Viessmann Boiler: Parameter R62 after a flame loss
Parameter R62 after a flame loss on a Viessmann boiler: After a fail of flame during operation the burner cannot modulate at partial load (20%) for one hour. During this time the minimum input for R62 is 50 to 60%. Standby before the hour is up does not clear the setting.
Applies to: Vitocrossal 200 CM2 burner control unit
How to fix parameter r62 after a flame loss: step by step
- To clear the one hour lockout early, press the reset button or switch the burner control off.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 44. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.