Viessmann Boiler: Flue connection and venting practice
Flue connection and venting practice on a Viessmann boiler: Keep the flue run to the boiler as short as possible with a slight rise of 2-3 degrees and no sharp bends. Support all venting components so connections carry no load or torque. The boiler flue collar is not designed to carry the weight of the vent, so the vent must be anchored per the venting manufacturer. A flue gas adaptor may be needed (supplied by the venting manufacturer) for stainless steel venting. Insert the adaptor fully into the flue outlet, and seat the vent fully into the flue gas collector. Check every joint for leaks with a certified leak detector. Escaping flue gas can cause fatal carbon monoxide poisoning. Refer to the common venting instructions for the Vitocrossal 200 CI2 when venting is shared. A motorized flue gas damper is available for common vented systems.
Applies to: Vitocrossal 200 CI2 399 to 2000
How to fix flue connection and venting practice: step by step
- Run the flue outlet to the flue pipe on the shortest route with a slight rise of 2-3 degrees.
- Avoid sharp bends in the flue run.
- Support all venting components so connections carry no load or torque.
- Anchor the vent with a system approved by the venting manufacturer.
- Fit a flue gas adaptor from the venting manufacturer if needed for stainless steel venting, fully inserted in the flue outlet.
- Seat the venting fully into the flue gas collector.
- Check all vent and coupling connections for leaks with a certified leak detector.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 Installation Instructions, p. 47-48. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.