Viessmann Boiler: Gas consumption meter setup
Gas consumption meter setup on a Viessmann boiler: The boiler has an integral gas meter. Accuracy depends on the gas volume correction factor (parameter 1098.4) and the gross calorific value (parameter 1098.5). Both can be set on the HMI or in ViGuide Web Pro. Get the values from the gas supplier or the gas bill. Lag boiler consumption is set by selecting that boiler's HMU in ViGuide Web Pro.
Applies to: Vitocrossal 200 CI2 boilers
How to fix gas consumption meter setup: step by step
- Get the gas volume correction factor and gross calorific value from the supplier or gas bill.
- Enter them at parameters 1098.4 and 1098.5.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
More settings shortcuts tips for boiler
Source: Viessmann Vitocrossal 200 CI2 service instructions, p. 80. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.