Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann Boiler: Enter emissions test mode

Updated · by Aurora Star Tech Inc.

Enter emissions test mode on a Viessmann boiler: Test mode lets you run the burner at high or low fire for combustion checks. The status display shows P (relay test) and the service display shows modulation level in percent: 100 is upper input, 0 is lower input.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocrossal 200 CM2 186 to 311

How to fix enter emissions test mode: step by step

  1. Open the gas shut-off valve.
  2. Enable the emissions test switch on the boiler control unit.
  3. Start the burner.
  4. At the same time press the S F and B G buttons and hold for more than 2 seconds.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX

More service & test modes tips for boiler

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 16. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977