Other: Boiler tips (part 17 of 45)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.

Finding the serial number for parts orders

Viessmann · All B2TB 19, 35, 68, 125 models

Parts orders need either the 16-digit serial on the bar code label or the 12-digit ASME/NB serial. Both are under the boiler front enclosure panel.

  1. Remove the front enclosure panels (see the front panel removal guide).
  2. Read the 16-digit bar code serial or the 12-digit ASME/NB serial.
  3. Give the boiler serial number when ordering replacement parts.

Fire in the boiler room

Viessmann · Vitodens 200-W B2HA 112, 150, 399, 530

If fire is seen coming from the appliance, call the fire department first. Do not fight the fire unless trained to do so.

  1. Shut down the boiler.
  2. Close the fuel shut-off valves.
  3. Use a tested class ABC fire extinguisher only if qualified.

Fire response

Viessmann · Boiler room fire

If the appliance is on fire, call the fire department. Only attempt to extinguish if qualified.

  1. Call the fire department immediately.
  2. Shut down the boiler.
  3. Close fuel shutoff valves.
  4. Use a tested class ABC fire extinguisher only if qualified.

Fitting the front panel

Viessmann · Vitocrossal 300 CU3A front panel

Refit the front panel by locating it on the pegs and securing it at the top.

  1. Place the front cover onto the locating pegs.
  2. Push the top of the panel in place.
  3. Secure the panel with the retaining screw.

Fixed high limit location for underfloor heating

Viessmann · Vitotronic 300 with underfloor heating

An adjustable high limit is required for underfloor heating. The fixed high limit goes in the heating supply pipe after the mixing valve and the heating circuit pump.

  1. Install the fixed high limit in the heating supply pipe downstream of the mixing valve and the heating circuit pump.
  2. Follow the limit thermostat installation instructions.

Fixed high limit warning

Viessmann · Vitotronic 100 GC1

If the fixed high limit is set to 99 °C / 210 °F, keep the adjustable high limit at or below 75 °C / 167 °F.

Flashing and storm collar selection

Viessmann · Roof and wall vent penetrations

Flashings and storm collars are field supplied and must suit the vent type.

  1. Use flashings and storm collars rated for Type B vent materials or better.
  2. Follow the installation instructions from the special venting manufacturer.

Flashing data in display means settings can be changed

Viessmann · Vitotronic 200-H HK1S and HK3S

When a value flashes in the display window, the control is waiting for a new setting to be entered.

  1. Use the setting buttons to enter the new value while it flashes.
  2. Confirm the entry with the confirmation button.

Flashing data in the display means input is open

Viessmann · HK1S and HK3S

Data flashing in the display window means the value can be changed now.

  1. Use the up/down buttons to set the value.
  2. Press the confirm button to store it; the value stops flashing.

Flashing data means it can be changed

Viessmann · Vitocontrol-S and Vitotronic 100, GC1

When the value in the display flashes, a new setting can be entered. Use the value selector to change it and confirm with the confirmation button.

  1. Wait for the value to flash in the display.
  2. Use the value selector to set the new value.
  3. Press the confirmation button to save it.

Flashing data means the value can be changed

Viessmann · Vitotronic 300 GW2

Flashing data in the display window means a new setting can be entered.

  1. Use the setting buttons to change the flashing value.
  2. Confirm to store it.

Flow check valve and underfloor heating notes

Viessmann · System layouts in Application Examples 2 and 3

A flow check valve is only needed when the piping connects to one common boiler return. For underfloor heating, the control measures supply and return water temperature, so the return water sensor is used.

Flow check valve on the supply side

Viessmann · Heating circuit supply

Install a spring-loaded flow check valve just downstream of the circulation pump. It stops unintended flow to space heating during DHW priority or summer operation.

  1. Install the spring-loaded check valve immediately after the circulation pump on the heating circuit supply.

Flue connection and venting practice

Viessmann · Vitocrossal 200 CI2 399 to 2000

Keep the flue run to the boiler as short as possible with a slight rise of 2-3 degrees and no sharp bends. Support all venting components so connections carry no load or torque. The boiler flue collar is not designed to carry the weight of the vent, so the vent must be anchored per the venting manufacturer. A flue gas adaptor may be needed (supplied by the venting manufacturer) for stainless steel venting. Insert the adaptor fully into the flue outlet, and seat the vent fully into the flue gas collector. Check every joint for leaks with a certified leak detector. Escaping flue gas can cause fatal carbon monoxide poisoning. Refer to the common venting instructions for the Vitocrossal 200 CI2 when venting is shared. A motorized flue gas damper is available for common vented systems.

  1. Run the flue outlet to the flue pipe on the shortest route with a slight rise of 2-3 degrees.
  2. Avoid sharp bends in the flue run.
  3. Support all venting components so connections carry no load or torque.
  4. Anchor the vent with a system approved by the venting manufacturer.
  5. Fit a flue gas adaptor from the venting manufacturer if needed for stainless steel venting, fully inserted in the flue outlet.
  6. Seat the venting fully into the flue gas collector.
  7. Check all vent and coupling connections for leaks with a certified leak detector.

Flue gas temperature and efficiency

Viessmann · Vitodens 222-F B2TB

Flue gas runs only about 5 to 15°C (9 to 27°F) above boiler return temperature. Efficiency depends on system return temperature and load.

  1. Keep system return temperatures low to get the best efficiency.
  2. Check the waterside flow information on page 8 before sizing piping.

Flue gas temperature and protection

Viessmann · Vitodens 222-F, B2TB 68 and 125

Flue pipes are rated for a maximum flue gas temperature of 230°F (110°C). No flue gas temperature protection is required because the maximum is not exceeded in any operating or malfunction condition.

Flue gas temperature rating

Viessmann · Coaxial PPS flue installations

Coaxial PPS flue pipes are rated up to 230°F (110°C) max flue gas temperature. Flue gas temperature protection is built in.

  1. Confirm the flue pipe material is rated for the expected flue gas temperature.
  2. Refer to the Vitodens venting installation instructions for full venting detail.

Flue products and nearby building materials

Viessmann · Vitodens 100-W B1HE/B1KE

Flue products vented close to unprotected surfaces can stain or damage some building materials. Shield exposed surfaces with corrosion-resistant material such as aluminum sheeting before fitting the vent termination. Install the vent termination on the leeward side of the building.

Follow the Viessmann maintenance schedule

Viessmann · Vitorond 200 VD2 boilers

Service the boiler according to the maintenance schedule in these service instructions. Annual professional service is needed before each heating season.

Free up DIN rail space for accessory adaptors (CM2)

Viessmann · CM2

Remove the four spare DIN terminals to make room for accessory adaptors.

  1. Pull up on the bottom front of the DIN rail clamp and set it aside.
  2. With a flat-head screwdriver, remove spare terminals 23, 24, 25 and 26 one at a time. Turn the screwdriver clockwise between rail and terminal base.
  3. Discard the removed terminals.
  4. Refit the DIN rail clamp: hook the latch over the top of the rail, then push the front down.

Free-standing frame mounting

Viessmann · Vitodens 200-W B2HA 80 to 100, 285 to 352

A boiler stand can be used for free-standing single-boiler installs. Anchor the stand securely to the floor; the manual recommends Hilti KB-TZ 3/8 x 4 concrete anchors or equivalent.

  1. Position the stand in the mechanical room.
  2. Anchor the stand to the floor with concrete expansion anchors (Hilti KB-TZ or equivalent).
  3. Confirm the stand is secure before mounting the boiler.

Freeze protection for unattended homes

Viessmann · Vitocrossal 300 CA3B

The boiler is not designed to protect water pipes from freezing. A shutdown during cold weather can cause pipe bursts and mold.

  1. Shut off the building water supply, drain the pipes and add potable-water antifreeze to drain traps and toilet tanks, or
  2. have someone check the building often in cold weather and call a service agency if needed, or
  3. install a reliable remote temperature sensor that alerts someone to freezing conditions.

Freeze protection is not guaranteed

Viessmann · Vitotronic 200 and 300-K

The boiler is not designed to prevent water pipes from freezing. If the boiler stays off during cold weather, pipes can freeze and burst. The boiler may shut down when frozen pipe conditions occur.

  1. If the home will be empty in cold weather, shut off the water supply and drain the pipes.
  2. Add potable-water antifreeze to drain traps and toilet tanks where appropriate.
  3. Alternatively, have someone check the building often or install a remote temperature sensor that alerts someone to freezing conditions.

Freeze protection when the system is drained

Viessmann · Vitocrossal 200 CM2 186 to 620

If the system is exposed to freezing and not protected with antifreeze, the system including the boiler must be drained.

  1. Close the valve before the automatic feed valve, if installed.
  2. Leave all other valves, air vents and drain valves open while draining.

Freeze protection when the system is not in use

Viessmann · Heating system with Vitocrossal 300 boiler

If the system is exposed to freezing temperatures and has no antifreeze, drain the system including the boiler.

  1. Close the valve before the automatic feed valve (if installed).
  2. Keep all other valves, air vents and drain valves open while draining.
  3. Drain the boiler and the system water.

Freeze-up protection

Viessmann · Heating circuit control

When outdoor temperature drops below +1 °C / 34 °F the control holds a supply temperature of 10 °C / 50 °F. The frost limit can be changed with coding A3.

Freezing protection when the home is left unattended

Viessmann · All CM2 models

The boiler is not designed to protect water pipes from freezing and may shut down in cold weather.

  1. Shut off the water supply, drain the water pipes and add potable-water antifreeze to drain traps and toilet tanks, opening faucets where appropriate.
  2. Or have someone check the building often in cold weather.
  3. Or install a reliable remote temperature sensor that alerts someone to freezing conditions.

Fresh air and contaminated combustion air

Viessmann · Vitodens 200-W B2HA 45, 60

The boiler needs adequate combustion and ventilation air. Do not operate it where combustion air is contaminated by dust, lint or chemicals, such as construction sites, garages, laundries or near pools.

  1. Confirm the boiler room has adequate combustion and ventilation air.
  2. Check the boiler room for chemicals and dust before start-up.
  3. Have the boiler inspected and serviced at least once a year.

Front cover and connections

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

Operate the boiler only with the front cover in place. Use approved sealant or PTFE tape on field fittings.

  1. Never run the boiler with the front cover off.
  2. Use approved pipe sealant or teflon tape on the installation fittings.
  3. Make the heating water and gas connections in the field, and the power supply per the electrical connections section.
  4. Keep the maximum ambient temperature at or below 104°F (40°C) when making connections.

Front cover and service access

Viessmann · Vitodens 222-F B2TB 19, 35, 68, 125

There are no user-serviceable parts on the boiler, burner or control. The boiler must never run with the front cover removed.

  1. Keep the front cover in place during operation.
  2. Leave service to a licensed professional heating contractor.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.