Other: Boiler tips (part 26 of 45)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.

Operating status: standard and reduced heating mode

Viessmann · Vitotronic 200 and 300-K heating circuits

In the 'Heating and DHW' program, the control switches between standard heating mode (rooms at standard room temperature) and reduced heating mode (setback to reduced room temperature). The switch times come from the central heating time program. Standard mode is used when occupied, and reduced mode when away or at night.

  1. Set the standard room temperature for occupied periods.
  2. Set the reduced room temperature for away or night periods.
  3. Set the central heating time program to define when each mode runs.

Order parts with the boiler serial number

Viessmann · Vitodens 222-F, B2TB 19, 35, 68, 125

When ordering replacement parts, give the 16-digit boiler serial number from the barcode label, or the 12-digit ASME/NB serial. Both are under the front enclosure panel.

  1. Remove the front enclosure panel to reach the serial number labels.
  2. Record the 16-digit serial number or the 12-digit ASME/NB serial number before ordering parts.

Ordering parts: serial number

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

Parts orders need the 16-digit serial number on the barcode label, or the 12-digit ASME/NB serial number. Both are behind the front enclosure panel. Some parts are not reverse compatible with earlier Vitodens 200-W B2HB versions.

  1. Remove the front enclosure panel to read the serial number.
  2. Give the 16-digit barcode serial or the 12-digit ASME/NB serial when ordering.
  3. Confirm the part works with the boiler serial before ordering.

Ordering parts: serial number needed

Viessmann · Models 112, 150, 399, 530

Replacement parts must be ordered with the boiler serial number. Some parts are not reverse compatible with earlier B2HA versions. Use either the 16-digit serial on the barcode label or the 12-digit ASME/NB serial, found under the front enclosure panel. Serial numbers printed on the page: B2HA 112 and 399 are 7510835 and 7550393; B2HA 150 and 530 are 7510836 and 7550394.

  1. Remove the front enclosure panel to find the ASME/NB serial (see the front panel removal steps).
  2. Quote the 16-digit barcode serial or the 12-digit ASME/NB serial when ordering parts.

Ordering replacement parts

Viessmann · Vitocrossal 200 CI2 all sizes

Have the model and serial number from the CSA rating plate ready before ordering. Order parts through a Viessmann distributor.

  1. Read the model and serial number from the CSA rating plate (plate A).
  2. Order replacement components from your Viessmann distributor.

Ordering replacement parts for the control unit

Viessmann · Vitotronic 300 GW2 replacement parts

Parts orders need the model and serial number from the rating plate. The serial number is a 16-digit bar-coded number on the front housing, below the flip-down cover.

  1. Read the model and serial number from the rating plate.
  2. Find the serial number on the front housing, below the flip-down cover.
  3. Order replacement components through a Viessmann distributor.

Ordering replacement parts needs the serial number

Viessmann · All Vitodens 200-W B2HB models

Always give the 16-digit boiler serial number (bar code label) or the 12-digit ASME/NB serial number when ordering parts. Some parts are not reverse compatible with earlier B2HB versions.

  1. Find the serial number under the front enclosure panel.
  2. Quote the 16-digit or 12-digit serial number with the model when ordering.
  3. Check parts compatibility before fitting a part to an earlier B2HB unit.

Outdoor and DHW temperature sensor connections

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

The outdoor temperature sensor and the DHW temperature sensor connect to the control base. For the connection to the external accessory connection box, see the wiring diagram on page 47.

  1. Connect the outdoor temperature sensor to the control base.
  2. Connect the DHW temperature sensor to the control base.
  3. Refer to the wiring diagram on p. 47 for the accessory connection box.

Outdoor reset and energy management override restrictions

Viessmann · Hydrostat control on Vitorond 100 VR1 boilers

The Hydrostat boiler control has an override intended for use with an external energy management system. It may only be used when one of the listed conditions is true.

  1. Use the override only if an external energy management system lowers boiler water temperature as heating load drops.
  2. Or use it only if the boiler is not used for space heating.
  3. Or use it only if the boiler is part of a modular or multiple boiler system with 300,000 BTU/h total input or more.
  4. Or use it only if the boiler has a tankless coil.

Outdoor reset override restrictions

Viessmann · Vitorond 100 with Hydrostat or outdoor reset module

The outdoor reset energy saving feature has an override meant mainly for an external energy management system. The override may only be used if one of the listed conditions is true.

  1. Use the override only if an external energy management system lowers boiler water temperature as heating load falls.
  2. Or use it only if the boiler is not used for any space heating.
  3. Or use it only if the boiler is part of a modular or multiple boiler system with total input of 300,000 Btu/h or more.
  4. Or use it only if the boiler is equipped with a tankless coil.

Outdoor reset override use limits

Viessmann · Vitorond 100 with Hydrostat outdoor reset

The outdoor reset override is meant for an external energy management system. Use it only when one of the listed conditions applies.

  1. Use the override only if an external energy management system lowers boiler water temperature as the load drops.
  2. Or use it only if the boiler is not used for space heating.
  3. Or use it only if the boiler is part of a modular or multiple boiler system with 300,000 Btu/h total input or more.
  4. Or use it only if the boiler has a tankless coil.

Outdoor reset override: when it may be used

Viessmann · VR1 22 to 33, 91 to 140

The outdoor reset override is only for use when one of these is true: an external energy management system lowers boiler water temperature as load drops; the boiler is not used for space heating; the boiler is part of a modular or multiple boiler system of 300,000 BTU/h or more; or the boiler has a tankless coil.

Outdoor reset pump behaviour at low outdoor temperature

Viessmann · Vitotronic 100 KW10B with outdoor sensor

With an outdoor sensor and internal outdoor reset or OpenTherm thermostat, the control starts calculating boiler water temperature at 37°F (3°C) outdoor and below. The boiler pump then runs continuously.

  1. Confirm the outdoor sensor is connected before testing outdoor reset.
  2. Expect the boiler pump to run continuously when outdoor temperature is 37°F (3°C) or below.

Outdoor sensor wiring can pick up interference

Viessmann · Outdoor temperature sensor wiring

Extending the outdoor sensor wire can expose it to electromagnetic interference. Keep the wire away from high voltage conductors and shield it correctly.

  1. Do not run sensor wires beside or near 120/240 VAC conductors.
  2. If that cannot be avoided, use stranded, twisted pair or shielded wire.
  3. Ground only one end of the shield.

Output aBJ function

Viessmann · Output aBJ on EA1

Output aBJ can run either the DHW recirculation pump or the fault message facility. The function is selected with coding address 36 in the General group.

  1. Select the output function with coding address 36 at the boiler control unit.

Overheating or gas supply fails to shut off

Viessmann · All CM2 models

Do not cut power to the pump in this case.

  1. Do not disconnect the electrical supply to the pump.
  2. Shut off the gas supply at a location outside the appliance.

Overheating or gas valve fails to close

Viessmann · Vitocrossal 300 CA3B

If the boiler overheats or the gas supply does not shut off, the circulating pump must keep its power.

  1. Do not disconnect the electrical supply to the pump.
  2. Shut off the gas supply at a location outside the appliance.

Overheating or gas valve failure

Viessmann · Vitotronic 200 and 300-K

If the boiler overheats or the gas supply does not shut off, do not disconnect the electrical supply to the pump. Shut off the gas supply at a point outside the appliance instead.

  1. Do not switch off power to the circulating pump.
  2. Shut off the gas supply at a location outside the appliance.
  3. Close the main gas supply valve if there is a dangerous condition, and deactivate main power.

Overheating or gas will not shut off

Viessmann · Vitocrossal 300 CU3A, all models

If the boiler overheats or the gas supply does not shut off, do not cut power to the circulating pump. Shut off the gas at a point outside the appliance.

  1. Do not disconnect the electrical supply to the pump.
  2. Shut off the gas supply at a location outside the appliance.

Override switch positions

Viessmann · Vitotronic 100 KW10B

Up turns the boiler pump on, enables stage 1 and 2 calls for heat, and runs the boiler on the adjustable high limit. Down is normal operation.

Owner checks and annual service

Viessmann · Vitocrossal 200 CI2

Owner-level checks and the required service interval. The end user must not adjust or service boiler components.

  1. Check system (water) pressure on the gauge regularly.
  2. Look for water on the floor from the pressure relief valve discharge, pipes, joints, valves or air vents.
  3. Have the boiler, burner and controls checked at least once a year by a qualified heating contractor.
  4. Correct any defects immediately.
  5. Do not allow unsupervised children near the boiler.

Owner checks between services

Viessmann · Vitocrossal 300 CU3A, all models

Items the owner should check regularly. Blocked venting is a carbon monoxide risk. Any blockage must be removed by a qualified heating contractor.

  1. Check that the vent or chimney is not blocked or partly blocked.
  2. Check the system water pressure on the pressure gauge.
  3. Check for water on the floor from the relief valve discharge or any pipe, joint, valve or air vent.
  4. Check flue pipes, joints, vent dampers and side wall terminals for moisture, water or rust.
  5. Make sure nothing blocks combustion and ventilation air and that no chemicals, gasoline or flammable materials are stored near the boiler.
  6. Keep unsupervised children away from the boiler.

Owner maintenance and service interval

Viessmann · Vitocrossal 300 CA3B Dual Fuel

Only a qualified heating contractor should service the boiler, burners and controls. Soot build-up on the heat exchanger lowers efficiency and raises flue gas temperature. Indirect-fired DHW storage tanks must be serviced within two years of installation and regularly after that. The owner or dedicated staff should do the checks in the Service Schedule (p. 41).

  1. Have a qualified heating contractor service the system regularly.
  2. Service indirect-fired DHW tanks within two years of installation, then regularly.
  3. Owner checks the items listed in the Service Schedule on p. 41.

Oxygen diffusion barrier tubing

Viessmann · Underfloor heating loops

Underfloor plastic tubing without an oxygen diffusion barrier causes corrosion. The warranty does not cover resulting leaks.

  1. Separate non-barrier underfloor tubing from the boiler with a heat exchanger.
  2. Use oxygen diffusion barrier tubing where possible.

Parameter R62 after a flame loss

Viessmann · Vitocrossal 200 CM2 burner control unit

After a fail of flame during operation the burner cannot modulate at partial load (20%) for one hour. During this time the minimum input for R62 is 50 to 60%. Standby before the hour is up does not clear the setting.

  1. To clear the one hour lockout early, press the reset button or switch the burner control off.

Parameter settings reference

Viessmann · Parameters 1706.0 and CAI feedback

Parameter settings for CAI, changeover contact and 0-10V are set in the Service Instructions or system configuration.

  1. Refer to the Service Instructions for parameter settings.

Parameters shown with no function

Viessmann · Vitocrossal 200 CI2 control unit

These parameters appear on the display but do nothing on this boiler. Do not expect a change from them.

Parts list for ordering

Viessmann · Vitorond 100 VR1 replacement parts

Provide the boiler model and serial number from the rating plate when ordering. Order from your Viessmann distributor.

  1. Use the reference numbers below when identifying parts.

Parts ordering information

Viessmann · Vitodens 200-W B2HA 19, 28, 35

Parts must be ordered from the Viessmann distributor using the model number from the rating plate and the serial number.

  1. Get the model number from the rating plate.
  2. Get the serial number.
  3. Order the parts from your Viessmann distributor.

Parts to keep on hand for service calls

Viessmann · All VD2 sizes 320 to 1080

Stock these items for every service call. Full parts list is in the Parts List section.

  1. Carry O-rings for the mixing valve(s).
  2. Carry sealant rope for the combustion chamber door.
  3. Carry refractory for the combustion chamber door.
  4. Carry sealant rope for the clean-out opening cover.
  5. Carry glue for the sealant rope.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.