Settings shortcuts: Boiler tips (part 5 of 10)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on settings shortcuts for boiler. Check each one against the manual for your exact model before acting.

DHW tank aquastat limit

Viessmann · DHW tank aquastat on Versatronik 10.WB1 systems

The DHW tank aquastat must not be set above 55 °C (131 °F).

  1. Confirm the DHW tank aquastat setting is 55 °C (131 °F) or lower.

DHW temperature and time program

Viessmann · DHW heating

DHW temperature changes affect all heating circuits. Automatic mode starts DHW reheating half an hour before the standard heating phase. Individual phases can be set instead, up to four per day. Allow heat-up time before the hot water is needed.

  1. Open the extended menu and select DHW.
  2. Select DHW setpoint temperature and set the value.
  3. Select DHW schedule and choose Automatic or Individual.
  4. For individual phases, set start and end times for each phase.

DHW time program

Viessmann · DHW heating

Automatic program starts DHW heating 30 minutes before the first heating circuit warm-up. Individual programs allow up to four switching times per day for DHW and the DHW circulation pump. Once started, DHW heating always finishes.

  1. Select automatic or individual program on the timer.
  2. For individual heating circuit timing, set coding 7F.
  3. Set up to four DHW circulation pump times if needed.

DHW time program and heating circuit timing (coding 7f)

Viessmann · DHW pump and DHW recirculation pump scheduling

Automatic DHW heating starts 30 min before the heating circuit heat-up phase. Individual programs allow up to 4 DHW time phases per day for every weekday.

  1. Detached house, coding 7f:1: heating times for heating circuit 1 are used for all circuits. Individual DHW pump and recirculation phases apply to all heating circuits.
  2. Apartment building, coding 7f:0: each heating circuit uses its own heating times in automatic mode, and individual DHW phases can be set per circuit.
  3. Tank heating cycles always finish regardless of the time program.

DHW time program and recirculation pump timing

Viessmann · Vitocrossal 300 CU3A

Between DHW time phases the tank is not heated and only frost protection runs. Allow for the time the tank needs to reach temperature. The DHW recirculation pump can run in Automatic mode or in up to 4 set time phases per day. Only run it when hot water is actually drawn.

  1. Open the extended menu.
  2. Select 'DHW'.
  3. Select 'DHW time program' for DHW heating, or 'DHW circ time prog' for the recirculation pump.
  4. Set the required time phases.

DHW timer schedule for any-time production

Viessmann · Applications 1 and 2

If domestic hot water can be made at any time, the timer is set to run all day.

  1. Set the timer schedule as desired.
  2. For any-time DHW production, program the timer from 0:00 to 24:00.

DIP switch for separate room temperature sensor

Viessmann · Vitotrol 200 and Vitotrol 300 with separate room temperature sensor

When a separate room temperature sensor is connected to a remote control, set the matching DIP switch to ON on the remote control's printed circuit board (rear of top casing).

  1. Vitotrol 200: set DIP switch S6.3 to ON.
  2. Vitotrol 300: set DIP switch S30.3 to ON.
  3. For Vitotrol 300 also set coding switch 3 to ON when using the separate room temperature sensor (see the room temperature sensor section).

Display contrast and brightness

Viessmann · Vitotrol 300A remote control

Adjust display contrast, brightness, and whether the backlight stays on in standby.

  1. Contrast: extended menu, Settings, Contrast, then set the contrast.
  2. Brightness: extended menu, Settings, Brightness, Control, then set the brightness.
  3. Standby backlight: extended menu, Settings, Brightness, Standby, then choose on or off.

Display contrast, brightness and language

Viessmann · Vitocrossal 300 CU3A

Adjusts the screen for readability. Brightness can be set separately for the control screen and the screen saver. Language is chosen from the menu and accepted with OK.

  1. Open the extended menu.
  2. Select 'Settings'.
  3. For contrast, select 'Contrast' and set the value.
  4. For brightness, select 'Brightness', then 'Control' or 'Screen saver', and set the value.
  5. For language, select 'Language', choose it and press OK.

Economy mode on a heating circuit

Viessmann · Heating circuits on Vitotronic 300-K

Economy mode is an energy saving function. It can only be turned on while the system is in standard heating mode.

  1. From the home screen, select the heating circuit in the header.
  2. Select economy mode and set it to ON, then confirm.
  3. To end it, set economy mode to OFF and confirm.
  4. It also ends automatically when the time program switches to reduced heating.

Enable economy mode for a heating circuit

Viessmann · Heating circuits 1 to 3

Economy mode is an energy saving function for one heating circuit. It can only be turned on while the system is in standard heating mode.

  1. Press Menu, then Heating.
  2. Choose the heating circuit (1, 2 or 3).
  3. Press Economy mode and select the white frame.
  4. Press OK to confirm.

Enable or end economy mode for a heating circuit

Viessmann · Vitotronic 300-K, MW2C

Economy mode is a heating circuit energy saving function. It can only be switched on while the system is in standard heating mode. It ends by itself when the time program switches the circuit to reduced heating.

  1. From the home screen, open the header and select the heating circuit (1, 2 or 3).
  2. Select 'Economy mode'.
  3. Choose 'ON' to enable or 'OFF' to end it, then confirm.

Enable the INT interlock in Specifications

Viessmann · Versatronik 300 Cascade Control, INT interlock

The interlock must be turned on in the control menu before it works. Once it is on, an open contact shows C1 and turns the fault output on.

  1. Press and hold ENTER for 5 seconds.
  2. Press the up arrow to reach the Specifications menu.
  3. Find the Interlock item and press ENTER to set it to Enable.
  4. Press ESC to leave the menu.

Ending Comfort mode

Viessmann · Vitocrossal 300 CA3B

Comfort mode for a heating circuit can be turned off by hand from the home screen. It also ends on its own when the system switches to standard heating mode under the time program, or after 8 hours. Changing the automatic end needs the heating contractor.

  1. From the home screen, select Heating circuit 1, 2 or 3 as required.
  2. Select Comfort mode.
  3. Set it to OFF.
  4. Confirm.

Enter heating timer programs

Viessmann · Versatronik COMO OT

Heating timer programs are entered per weekday or block (Mo-Fr, Sa-Su, Mo-Su). Each switch-on and switch-off time must be entered. Use dashes to disable a timer.

  1. Press Plus three times to reach HTGPROG.
  2. Select the weekday or block.
  3. Set the first switch-on time and room temperature, then confirm.
  4. Set the first switch-off time and confirm.
  5. Enter switch-on and switch-off times 2 and 3 the same way.
  6. Select the next weekday or block, or leave with RETURN.
  7. Enter dashes for any time not used to deactivate that timer.
  8. Note that times are saved only after all times for a weekday or block are entered.

Enter holiday program

Viessmann · Versatronik COMO OT

The holiday program uses day counts. The start is always taken at 12:00 pm, and the end is also at 12:00 pm.

  1. Open the cover and press Plus six times to reach HOLIDAY.
  2. Press Prog to open START-HOLIDAY and enter the number of days until the holiday starts.
  3. Enter the first holiday day, not the travel day, as the start.
  4. Press Prog to open HOLIDAY-DUR and enter the holiday length in days.
  5. Press Mode selector to end the holiday programming.

Erase heating time cycles

Viessmann · Vitotronic 300 Model GW2

Clears a heating cycle by setting its start and finish to blank times.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button so it lights up.
  3. Press the heating time program button.
  4. Press up or down until the required 'Heating cycle OFF' appears.
  5. Press up or down until '– – : – –' appears for the finish time.
  6. Press OK until the display returns to the boiler temperature.
  7. Close the hinged cover.

Fixed high limit setting is changed by coding card only

Viessmann · Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

The fixed high limit safety cut-out is preset to 210°F (99°C). It can only be changed by changing the coding card. This is separate from the adjustable max boiler water temperature in menu 6, item 4.

  1. Refer to the control section of the installation instructions before changing the coding card.

Flashing display means settings can be entered

Viessmann · Vitotronic 100, GC1

When the data in the display window flashes, new settings can be entered with the value selector buttons and the confirmation button.

Functions adjustable from the Vitotrol remote

Viessmann · Vitotrol 200 (p. 130), Vitotrol 300 (p. 132)

Vitotrol 200 and Vitotrol 300 allow day/normal temperature, reduced temperature, domestic hot water temperature, heating program, holiday program, switching times and economy/party mode to be adjusted. Changes can also be made through coding addresses A0, b0 to b9, C0 to C2, E1 and E2.

  1. Use the remote's controls to set the desired function.
  2. For changes beyond the remote, use the listed coding addresses on the control unit.

Gas consumption meter setup

Viessmann · Vitocrossal 200 CI2 boilers

The boiler has an integral gas meter. Accuracy depends on the gas volume correction factor (parameter 1098.4) and the gross calorific value (parameter 1098.5). Both can be set on the HMI or in ViGuide Web Pro. Get the values from the gas supplier or the gas bill. Lag boiler consumption is set by selecting that boiler's HMU in ViGuide Web Pro.

  1. Get the gas volume correction factor and gross calorific value from the supplier or gas bill.
  2. Enter them at parameters 1098.4 and 1098.5.

Heat rooms only, no DHW

Viessmann · Vitotronic 200 and 300-K

Used when the rooms must be heated but domestic hot water is not wanted. The DHW set temperature is lowered to the minimum value shown in the manual.

  1. Open the extended menu.
  2. Select the heating circuit if needed.
  3. Select "Heating", then "Heating program".
  4. Select "Heating and DHW".
  5. Go back until the menu is shown.
  6. Select "DHW", then "Set DHW temperature".
  7. Set the DHW temperature to 50 °F (10 °C).

Heating circuit default display controls

Viessmann · Vitocrossal 200 CI2 heating circuit or continuous operation display

On the heating circuit or continuous operation default display you can raise or lower the room temperature (weather-compensated) or supply temperature (constant operation). You can also set the Heating or Standby mode, switch Extended heating on or off, and open the central heating time program. The temperature shown is the target room temperature or target supply temperature for the current time phase.

  1. Use the up or down buttons to change the room or supply target.
  2. Use the operating program button to choose Heating or Standby mode.
  3. Use the Extended heating button to switch that function on or off.
  4. Use the time program button to open the central heating time program.

Heating programs in the standard menu

Viessmann · Vitodens 200-W B2HB with Vitotronic control

The standard menu sets room temperature and the heating program for the circuit shown in the header. Programs: standby with frost protection, DHW only, or heating plus DHW. Settings revert to the standard menu after 2 minutes.

  1. Select the required room temperature and confirm with OK.
  2. Select the required heating program and confirm with OK.
  3. If the system has 2 or 3 heating circuits, select HC1, HC2 or HC3 to show in the standard menu.

Holiday program

Viessmann · Vitocrossal 300 CA3B

The holiday program applies to all heating circuits and runs from 00:00 on the day after departure to 00:00 on the return date. Central heating goes to reduced room temperature in Heating and DHW circuits, and is off with frost protection in DHW only circuits. DHW heating is off with frost protection for the tank.

  1. From the home screen, open Holiday program.
  2. Set the departure date and the return date.
  3. Confirm.
  4. To cancel or delete the holiday program, open Holiday program from the home screen and use the delete option (shown as an icon in the manual).

Holiday program (energy saving for central heating)

Viessmann · Vitocrossal 300 CU3A

Lowers central heating to the reduced room temperature for the length of an absence. DHW heating is switched off during the holiday, with DHW tank frost protection still active. The program starts at 00:00 on the day after departure and ends at 00:00 on the day of return, so the time program runs on the departure and return days. It applies to all heating circuits. Heating circuits set to 'Only DHW' get no central heating and only boiler and DHW tank frost protection. The set dates can be checked under Information.

  1. Open the extended menu.
  2. Select 'Heating'.
  3. Select 'Holiday program'.
  4. Enter the departure and return dates.

Language and measuring units

Viessmann · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Language and units (Metric or Imperial) are set from the Settings menu.

  1. For language: Menu > Settings > Language, pick the language, press OK.
  2. For units: Menu > Settings > Measuring units, pick Metric or Imperial, press OK.

Language selection

Viessmann · Vitotrol 300A remote control

Change the menu language.

  1. Open the extended menu.
  2. Select Settings, then Language.
  3. Select the required language.

Limit DHW temperature when using the second DHW set-point

Viessmann · Vitotronic 100 GC1, coding 56 and 58

If coding 58 is used, keep high limit R at least 10 °C / 18 °F above the DHW temperature the extra function reaches. Never let it go above the maximum allowed for the DHW tank.

  1. Check the maximum DHW temperature allowed by the tank installation instructions.
  2. Set coding 58 to the second set-point value.
  3. Set high limit R at least 10 °C / 18 °F above the temperature reached with the extra function, without exceeding the tank maximum.

Limit domestic hot water input

Viessmann · Vitodens 200-W B2HA 19, 28, 35

DHW heating input can be limited separately from heating.

  1. Enter coding level 2.
  2. Change coding address 6F to the required limit.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.