Service & test modes: Boiler tips (part 5 of 10)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on service & test modes for boiler. Check each one against the manual for your exact model before acting.

Enter service menu and run actuator test

Viessmann · Service menu, actuator test

Used to force the burner to low fire or high fire for combustion testing. The key pressed with OK is not legible in the source text.

  1. Press OK and the second key together for about 4 seconds to open the service menu.
  2. Select Actuator test.
  3. Select Base load OFF to run low fire, or Full load OFF to run high fire.
  4. Select all actuators off to end the test.

Enter service mode for test and setting functions

Viessmann · Service menu entry

Entering SERV mode is the first step for all manual service functions on this boiler.

  1. Turn both selector dials to the centre position together. SERV appears on the display.
  2. Complete the next step while SERV is still shown, or the mode will not accept changes.

Enter the emissions/relay test mode

Viessmann · Vitocrossal 300 CA3B Dual Fuel burner control unit

Starts the CO2 test mode and shows the relay test status.

  1. Open the gas shut-off valve.
  2. Start the burner with the emissions test switch enabled at the boiler control unit.
  3. While the burner runs, press the two buttons shown on page 66 together and hold for more than 2 seconds.
  4. Status shows "P" (relay test). Service shows the modulation level in %: 100 = upper heating input, 0 = lower heating input.

Enter the relay test for emissions measurement

Viessmann · Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Used to hold the burner at set output while measuring combustion. Only one burner may run during adjustment; the other boiler burners must be off.

  1. Open the gas shut-off valve.
  2. Start the burner with the emissions test switch enabled at the boiler control unit.
  3. Press buttons S, E and D together and hold for more than 2 seconds.
  4. Check the display: Status shows P (relay test) and Service shows modulation in % (100 = upper output, 0 = lower output).

Enter the service level

Viessmann · Vitotronic 200 and Vitotronic 300-K

Service level is entered by holding OK together with a second button (symbol not legible in this copy) for about 4 seconds. Service level exits automatically after 30 minutes.

  1. Press OK and the second button together for about 4 seconds to enter the service level.
  2. Use the service menu overview to reach Diagnosis, Actuator test, Coding level 1 or Coding level 2 as needed.

Extended menu layout and Test mode entry

Viessmann · Vitocrossal 300 CU3A boilers with Vitotronic 200 KW6B control

The extended menu's main branches are Heating, DHW, Information, Settings, Test mode, Solar energy and General. Heating and DHW hold the heating circuit, time program and temperature setpoint entries. Settings holds the clock, language, display and unit options, and the Reset data entry is also here. Test mode is a separate branch on the same menu. Some entries appear only if the matching equipment is installed.

Field test the fixed high limit (CSD-1)

Viessmann · Vitodens 100/200 boilers

Where required by law, the fixed high limit can be tested in the field. The fixed high limit trip produces a fault that needs a manual reset. Viessmann is not responsible for damage caused by overheating during this test.

  1. Method 1: close the boiler valve and jump the flow switch. Run the boiler at high fire, setting coding address 06 to max on WB2B models, and let the temperature rise until the fixed high limit trips. Then slowly open the boiler valve to cool it.
  2. Method 2: throttle the boiler valve so the burner runs with minimal flow. Run the boiler to high fire using the relay test. When the burner shuts down on the electronic limit, close the ball valve to stop flow and let the temperature rise until the fixed high limit trips. Then slowly open the valve to cool it.
  3. Method 3: disconnect one wire from the limit switch. This creates a control fault that requires manual reset.
  4. Reset the boiler control manually after the test.

Fill program

Viessmann · System fill with control unit on

Code 2F:2 starts the pump when the system is filled with the control unit on. The burner shuts down if this function is enabled through coding address 2F. The program turns off automatically after 20 minutes and 2F resets to 0.

  1. Set code 2F:2 at the control unit to start the fill pump.
  2. Fill the system.
  3. Wait for the program to end after 20 minutes, or confirm that coding address 2F has returned to 0.

Fill program (system filling with control unit on)

Viessmann · Vitodens 222-F B2TB

Runs the circulation pump to help fill the system. The burner shuts down if this function is enabled.

  1. Switch the control unit on.
  2. Set coding address 2F to 2 (code 2F:2) to start the pump.
  3. Note that the burner shuts down while the function is enabled through coding address 2F.
  4. The program turns off by itself after 20 minutes and coding address 2F resets to 0.

Filling program (service function)

Viessmann · Vitodens 200-W B2HA 19, 28, 35

The filling program is started from the service menu. Its button combination is not legible in the source extraction.

  1. Press OK and the marked button together for about 4 seconds.
  2. Select Service functions.
  3. Select Filling.
  4. To end the function, press OK or the marked button.

Flow switch check

Viessmann · Vitodens 222-F B2TB 19, 35, 68, 125

The B2TB has a flow sensing device. If flow is too low the switch opens, the burner shuts down, and it will not restart until adequate flow returns.

  1. Throttle the water flow to or from the boiler.
  2. Confirm the boiler shuts down once flow drops below its safe operating set point.
  3. Restore flow and confirm the burner restarts.

Flue gas test mode

Viessmann · Vitodens 200-W B2HA 45, 60

Test mode is found in the extended menu of the operating manual. Flue gas test ON starts a firing cycle that goes to high fire.

  1. Open the extended menu and select 'Test mode'.
  2. Select 'flue gas test ON' and press OK.

Flue gas test mode from the extended menu

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

Test mode with flue gas test ON makes the burner start and ramp to high fire. Used for combustion checks and for the high limit test.

  1. Open the extended menu on the boiler control.
  2. Select Test mode, then select flue gas test ON.
  3. Press OK to start the firing cycle.

Front panel indicators and switches

Viessmann · Vitocrossal 200 CM2 186 to 620

The front panel has a green ON indicator, a red fault indicator, an emissions test switch (service use only) and the ON/OFF switch. MCBs/fuses are also located here.

  1. Check the green ON indicator to confirm the boiler is powered and on.
  2. Check the red fault indicator when the boiler is not running.
  3. Use the emissions test switch for service purposes only.

Functional checks of high limits

Viessmann · Fixed and adjustable high limits

The fixed high limit is checked with the TEST button. The adjustable high limit is checked through emissions test mode.

  1. Fixed high limit: use the TEST button (7819 314) to run the functional check.
  2. Adjustable high limit: run the functional check in emissions test mode.

Heat generator bus scan after restart

Viessmann · Versatronik 200 cascade controller

After a restart or new configuration the controller scans the bus for heat generators for about 1 minute. The display shows SCAN. Manual output entries are blocked during this time.

  1. Wait for the SCAN to finish (about 1 min).
  2. Check the list of detected boilers. An X shows a heat generator that answered on the bus.
  3. Check each output value. If a heat generator gave no output, 15 kW is entered; change it if needed.
  4. If the list is correct, save it with Config OK.

Heat rooms without DHW

Viessmann · Vitotronic 300-K, MW1B

Lets the rooms heat while DHW is not wanted, by lowering the DHW set temperature to the minimum value.

  1. Open the extended menu.
  2. Select the heating circuit if needed.
  3. Select "Heating".
  4. Select "Heating program" and choose "Heating and DHW".
  5. Go back until the menu shows "DHW".
  6. Select "DHW", then "Set DHW temperature".
  7. Set the value to 50° F (10° C).

High limit safety cut-out test

Viessmann · Vitocrossal 200 CI2 boilers

Tests the high limit safety cut-out. Make sure there is adequate heat transfer before testing. On lag boilers the test mode is only reachable through the software tool, and you exit with the chimney sweep button on the home screen.

  1. Open the service menu and enter password "viservice".
  2. Go to "Service", then "Test mode", then "Test mode".
  3. Confirm with OK. Ensure adequate heat transfer.
  4. Use the exit button to end the test.
  5. On a lag boiler, exit with the chimney sweep button on the home screen.

Ionization current acceptance limit

Viessmann · Vitocrossal 300 CA3B Dual Fuel burner

Minimum ionization current needed for a stable flame.

  1. Confirm the ionization current reaches at least 3 µA for approx. 2 to 3 sec after the combination gas valve opens and while in operation.

Maintenance display and service messages

Viessmann · Boiler control display

The maintenance display can be confirmed from the home screen. If several faults are active, a Service messages list appears in orange.

  1. On the maintenance display, tap Confirm.
  2. If several fault messages are active, tap Service messages to see the orange list.

Manual mode and service display

Viessmann · Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

The burner must be running to use the service display and manual mode. The service display shows the current modulation level in %.

  1. With the burner running, press B and S together for more than 2 seconds. The burner enters manual mode, P shows under Status, and the modulation level flashes under Service.
  2. Press B to lower the heating output, down to 0.
  3. Press Y to raise the heating output, up to 100.
  4. Press B and S together for more than 2 seconds to return to modulating mode.

Mixing valve moves during relay test

Viessmann · Vitotronic 200 KW2 mixing valve motor

The control unit opens and closes the mixing valve during the relay test, so you can confirm motor operation there.

  1. Run the relay test on the control unit.
  2. Watch the mixing valve open and close.

Open the information and configuration menu

Viessmann · Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

The information and configuration menu is opened from the operating display. It times out after 20 seconds with no button press. Menu item 5 shows process information and item 6 is used to change operating parameters. Make changes only when the burner control is on standby.

  1. Hold button S for more than 2 seconds until the menu indicator blinks.
  2. Scroll through the menu items with the Y/B buttons.
  3. Press button S to select an item. It is shown under Service.
  4. Make changes only when the burner control unit is on standby.

Open the service actuator test

Viessmann · Vitocrossal 200 CI2 control unit

Access the actuator test used for burner output selection and test firing.

  1. Tap the service button.
  2. Enter the service password "viservice".
  3. Confirm with the check button.
  4. Select "Actuator test" and confirm.

Override switch for flue gas testing

Viessmann · Vitotronic 100 GC1 Optolink/override switch board, Part 7820 165

The override switch on the Optolink/override board lets you run the boiler at constant water temperature for a short time, for flue gas measurement.

  1. Set the override switch to the h position.
  2. Expect the burner to start (it can be delayed by a fuel preheater or flue gas damper).
  3. Expect all pumps to run.
  4. Expect boiler water temperature to be held by the adjustable high limit R.

Override switch function

Viessmann · Vitotronic 100 KW10B

In the up position the override switch turns the boiler pump on and enables stage 1 and 2 calls for heat. The boiler then runs to the adjustable high limit temperature. In the down position the system runs normally.

  1. Set the override switch up to force pump run and stage 1 and 2 heat calls for testing.
  2. Return the switch down to normal operation when testing is finished.

Override switch position h

Viessmann · Printed circuit board override switch

Position h on the override switch is used to analyze flue gas with a briefly raised boiler water temperature.

  1. Set the override switch to position h.
  2. Confirm all pumps start.
  3. Confirm the mixing valve is in control function.

Override switch position h (manual operation)

Viessmann · Vitotronic 100 GC1 optolink/override switch

In position h the control runs the burner and pumps and controls boiler water temperature by the adjustable high limit. Use it for flue gas measurement with briefly raised boiler temperature.

  1. Set the override switch to position h.
  2. Expect burner start, which can be delayed by fuel oil pre-heating or accessories.
  3. Confirm all pumps start.
  4. Watch boiler water temperature, which is controlled by the adjustable high limit.

Participant check (LON)

Viessmann · Vitotronic 300 GW2 with LON module

Checks LON participants. Only works with the LON communication module installed.

  1. Press the w and OK buttons together for about 2 seconds to start.
  2. Press the w and OK buttons together for about 1 second to exit.

PCB extension LED and emissions test switch

Viessmann · PCB extension for heating circuits 2 and 3 with mixing valve

The PCB extension for heating circuits 2 and 3 has a red fault display, a green operating mode display and an emissions test switch.

  1. Check the red fault display (V1) for a fault.
  2. Check the green operating mode display (V2) for operating status.
  3. Use the emissions test switch (S3) on the PCB extension for emissions testing.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.