Viessmann Boiler: Read the fault memory
Read the fault memory on a Viessmann boiler: The last 10 faults are stored and can be scrolled from newest to oldest. The display exits on its own if no key is pressed for 20 seconds. A burner that will not start without a displayed code may still show the cause here.
Applies to: Vitocrossal 200 CM2 burner control unit
How to fix read the fault memory: step by step
- Press and hold S for longer than 2 seconds until the symbol flashes.
- Press Y until 4 shows under Service.
- Press S. 4 shows under Status.
- Press Y or B to scroll through the fault memory.
- Press S to open the selected fault memory display.
- Press Y or B to scroll through the stored fault codes.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
More service & test modes tips for boiler
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 49. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.