Other: Heat Pump tips (part 5 of 5)
Short, practical technician tips on other for heat pump. Check each one against the manual for your exact model before acting.
Refrigerant handling and mechanical loads
Viessmann · Vitocal 100-AW AM2V refrigerant circuit
Refrigerant is under pressure and direct contact can cause frostbite, burns or asphyxiation.
- Avoid direct contact with liquid and gaseous refrigerant and never breathe in vapours.
- Wear personal protective equipment when handling refrigerant.
- Do not load lines or components with tools or supports, as this can cause leaks.
- Label, store and transport refrigerant-containing components in well-ventilated areas.
Refrigerant leak: making the area safe
Viessmann · Vitocal 100-AW AM2V outdoor unit
Steps to take if a refrigerant leak is suspected in the outdoor unit.
- Clear people from the danger zone.
- From a safe position, switch off power to all system components.
- Ventilate the floor area of the outdoor unit very well.
- Remove all ignition sources and tell the system user that no ignition source may be brought in during the repair.
- Have an authorised contractor carry out the repair, then recommission only after repair.
Refrigerant pipe burial limits
Viessmann · DLCLRC sizes 36K-58K refrigerant piping
Do not bury more than 36 in. (914 mm) of refrigerant pipe. If any section is buried, it needs a 6 in. (152 mm) vertical rise to the outdoor unit valve connections. Longer buried runs let refrigerant migrate to the cold section during shutdown, which can cause slugging and compressor damage at start-up.
- Limit buried refrigerant pipe to 36 in. (914 mm).
- Provide a 6 in. (152 mm) vertical rise to the outdoor valve connections where any pipe is buried.
Refrigerant safety before brazing (R32 and R290)
Viessmann · DLCLRC 36K-58K, R32 and R290 systems
Before brazing or removing the four-way valve or compressor, make sure the system holds no refrigerant. For R32 and R290 the method is different.
- Evacuate the system and confirm no refrigerant is left.
- For R32 and R290, evacuate with a vacuum pump.
- Flush the system with nitrogen.
- Repeat the evacuation and flush steps before heating brazed parts.
Remove ground loop caps before installing
Viessmann · Vitocal 100-WA ground loop connections
Ground loop connections ship with caps fitted.
- Remove the caps from the ground loop connections before installing the piping.
Repairs and genuine parts
Viessmann · Vitocal 100-AW AM2V
Safety-function components and inverter repairs are restricted.
- Replace faulty components only with genuine Viessmann spare parts.
- Do not repair the inverter; replace it if it is defective.
- Do not drill, heat or otherwise modify a refrigerant circuit that is filled with refrigerant.
- Do not operate Schrader valves unless a fill valve or extraction equipment is attached.
Scalding risk from high DHW temperature
Viessmann · DHW storage tank and hygiene function
DHW temperatures above 140°F (60°C), such as during the hygiene function, can cause scalding. Mix with cold water at the draw-off points.
- Install mixing with cold water at draw-off points before running hygiene function.
Serial number needed for replacement parts
Viessmann · Vitocal 100-AW AM2V
Indoor and outdoor units each have their own 16-digit serial number on the rating plate. Some replacement parts are not reverse compatible with earlier versions.
- Read the 16-digit serial number from the indoor unit or outdoor unit rating plate.
- Provide the serial number with the parts order.
- Indoor serial prefixes: AM2V 020028 = 7228973, AM2V 034043 = 7228974, AM2V 051078 = 7228975.
- Outdoor serial prefixes: AM2V 020028 = 7986309, AM2V 034043 = 7986310, AM2V 051078 = 7986311.
Service clearance
Viessmann · Vitocal 100-WA
The recommended service clearance is 24 in. (600 mm). Leave extra room for piping, ductwork and electrical connections. The side the clearance applies to is not clear in the manual text.
- Keep at least 24 in. (600 mm) of service clearance.
- Allow extra space for piping, ductwork and electrical connections.
Site selection and high wind
Viessmann · DLCURA outdoor unit
Place the unit where it is level, can carry its weight and is sheltered from strong wind. In high wind, set the air inlet side facing the wall. Keep snow from blocking the air intake.
- Use a rigid base with the unit level.
- Use tie-down bolts through the base pan knockouts when a pad or local code requires it.
- Do not install where combustible gas could collect.
Storage conditions for the unit
Viessmann · Vitocal 100-WA
Storage temperature limits and conditions for the indoor unit before installation.
- Store the unit between -13 °F and 158 °F (-25 °C and 70 °C).
- Make sure the storage location has sufficient ventilation.
- Have an explosion prevention plan in place for storage.
- Protect the unit from damage.
Storage of outdoor unit
Viessmann · Vitocal 100-AW AM2V outdoor unit
Storage conditions for the outdoor unit, which is charged with R32 at the factory.
- Keep an explosion prevention plan in place for the storage site and make sure it is well ventilated.
- Store between -25 °C and 70 °C (-13 °F to 158 °F).
- Keep the unit in its factory protective packaging and protect it from damage.
- Limit the number of units stored in one place according to local conditions.
Support piping and use isolation valves
Viessmann · Vitocal 100-WA
The unit must not carry the weight of the piping.
- Support all piping with hangers.
- Do not support piping by the Vitocal or its components.
- Install isolation valves so system components can be isolated.
Thermostat mounting
Viessmann · Thermostat installation
Mount the thermostat on foam tape to seal the wire hole; silicone can also be used. This keeps drafts off the thermistor and helps prevent short cycling.
- Seal the wire penetration behind the thermostat with foam tape or silicone.
- Keep the thermostat away from drafts.
Thermostat terminal use on the terminal strip
Viessmann · Terminal strip wiring
Y2 is used for optional stage 2 heating or cooling. On a single speed system nothing is wired to the B terminal. E is used for an optional strip heater; leave it unwired if there is no strip heat or aux heat.
- Wire stage 2 heat/cool to Y2 if the system has it.
- Leave B unwired on single speed systems.
- Wire strip heat to E only if the system has strip or aux heat.
Thread sealing on water fittings
Viessmann · Vitocal 100-WA water connections
Thread prep is specified for the installation fittings on the DHW and ground loop connections.
- Use an approved pipe sealant or Teflon tape on the installation fittings.
- Use a moderate amount of pipe dope.
- Leave two threads bare at the end of the thread.
- Expect two imperfect threads at the end of the pipe.
Two-wrench method for fittings
Viessmann · Vitocal 100-WA
Turning a fitting onto the heat pump connector without support can twist the internal piping and damage the unit.
- Use one wrench to hold the heat pump connector so the pipe does not twist.
- Use a second wrench to tighten the fitting or piping.
- Do not exceed the pressures and temperatures listed for the unit.
Unit configuration features
Viessmann · Vitocal 100-WA
The Vitocal 100-WA is a two-stage packaged water source heat pump for heating or cooling and domestic hot water. It supports closed or open loop, uses an integrated desuperheater with pump for DHW, and has a flexible junction box mounting and an information display panel.
Use only dry nitrogen for testing
Viessmann · DLCURA refrigerant circuit
Never use air or oxygen-containing gas for leak testing, because it can explode. Only use dry nitrogen to pressure test refrigerant systems. Never use the compressor as a vacuum pump.
Use the refrigerant service ports
Viessmann · DLCURA outdoor units
The outdoor unit has service ports on the liquid and suction lines, and Schrader gauge ports on the compressor suction and discharge lines.
- Locate the liquid line service valve and the suction line service valve.
- Connect gauges to the Schrader ports on the compressor suction and discharge lines.
- Use the brass service caps when the ports are not in use.
Wait before opening covers after power-off
Viessmann · Vitocal 100-WA
Some PCB components stay live after the supply is switched off.
- Switch off the power at the breaker and confirm the system is dead.
- Remember that a control circuit and possibly several power circuits may be present.
- Wait at least 4 minutes after switching off before removing any covers.
- Lock out the system against reconnection and wear suitable PPE.
Water supply and potable water connection
Viessmann · Vitocal 100-WA
The unit needs a water supply. Potable water is not recommended for it.
- Refer to the Water Quality section for the required water quality.
- If potable water is used, protect the supply against back-siphonage at the equipment.
Wiring alternative in high EMF areas and multi-zone matches
Viessmann · DLCSRB outdoor units with indoor fan coil matches
In high electromagnetic field areas with communication problems, a 14/2 stranded shielded wire may replace L2 and (S). Multi-family and residential fan coil matches need separate power for the indoor and outdoor units and a 24V interface kit.
- Replace L2 and (S) with 14/2 stranded shielded wire between the outdoor and indoor units if EMF communication problems exist.
- Ground the shield at the outdoor unit only.
- For multi-family or residential fan coil matches, provide separate power to the indoor and outdoor units.
- Install the 24V interface kit and follow its installation manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.