Service & test modes: Boiler tips (part 6 of 10)
Short, practical technician tips on service & test modes for boiler. Check each one against the manual for your exact model before acting.
Perform LON participant check
Viessmann · Vitotronic fault manager on LON system
Tests communication between the fault manager and the connected LON devices. Requires the control unit set as fault manager (code 79:1), participant numbers set in all units, and an up-to-date participant list.
- Press OK together with the second service key (symbol not legible on the page) for about 4 seconds.
- Select Service functions.
- Select Participant check.
- Select the participant to test, e.g. participant 10.
- Read the result: OK means passed, Not OK means failed.
- To run a new check, create a new participant list using Delete list in the menu.
Read a fault code from the remote control
Viessmann · Vitotrol 300 remote control, fault indication
When a fault occurs the display shows it with the flip-down cover closed. The fault source is shown in clear text and as a fault code. Give the fault code to the heating contractor.
- Open the flip-down cover of the remote control.
- Select the fault search key. The fault source appears in clear text and as a code.
- Confirm the fault.
- Use the up/down keys to answer yes or no for acknowledgment.
- Confirm. The display returns to the time.
- Close the flip-down cover.
- If the fault is not corrected, the message returns at 07:00 hrs the next morning.
Read and acknowledge fault codes on Vitotronic 100
Viessmann · Vitotronic 100 GC1B
A flashing fault symbol and the red fault indicator show a fault. The fault code is shown on the display. If several faults are stored, they can be scanned in sequence.
- Note the fault code and tell the heating contractor.
- Acknowledge the fault with OK; the fault symbol stops flashing.
- To view an acknowledged fault again, press and hold OK for about 4 seconds.
- If several faults are stored, scan them with the selector keys.
- If the fault is not fixed, it shows again the next day and any buzzer is switched on again.
Read and acknowledge fault messages on Vitotronic 300-K
Viessmann · Vitotronic 300-K MW1B
A flashing fault symbol and the red fault indicator show a fault, and the display shows Fault. The cause text and fault code are shown together.
- Press OK to show the cause of the fault.
- Press the help key to see information on system functions and simple measures the operator can take.
- Note the cause and the fault code shown with it.
- Acknowledge the message by following the instructions in the menu; it then moves to the fault menu.
- To view an acknowledged fault later, open the extended menu and select Fault.
- If the fault is not fixed, it shows again the next day and any buzzer is switched on again.
Read brief scan operating data
Viessmann · Vitodens 222-F B2TB
The brief scan shows temperatures, software versions and connected components in 9 lines with 6 fields each.
- Enter the service level.
- Select 'Diagnosis', then 'Brief scan'.
- Press OK. The display shows 9 lines of values.
- Read '- - -' as a faulty sensor.
Read fault codes and the error history on Vitocontrol-S
Viessmann · Vitocontrol-S VD2/CT3/CM2 programming unit
Faults can be shown as codes or in plain text. The manual gives the plain-text names for each sensor and device that can fault.
- Scroll through active faults to read the code and the plain-text name.
- Recall acknowledged faults by holding the key for about 3 seconds.
- Use the error history to find repeat faults.
Read fault history (last 10 faults)
Viessmann · Vitodens 200-W B2HB 19 to 35, 68 to 125
The control unit stores the 10 most recent faults, including resolved ones, sorted by date. Detailed codes are shown as a sub-code in the fault history.
- Press OK and the button symbol shown in the manual at the same time for about 4 seconds.
- Select 'Fault history'.
- Select 'Display?'.
- Press OK to show the fault code. Look up the code in the fault code tables.
- For some faults, the type of fault is also shown in plain text.
- After servicing, select code 24:0 to reset the service-required indication (code 0F).
Read ionization current
Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0
Shows the ionization current in the process information menu. The value displays in 1/10 μA, so 30 means 3.0 μA.
- Press and hold button S for more than 2 seconds until it blinks.
- Press button Y until 5 shows under Service.
- Press button S. A 5 shows under Status.
- Press button Y until 3 shows under Service.
- Press button S. A 3 shows under Status and the ionization current shows under Service during operation.
- To exit, press and hold S for more than 2 seconds, then press Y until 5 shows under Service and press B until 0 shows.
- Press button S to return to the operating display.
Read ionization current from the burner control
Viessmann · CA3B 2.5 to 6.0
Ionization current must be read through the burner control, not with a meter.
- Press the S button for about 2 seconds until the indicator blinks.
- Press the button until 5 shows under Service, then press S. 5 shows under Status.
- Press the button until 3 shows under Service, then press S. The ionization current appears under Service (for example 30 = 3.0 µA).
- Start the burner with the emissions test switch on the GW6C control.
- Read and record the ionization current.
- To exit, press S for about 2 seconds, set Service to 5 then S, set Service to 0 then S. The operating display returns.
Read ionization current on the control unit
Viessmann · Vitocrossal 300 CA3B Dual Fuel burner control unit GW6C
Shows the flame ionization current through the burner control unit. A multimeter or Testomatic Gas cannot measure it.
- Press the service button for about 2 sec until the indicator blinks.
- Set Service to 5, press the button, then set Status to 3 and confirm.
- The ionization current in operation appears under Service (for example 30 = 3.0 µA).
- Start the burner with the emissions test switch on the GW6C control and read the value.
- Record the reading in the maintenance record on page 158.
- Exit the menu: press the service button for about 2 sec, set Service to 5, confirm, set Service to 0 and confirm.
Read key brief scan lines
Viessmann · Vitodens 200-W B2HA 45, 60
Line 1: system type 01 to 10 and control unit software version. Line 2: appliance version and device ID. Line 4: burner control unit type and version. Line 9: remote control (0 none, 1 Vitotrol 200/200A/200 RF, 2 Vitotrol 300/300A/300 RF or Vitohome). Line 10: variable speed pump (0 none, 1 Wilo, 2 Grundfos). Line 11: mixing valve extension present (0 = none). A field showing '- - -' means that scanned sensor is faulty.
Read operating data (Diagnosis)
Viessmann · Vitotronic 200 service level
Operating data is grouped into six areas. A "- - -" reading means a sensor that was scanned is faulty. Mixing valve and solar data only show if those components are installed.
- Enter the service level.
- Select "Diagnosis".
- Select the required group, for example "General".
Read operating data (Diagnostics)
Viessmann · Vitodens 100-W B1HE/B1KE
Operating data is grouped by area. Sensors that are faulty show a dashed placeholder.
- Enter the service menu.
- Select Diagnostics, then OK.
- Select the required group, then OK.
- Select the required information.
- If the sensor is faulty, - - - is shown on the display.
Read system temperatures and operating status
Viessmann · Vitotrol 300 remote control, system readings
Scan current values on the remote control. Available values depend on installed components and coding. Sensor-based values only appear if the sensor is installed.
- Open the flip-down cover of the remote control.
- Select the scan function. The outside temperature is shown.
- Use the up/down keys to scan through the values.
- End scanning. The display returns to the time.
- Close the flip-down cover.
Read the fault display and fault history
Viessmann · Vitocrossal 300 CA3B
Active faults flash red on the control unit. Acknowledged faults can be listed, and the last 10 faults (including cleared ones) are kept in the fault history, sorted by date.
- When a fault flashes red, tap the fault button to list acknowledged faults. Several faults show as a red list in date order.
- For history, go to Service, enter the 'viservice' password, then open Fault history.
- Tap the information option on a fault to see more detail.
- Use the delete option to clear the history list.
Read the fault history
Viessmann · Vitotronic 200 KW2
Shows every stored fault, starting with the most recent one. Entry 1 is the newest and entry 10 is the oldest.
- Press the two indicated buttons together for about 2 seconds to open the error history.
- Use the arrow buttons to step through entries 1 to 10.
- Press the back button to leave the history.
- To delete all stored fault codes, press the delete button while in the history.
Read the fault history (last 10 faults)
Viessmann · Vitodens 222-F B2TB 19, 35, 68, 125
The control keeps the 10 most recent faults, including resolved ones, sorted by date.
- Press OK and the second button shown together for about 4 seconds.
- Select 'Fault history'.
- Select 'Display?' and press OK to show the code.
- Use the fault code tables in the manual to read the explanation. Some faults also show plain text.
Read the fault history and clear the fault memory
Viessmann · Vitotronic 200-H, Model HK1M
All faults are saved. Position 1 is the most recent fault and position 10 is the tenth fault in memory.
- Press r and the arrow button together for about 2 seconds.
- Call up each saved fault code with the arrow buttons.
- To delete all saved fault codes, press D.
- Press OK to exit.
Read the fault memory
Viessmann · Vitocrossal 200 CM2 burner control unit
The last 10 faults are stored and can be scrolled from newest to oldest. The display exits on its own if no key is pressed for 20 seconds. A burner that will not start without a displayed code may still show the cause here.
- Press and hold S for longer than 2 seconds until the symbol flashes.
- Press Y until 4 shows under Service.
- Press S. 4 shows under Status.
- Press Y or B to scroll through the fault memory.
- Press S to open the selected fault memory display.
- Press Y or B to scroll through the stored fault codes.
Recall acknowledged fault messages
Viessmann · Vitotronic 200-H HK1S/HK3S
Use this to review faults that were already acknowledged. The next fault only shows if two or more faults have occurred.
- Press and hold the fault button for about 2 seconds.
- Press the arrow buttons to show further faults.
Recall acknowledged faults
Viessmann · HK1S, HK3S
Acknowledged faults can be viewed again from the fault list.
- Press and hold the fault key for about 2 seconds.
- Select the acknowledged fault with the up or down key.
Recall an acknowledged fault
Viessmann · Fault history
Used to view previously acknowledged faults. The up and down arrows only appear when two or more faults have occurred.
- Press the fault button for about 2 seconds.
- Press the up or down arrow to show further faults.
Relay status and test menu
Viessmann · Versatronik 200 service mode
Relay status and test is reached from the Service menu. The menu structure overview is shown as a diagram on the next page and is not transcribed here.
- Open the Service menu as described for viewing information.
- Select Relay Test or Relay status and test.
- Refer to the menu structure overview diagram for the full path.
Relay test
Viessmann · Vitotronic 200 KW2
Forces each relay output on or off to check wiring and components. Relays can be switched with a delay of up to 1 minute. Some outputs only show if the matching module is connected.
- Press the two buttons together for about 2 seconds to start the relay test.
- Select the relay output with the up/down button: burner ON, burner stage 1 ON, burner modulation up or down or stop, burner stage 1+2 ON, heating pump ON, mixing valve open or closed, DHW tank pump ON, DHW recirculation pump ON, or compiled fault indicator ON.
- Check the matching LED and the component.
- Press the button shown in the manual to end the relay test.
Relay test and sensor test menus
Viessmann · Versatronik 300 menu
The Menu holds a relay test and a sensor test. Use them to check outputs and inputs by hand.
- Open Menu and select Relay Test.
- Switch Pump, AUX or Fault between Off and On to test each output.
- Open Menu and select Sensor Test to view S1 (outdoor), S2 (supply), S3 (return), INT (interlock) and AUX (input).
Relay test display indications
Viessmann · Vitotronic 100, GC1 relay test
Relay test displays show which output is being energised. Button symbols are not clear on these pages, so confirm with the unit.
- Display 11: burner or stage 1 ON.
- Display 12: burner stage 1 and 2 ON or modulation up.
- Display 13: burner modulation neutral.
- Display 14: burner stage 1 ON, modulation down.
- Display 15: output 20 ON.
- Display 16: output 29 ON.
- Display 17: output 52 open.
- Display 18: output 52 neutral.
- Display 19: output 52 close.
Relay test of mixing valve motor direction
Viessmann · Mixing valve motor
The relay test of the control unit drives the mixing valve to Open and Closed, which is used to confirm rotation direction.
- Start the relay test on the control unit.
- Watch the mixing valve move to Open and then Closed.
Relay test of outputs and pumps
Viessmann · Vitotronic 200-H
Forces individual relay outputs and mixing valve motors on or off to confirm wiring and operation. Selectable outputs include output 20, output 52 (open, hold, closed), DHW pump, DHW re-circulation pump, heating circuit pumps M2 and M3, mixing valve M2 and M3 open/closed, and fault messaging. The illuminated heating circuit selector shows which circuit is active. To reverse the mixing valve motor rotation, refer to page 41.
- Press 9 and OK together for about 2 seconds to start the relay test.
- Use the arrow keys to switch the relay output on or off.
- Press OK to finish the relay test.
Relay test of the mixing valve
Viessmann · Mixing valve motor
The relay test on the control unit drives the mixing valve open and closed.
- Start the relay test on the control unit.
- Confirm the mixing valve moves to open and then to close.
Retrieve fault history (error memory)
Viessmann · Vitotronic 100 GC1 fault memory
All past faults are stored. Scanning starts with the most recent fault and runs back through the stored list (up to 10 entries, numbered 1 to 10 with 1 as the last fault).
- Press the two buttons together and hold for about 2 seconds to start error history scanning.
- Use the up or down button to step through the stored fault codes, starting with the most recent.
- Press the button shown after the scan step to end scanning.
- To delete all stored faults, press the delete button shown in the manual while scanning is active, then end the scan.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.