internal fault: Safety Key 4 | High |
| Lockout 36 | Internal fault: Safety Key 4 | High |
| Lockout 37 | Internal fault: Safety Key 5 | High |
| Lockout 37 | Internal fault: Safety Key 5 | High |
| Lockout 38 | Internal fault: Safety Key 6 | High |
| Lockout 38 | Internal fault: Safety Key 6 | High |
| Lockout 39 | Internal fault: Safety Key 7 | High |
| Lockout 39 | Internal fault: Safety Key 7 | High |
| Lockout 40 | Internal fault: Safety Key 8 | High |
| Lockout 40 | Internal fault: Safety Key 8 | High |
| Lockout 41 | Internal fault: Safety Key 9 | High |
| Lockout 41 | Internal fault: Safety Key 9 | High |
| Lockout 42 | Internal fault: Safety Key 10 | High |
| Lockout 42 | Internal fault: Safety Key 10 | High |
| Lockout 43 | Internal fault: Safety Key 11 | High |
| Lockout 43 | Internal fault: Safety Key 11 | High |
| Lockout 44 | Internal fault: Safety Key 12 | High |
| Lockout 44 | Internal fault: Safety Key 12 | High |
| Lockout 45 | Internal fault: Safety Key 13 | High |
| Lockout 45 | Internal fault: Safety Key 13 | High |
| Lockout 46 | Internal fault: Safety Key 14 | High |
| Lockout 46 | Internal fault: Safety Key 14 | High |
| Lockout 53 | AC inputs phase reversed | High |
| Lockout 53 | AC inputs phase reversed | High |
| Lockout 54 | Safety GVT model ID doesn���t match application���s model ID | High |
| Lockout 55 | Application configuration data block CRC errors | High |
| Lockout 58 | Internal fault: HFS shorted to IAS | High |
| Lockout 58 | Internal fault: HFS shorted to IAS | High |
| Lockout 59 | Internal fault: Mux pin shorted | High |
| Lockout 59 | Internal fault: Mux pin shorted | High |
| Lockout 60 | Internal fault: HFS shorted to LFS | High |
| Lockout 60 | Internal fault: HFS shorted to LFS | High |
| Lockout 71 | Input power frequency mismatch | High |
| Lockout 82 | Stack limit | Critical |
| Lockout 82 | Stack limit | Critical |
| Lockout 97 | Internal fault: A2D mismatch | High |
| Lockout 97 | Internal fault: A2D mismatch | High |
| Lockout 98 | Internal fault: Exceeded VSNSR voltage tolerance | High |
| Lockout 98 | Internal fault: Exceeded VSNSR voltage tolerance | High |
| Lockout 99 | Internal fault: Exceeded 28V voltage tolerance | High |
| Lockout 99 | Internal fault: Exceeded 28V voltage tolerance | High |
| Lockout 106 | Flame lost in MFEP | High |
| Lockout 106 | Flame lost in MFEP | High |
| Lockout 107 | Flame lost early in run | High |
| Lockout 107 | Flame lost early in run | High |
| Lockout 108 | Flame lost in run | High |
| Lockout 108 | Flame lost in run | High |
| Lockout 109 | Ignition failed | Critical |
| Lockout 109 | Ignition failed | Critical |
| Lockout 112 | Pilot test flame timeout | High |
| Lockout 112 | Pilot test flame timeout | High |
| Lockout 113 | Flame circuit timeout | High |
| Lockout 113 | Flame circuit timeout | High |
| Lockout 122 | Light off rate proving failed | High |
| Lockout 122 | Light-off rate proving failed | High |
| Lockout 123 | Purge rate proving failed | High |
| Lockout 123 | Purge rate proving failed | High |
| Lockout 138 | Flame too low | High |
| Lockout 143 | Internal fault: Flame bias out of range 1 | High |
| Lockout 144 | Internal fault: Flame bias out of range 2 | High |
| Lockout 145 | Internal fault: Flame bias out of range 3 | High |
| Lockout 146 | Internal fault: Flame bias out of range 4 | High |
| Lockout 147 | Internal fault: Flame bias out of range 5 | High |
| Lockout 148 | Internal fault: Flame bias out of range 6 | High |
| Lockout 157 | Combustion pressure and Flame OFF | High |
| Lockout 157 | Combustion pressure and Flame OFF | High |
| Lockout 158 | Main valve ON | High |
| Lockout 158 | Main valve ON | High |
| Lockout 159 | Main valve OFF | High |
| Lockout 159 | Main valve OFF | High |
| Lockout 160 | Ignition ON | High |
| Lockout 160 | Ignition ON | High |
| Lockout 161 | Ignition OFF | High |
| Lockout 161 | Ignition OFF | High |
| Lockout 162 | Pilot valve ON | High |
| Lockout 162 | Pilot valve ON | High |
| Lockout 163 | Pilot valve OFF | High |
| Lockout 163 | Pilot valve OFF | High |
| Lockout 164 | Block intake ON | High |
| Lockout 164 | Block intake ON | High |
| Lockout 165 | Block intake OFF | High |
| Lockout 165 | Block intake OFF | High |
| Lockout 169 | Safety opto bad in test state | High |
| Lockout 170 | Safety relay opto feedback incorrect | High |
| Lockout 171 | Safety relay feedback incorrect in run | High |
| Lockout 172 | Main relay feedback incorrect | High |
| Lockout 172 | Main relay feedback incorrect | High |
| Lockout 173 | Pilot relay feedback incorrect | High |
| Lockout 173 | Pilot relay feedback incorrect | Critical |
| Lockout 174 | Safety relay feedback incorrect | Critical |
| Lockout 174 | Safety relay feedback incorrect | Critical |
| Lockout 175 | Safety relay open | High |
| Lockout 175 | Safety relay open | High |
| Lockout 176 | Main relay ON at safe start check | High |
| Lockout 176 | Main relay ON at safe start check | High |
| Lockout 177 | Pilot relay ON at safe start check | High |
| Lockout 177 | Pilot relay ON at safe start check | High |
| Lockout 178 | Safety relay ON at safe start check | High |
| Lockout 178 | Safety relay ON at safe start check | High |
| Lockout 184 | Invalid BLOWER/HSI output setting | High |
| Lockout 184 | Invalid BLOWER/HSI output setting | High |
| Lockout 185 | Invalid Delta T limit enable setting | High |
| Lockout 185 | Invalid Delta T limit enable setting | High |
| Lockout 186 | Invalid Delta T limit response setting | High |
| Lockout 186 | Invalid Delta T limit response setting | High |
| Lockout 187 | Invalid DHW high limit enable setting | High |
| Lockout 187 | Invalid DHW high limit enable setting | High |
| Lockout 188 | Invalid DHW high limit response setting | High |
| Lockout 188 | Invalid DHW high limit response setting | High |
| Lockout 189 | Invalid Flame sensor type setting | High |
| Lockout 189 | Invalid Flame sensor type setting | High |
| Lockout 190 | Invalid interrupted air switch enable setting | High |
| Lockout 190 | Invalid interrupted air switch enable setting | High |
| Lockout 191 | Invalid interrupted air switch start check enable setting | High |
| Lockout 191 | Invalid interrupted air switch start check enable setting | High |
| Lockout 192 | Invalid Igniter on during setting | High |
| Lockout 192 | Invalid Igniter on during setting | High |
| Lockout 193 | Invalid Ignite failure delay setting | High |
| Lockout 193 | Invalid Ignite failure delay setting | High |
| Lockout 194 | Invalid Ignite failure response setting | High |
| Lockout 194 | Invalid Ignite failure response setting | High |
| Lockout 195 | Invalid Ignite failure retries setting | High |
| Lockout 195 | Invalid Ignite failure retries setting | High |
| Lockout 196 | Invalid Ignition source setting | High |
| Lockout 196 | Invalid Ignition source setting | High |
| Lockout 197 | Invalid Interlock open response setting | High |
| Lockout 197 | Invalid Interlock open response setting | High |
| Lockout 198 | Invalid Interlock start check setting | High |
| Lockout 198 | Invalid Interlock start check setting | High |
| Lockout 199 | Invalid LCI enable setting | High |
| Lockout 199 | Invalid LCI enable setting | High |
| Lockout 200 | Invalid light off rate setting | High |
| Lockout 200 | Invalid light off rate setting | High |
| Lockout 201 | Invalid Light off rate proving setting | High |
| Lockout 201 | Invalid Light off rate proving setting | High |
| Lockout 202 | Invalid Main Flame Establishing Period time setting | High |
| Lockout 202 | Invalid Main Flame Establishing Period time setting | High |
| Lockout 203 | Invalid MFEP flame failure response setting | High |
| Lockout 203 | Invalid MFEP flame failure response setting | High |
| Lockout 204 | Invalid NTC sensor type setting | High |
| Lockout 204 | Invalid NTC sensor type setting | High |
| Lockout 205 | Invalid Outlet high limit response setting | High |
| Lockout 205 | Invalid Outlet high limit response setting | High |
| Lockout 206 | Invalid Pilot Flame Establishing Period setting | High |
| Lockout 206 | Invalid Pilot Flame Establishing Period setting | High |
| Lockout 207 | Invalid PII enable setting | High |
| Lockout 207 | Invalid PII enable setting | High |
| Lockout 208 | Invalid pilot test hold setting | High |
| Lockout 208 | Invalid pilot test hold setting | High |
| Lockout 209 | Invalid Pilot type setting | High |
| Lockout 209 | Invalid Pilot type setting | High |
| Lockout 210 | Invalid Post-purge time setting | High |
| Lockout 210 | Invalid Post-purge time setting | High |
| Lockout 211 | Invalid Power up with lockout setting | High |
| Lockout 211 | Invalid Power up with lockout setting | High |
| Lockout 212 | Invalid Pre-ignition time setting | High |
| Lockout 212 | Invalid Pre-ignition time setting | High |
| Lockout 213 | Invalid Pre-purge rate setting | High |
| Lockout 213 | Invalid Pre-purge rate setting | High |
| Lockout 214 | Invalid Pre-purge time setting | High |
| Lockout 214 | Invalid Pre-purge time setting | High |
| Lockout 215 | Invalid Purge rate proving setting | High |
| Lockout 215 | Invalid Purge rate proving setting | High |
| Lockout 216 | Invalid Run flame failure response setting | High |
| Lockout 216 | Invalid Run flame failure response setting | High |
| Lockout 217 | Invalid Run stabilization time setting | High |
| Lockout 217 | Invalid Run stabilization time setting | High |
| Lockout 218 | Invalid Stack limit enable setting | High |
| Lockout 218 | Invalid Stack limit enable setting | High |
| Lockout 219 | Invalid Stack limit response setting | High |
| Lockout 219 | Invalid Stack limit response setting | High |
| Lockout 220 | Unconfigured Delta T limit set point setting | High |
| Lockout 220 | Unconfigured Delta T limit set point setting | High |
| Lockout 221 | Unconfigured DHW high limit set point setting | High |
| Lockout 221 | Unconfigured DHW high limit set point setting | High |
| Lockout 222 | Unconfigured Outlet high limit set point setting | High |
| Lockout 222 | Unconfigured Outlet high limit set point setting | High |
| Lockout 223 | Unconfigured Stack limit set point setting | High |
| Lockout 223 | Unconfigured Stack limit set point setting | High |
| Lockout 224 | Invalid DHW demand source setting | High |
| Lockout 224 | Invalid DHW demand source setting | High |
| Lockout 225 | Invalid Flame threshold setting | High |
| Lockout 225 | Invalid Flame threshold setting | High |
| Lockout 226 | Invalid Outlet high limit set point setting | High |
| Lockout 226 | Invalid Outlet high limit set point setting | High |
| Lockout 227 | Invalid DHW high limit set point setting | High |
| Lockout 227 | Invalid DHW high limit set point setting | High |
| Lockout 228 | Invalid Stack limit set point setting | High |
| Lockout 228 | Invalid Stack limit set point setting | High |
| Lockout 229 | Invalid Modulation output setting | High |
| Lockout 229 | Invalid Modulation output setting | High |
| Lockout 230 | Invalid CH demand source setting | High |
| Lockout 230 | Invalid CH demand source setting | High |
| Lockout 231 | Invalid Delta T limit delay setting | High |
| Lockout 231 | Invalid Delta T limit delay setting | High |
| Lockout 232 | Invalid Pressure sensor type setting | High |
| Lockout 232 | Invalid Pressure sensor type setting | High |
| Lockout 233 | Invalid IAS closed response setting | High |
| Lockout 233 | Invalid IAS closed response setting | High |
| Lockout 234 | Invalid Outlet high limit enable setting | High |
| Lockout 234 | Invalid Outlet high limit enable setting | High |
| Lockout 235 | Invalid Outlet connector type setting | High |
| Lockout 235 | Invalid Outlet connector type setting | High |
| Lockout 236 | Invalid Inlet connector type setting | High |
| Lockout 236 | Invalid Inlet connector type setting | High |
| Lockout 237 | Invalid DHW connector type setting | High |
| Lockout 237 | Invalid DHW connector type setting | High |
| Lockout 238 | Invalid Stack connector type setting | High |
| Lockout 238 | Invalid Stack connector type setting | High |
| Lockout 239 | Invalid Header connector type setting | High |
| Lockout 239 | Invalid Header connector type setting | High |
| Lockout 240 | Invalid Outdoor connector type setting | High |
| Lockout 241 | Exchanger sensor not allowed with stack connector setting | High |
| Lockout 242 | Invalid DHW auto detect configuration | High |
| Lockout 244 | PFEP Internal fault: Safety relay test invalid state | High |
| Lockout 245 | Invalid Outlet connector type setting for T-rise | High |
| Lockout 246 | 4-20mA cannot be used for both modulation and setpoint control | High |
| Lockout 247 | Invalid ILK bounce detection enable | High |
| Lockout 248 | Invalid forced recycle interval | High |
| Lockout 249 | STAT cannot be demand source when Remote Stat is enabled | High |
| Lockout 250 | Invalid Fan speed error response | High |
| Lockout 251 | Lead drop-stage on error setting does not match drop method configuration | High |
| Lockout 252 | Invalid Line frequency setting | High |
| Lockout 253 | Lead Lag modulation sensor not valid with setpoint source | High |
| Lockout 254 | Lead Lag modulation sensor not valid with local setpoint source | High |
| Lockout 255 | Lead Lag modulation sensor not valid with local modulation source | High |
| Lockout 256 | Selected Controller interaction enable setting is not allowed | High |
| Lockout 257 | Controller interaction enable does not match neighbor stack fault setting | High |
| Lockout 258 | Controller ID must be non-zero if controller interaction is enabled | High |
| Lockout 259 | Modulation output must be fan if controller interaction is enabled | High |
| Lockout 260 | Asymmetrical paired (no flap) is set but flap switch input is energized | High |
| Lockout 261 | Neighbor burner control blower fault detected | High |
| Lockout 262 | Blower fault detected during flap test | High |
| Lockout 263 | Invalid DHW demand temperature setting | High |
| Lockout 264 | Invalid preferred outlet high limit setting | High |
| Lockout 265 | Invalid preferred lightoff rate setting | High |
| Lockout 266 | Invalid preferred stack limit rate setting | High |