Viessmann Heat Pump: Wiring alternative in high EMF areas and multi-zone matches
Wiring alternative in high EMF areas and multi-zone matches on a Viessmann heat pump: In high electromagnetic field areas with communication problems, a 14/2 stranded shielded wire may replace L2 and (S). Multi-family and residential fan coil matches need separate power for the indoor and outdoor units and a 24V interface kit.
Applies to: DLCSRB outdoor units with indoor fan coil matches
How to fix wiring alternative in high emf areas and multi-zone matches: step by step
- Replace L2 and (S) with 14/2 stranded shielded wire between the outdoor and indoor units if EMF communication problems exist.
- Ground the shield at the outdoor unit only.
- For multi-family or residential fan coil matches, provide separate power to the indoor and outdoor units.
- Install the 24V interface kit and follow its installation manual.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3
Source: DLCSRB Service Manual, p. 3. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.