Viessmann Boiler: High limit safety cut-out test
High limit safety cut-out test on a Viessmann boiler: Tests the high limit safety cut-out. Make sure there is adequate heat transfer before testing. On lag boilers the test mode is only reachable through the software tool, and you exit with the chimney sweep button on the home screen.
Applies to: Vitocrossal 200 CI2 boilers
How to fix high limit safety cut-out test: step by step
- Open the service menu and enter password "viservice".
- Go to "Service", then "Test mode", then "Test mode".
- Confirm with OK. Ensure adequate heat transfer.
- Use the exit button to end the test.
- On a lag boiler, exit with the chimney sweep button on the home screen.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
More service & test modes tips for boiler
Source: Viessmann Vitocrossal 200 CI2 service instructions, p. 57. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.