Clear the fault memory

Viessmann · Vitocrossal 200 CM2 burner control unit

Deletes all stored fault entries from the operating display.

  1. Press and hold S for longer than 2 seconds until the symbol flashes.
  2. Press Y until 4 shows under Service, then press S. 4 shows under Status.
  3. Press Y until 3 shows under Service.
  4. Press S. 1 shows under Status and dEL under Service.
  5. Press S to confirm. 1 under Service means deleted, 0 means it failed.
  6. Press S to return to the operating display.

Coding 8F: menu lock and emissions test mode

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

Address 8F controls whether the standard and extended service menus are available and whether emissions test mode can be enabled. The new value only takes effect after you exit the service menu.

  1. Open coding address 8F and select the menu access level needed (0, 1 or 2).
  2. Exit the service menu so the change takes effect.
  3. Use emissions test mode only where the setting allows it (8F:1 or 8F:2).

CSD-1 field test of fixed high limit

Viessmann · Vitocrossal 300 CU3A 26 to 199

Where required by law, test the fixed high limit by simulating an overheat. Viessmann is not responsible for damage caused by overheating during this test. A tripped fixed high limit needs a manual reset of the control.

  1. Run the boiler to high fire using the relays test.
  2. Throttle the boiler valve until the burner runs with as little flow as possible.
  3. When the burner shuts down on the electronic limit, close the ball valve to stop the flow.
  4. Let the boiler temperature keep rising until the fixed high limit trips.
  5. After the fixed high limit trips, slowly open the boiler valve to cool the boiler down.
  6. Reset the boiler control manually.

Diagnosis and service scans

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

Service scans show live values such as outdoor temperature, boiler and DHW setpoints and actual temperatures, supply temperatures, system type, software versions, LON and KM BUS participants, remote control type and pump type. A brief scan shows lines 1 to 8 with fields 1 to 6. The page does not show the button used to start scans, so check the control display.

  1. Use the scan function on the control to show values. Read the value names on the display and match them to the scan table.
  2. Use "D" to reset the adjusted outdoor temperature to the actual outdoor temperature where the display offers it.
  3. Use the brief scan (lines 1 to 8) to check system type, software versions, and communication participants.

Diagnosis and service scans (brief scan lines 1 to 8)

Viessmann · Vitodens 200-W B2HB 19 to 35, 68 to 125

The control unit can scan a set of values in numbered lines. Which values appear depends on the installed system. Lines 1 to 8 cover system type, software and appliance version, burner control unit, flow rate sensor, and LON addressing. Line 9 covers remote control type, line 10 covers pump type, and line 11 covers mixing valve extensions. The manual's scan table is partly jumbled in this extract, so check the full table on the original page.

  1. Use the diagnosis scan on the control unit to read the values.
  2. Line 1: system type (01 to 10), control unit software version, programming unit software version.
  3. Line 2: appliance version and device identification.
  4. Line 4: burner control unit type and version.
  5. Line 6: flow rate sensor switching state (flow rate too low or not present).
  6. Line 9: remote control type (0 none, 1 Vitotrol 200 series, 2 Vitotrol 300 series or Vitohome) and its software version for each heating circuit.
  7. Line 10: internal and external pump type (0 none, 1 Wilo, 2 Grundfos) and variable speed pump status.
  8. Line 11: mixing valve extension present for heating circuits M2 and M3.

Download the fault history (last 10 faults)

Viessmann · HK1S, HK3S

The control saves the 10 most recent faults, sorted by date. Fault 1 is the newest. All saved faults can be cleared with 'D'.

  1. Press the two keys shown in the manual together for about 2 seconds (key symbols unclear in this text).
  2. Scroll through the saved faults with the up or down key.
  3. To clear the whole history, select 'D'.
  4. Press the confirm key to exit.

Emissions (flue gas) test mode

Viessmann · Vitocrossal 300 CU3A with Vitotronic 200 KW6B

For use only by a certified technician during the annual inspection. The burner runs, the pumps start, mixing valves stay in control, and the temperature controller regulates boiler water temperature. Start-up can be delayed, for example by fuel oil preheating. It can be started even if the heating contractor has locked the controls.

  1. Open the extended menu.
  2. Choose Test mode.
  3. Choose Flue gas test °C ON.
  4. To end the test, wait for the automatic stop after 30 minutes or press OK.

Emissions test function

Viessmann · CA3B Dual Fuel 2.5 to 6.0

Enable the emissions test on all control units. It starts the burner, starts all pumps and keeps the mixing valve on control. Short runs go to full output; long runs drop to modulating so the boiler does not cycle.

  1. Enable the emissions test function on all control units.
  2. For runs under 30 min, the burner runs at 100% until the temperature limiter in the burner control unit switches it off, then cycles at 100% around the limiter value.
  3. For runs over 30 min, the boiler water is held at its maximum set value (example 194 °F / 90 °C) and the burner modulates.

Emissions test mode

Viessmann · Boiler control board

Holds the boiler at a steady temperature for a short flue gas test.

  1. Activate the emissions test switch on the Optolink/emissions test board.
  2. Burner switches on, and all pumps run.
  3. Mixing valve stays in its control mode.
  4. Boiler water is controlled by the adjustable high limit, which is set to 167 °F / 75 °C by default.
  5. Take flue gas readings during the short test window.

Emissions test mode (flue gas measurement)

Viessmann · Vitotronic 200 KW2 boiler

The emissions test switch on the optolink/emissions board runs the boiler at a constant water temperature for a short time for flue gas measurement. The burner starts, all pumps run, the mixing valve stays in control mode, and boiler water temperature is held by the adjustable high limit.

  1. Set the emissions test switch to its test position.
  2. Confirm the burner is firing and all pumps are running.
  3. Measure flue gas at the test point.
  4. Return the switch to normal operation when finished.

Emissions test mode (flue gas test)

Viessmann · Boiler model 2.5 to 4.0 (switch A and B) and 5.0 and 6.0 (switch A, B and C)

Used to test flue gas with briefly raised boiler water temperature. Only the heating contractor should activate it, during the annual inspection. The emissions test switch position symbols are not legible in this copy, so the exact switch positions are not stated here.

  1. Set the emissions test switch on each boiler section to the test position (A boiler section 1, B boiler section 2, C boiler section 3, depending on model).
  2. Check that the burner runs, the pumps start and the electronic temperature controller regulates boiler water temperature.
  3. Mixing valves stay under control function during the test.
  4. To end emissions test mode, set the emissions test switch back to the normal position.

Emissions test mode (service technician only)

Viessmann · Vitotronic 200 type H01B (printed as HO1B) and Vitotronic 300-K

Raises boiler water temperature briefly to test flue gas. Only the service technician should use it, during the annual inspection. It must be activated on the Vitotronic 200 of the boiler being tested, and on the Vitotronic 300-K cascade control for heat transfer.

  1. Press the keys shown to open test mode.
  2. Select "test mode".
  3. Use the arrow keys to select "ON".
  4. Confirm with OK.
  5. Press the exit key to leave the menu.
  6. To end: open settings, scroll until "S" flashes, confirm with OK so "OFF" flashes, then confirm again with OK.
  7. Test mode also ends automatically after 30 minutes.

Emissions test mode for flue gas testing

Viessmann · Vitotronic 300-K MW2C multi-boiler cascade

Briefly raises boiler water temperature for flue gas testing. Only the service technician should activate it, during the annual inspection.

  1. Set the emissions test switch on the Vitotronic 300-K to the test position.
  2. The pumps start and the mixers stay in control function.
  3. Enable emissions test at the control unit of each boiler. The burner comes on and the boiler circuit pump starts.
  4. To end: set the emissions test switch back, or close the cover flap.
  5. Disable emissions test at the control unit of each boiler.
  6. Follow the applicable boiler operating instructions.

Emissions test switch

Viessmann · Vitocontrol-S, VD2/CT3/CM2

The Vitocontrol-S has an emissions test switch on the front. The full emissions test procedure is described on page 34 of the manual, which is not on these pages.

  1. Locate the emissions test switch on the Vitocontrol-S front panel.
  2. Refer to page 34 of the manual before using it.

Emissions test switch and status LEDs on Main PCB LV

Viessmann · Vitotronic 200 HO1B / 300-K MW2B main PCB LV

The Main PCB LV legend marks S3 as the emissions test switch on the board. Two indicators are also shown: a red fault indicator (V1) and a green ON indicator (V2).

Emissions test switch for temporary operation after a control fault

Viessmann · Single-boiler and multi-boiler systems

Only use after consulting the heating contractor. The boiler then runs temporarily at constant boiler water temperature.

  1. Consult the heating contractor first.
  2. Leave the cover open and turn emissions test switch S to h.

Emissions test switches are behind the front panels

Viessmann · Vitocrossal 300 CA3B all sizes

The emissions test switches D, E and F are only reached by opening the top and bottom front boiler panels and the control covers.

  1. Remove the top and bottom front boiler panels.
  2. Open the control covers to reach the emissions test switches D, E and F.

Enable emissions test mode

Viessmann · Vitodens 200-W B2HA, emissions test

Coding 8F:1 or 8F:2 allows emissions test mode to be enabled. Coding 8F:0 keeps full menu access. The setting takes effect only when the service menu is exited.

  1. Set coding 8F to 1 or 2 in the service menu.
  2. Exit the service menu so the coding is active.
  3. Enable emissions test mode from the service menu.

Enter CO2 test mode (relay test and modulation)

Viessmann · Vitocrossal 200 CM2 burner control

Burner test mode used to hold the burner at a set output for combustion checks.

  1. Open the gas shut-off valve.
  2. Start the burner with the emissions test switch enabled on the boiler control unit.
  3. Press button S and button B together and hold for more than 2 seconds.
  4. Status display shows P (relay test). Service display shows modulation level in %.
  5. Use 100 for 100% (upper heating input) and 0 for 0% (lower heating input).

Enter coding 1 (system design and multi-boiler addresses)

Viessmann · Vitocontrol-S VD2/CT3/CM2 coding 1

Coding 1 holds the system design and multi-boiler addresses. The button symbols in this part of the text are partly garbled, so confirm the keys on the unit before starting.

  1. Press the 9 key and the w key together for about 2 seconds.
  2. Select the coding address with the up or down key. The address flashes.
  3. Confirm with the selection key. The value flashes.
  4. Change the value with the up or down key and confirm. 'Adopted' shows briefly and the address flashes again.
  5. To view more addresses, use the up or down key.
  6. Press the 9 key and the w key together for about 1 second to leave coding.

Enter coding 2 (general, pump, LON and fault settings)

Viessmann · Vitocontrol-S VD2/CT3/CM2 coding 2

Coding 2 covers the remaining addresses. Addresses are scrolled in sequence: system circuit A1 first, then mixing valve circuits M2 and M3.

  1. Press the w key and the rw key together for about 2 seconds, then confirm.
  2. Select the required address with the up or down key. The address flashes.
  3. Confirm. The value flashes.
  4. Change the value with the up or down key and confirm. 'Adopted' shows briefly.
  5. To view more addresses, use the up or down key.
  6. Press the w key and the rw key together for about 1 second to leave coding.

Enter coding level 2 and change coding addresses

Viessmann · Vitocrossal 300 CU3A boilers

Coding level 2 shows all codes, including level 1 codes. Codes not assigned by the system equipment level are hidden.

  1. Press OK and the second button together for about 4 seconds (second button name is not printed on the page).
  2. Press OK and the second button together for about 4 seconds again to reach coding level 2.
  3. Select the group: General, Boiler, DHW, Heating circuit 1/2/3, or All codes or solar.
  4. Select the coding address.
  5. Select the value and confirm with OK.
  6. To reset all codes to factory setting, select Standard setting in Coding level 2. This also resets level 1 codes.

Enter emissions test (relay test) mode

Viessmann · CA3B 2.5 to 6.0

Opens the service display for combustion testing on the GW6C burner control.

  1. Start the burner with the emissions test switch enabled at the control unit.
  2. At the same time, press the two buttons shown as S E and B D and hold for more than 2 seconds.
  3. Status shows P (relay test). Service shows modulation level in %.
  4. 100 means upper heating input and 0 means lower heating input.

Enter emissions test mode

Viessmann · Vitocrossal 200 CM2 186 to 311

Test mode lets you run the burner at high or low fire for combustion checks. The status display shows P (relay test) and the service display shows modulation level in percent: 100 is upper input, 0 is lower input.

  1. Open the gas shut-off valve.
  2. Enable the emissions test switch on the boiler control unit.
  3. Start the burner.
  4. At the same time press the S F and B G buttons and hold for more than 2 seconds.

Enter extended parameters on Vitotron 100 VLN2

Viessmann · Vitotron 100 VLN2

Extended parameters can only be reached with the boiler in standby. Standby is confirmed by the flashing red dot in the bottom right of the blank display.

  1. Press and hold the power button for about 3 seconds until the display goes blank, then release it.
  2. Confirm standby by checking for the flashing red dot in the bottom right corner.
  3. Press and hold the right arrow button.
  4. While still holding the right arrow, press and immediately release the power button.
  5. Release the right arrow when the first parameter group appears.
  6. Use the up and down arrows to change a value. Press the right arrow to move to the next parameter.
  7. When finished, press and hold the power button until the display returns to standby (blank with intermittent red dot).
  8. Press the power button to turn the boiler back on.

Enter flue gas test mode

Viessmann · Vitodens 200-W B2HA 80 to 100, 285 to 352

Test mode is used to bring the burner up to high fire for the fixed high limit tests.

  1. Open the extended menu in the operating manual.
  2. Select 'Test mode', then 'flue gas test ON'.
  3. Press OK. The burner starts a firing cycle and gradually goes to high fire.

Enter service display and manual mode

Viessmann · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

The burner must be running to open the service display and manual mode. The service display shows the current modulation level in %.

  1. With the burner running, hold the B and S buttons together for more than 2 seconds.
  2. The burner switches to manual mode. A 'P' shows under Status and the modulation level flashes under Service.
  3. Press B to lower the heating output until '0' shows under Service.
  4. Press Y to raise the heating output until '100' shows under Service.
  5. Hold B and S together for more than 2 seconds to return the burner to modulating mode.

Enter service functions for filling, venting and max output

Viessmann · Vitodens 200-W B2HB 19 to 125

Service functions are entered from the control panel. Use the menu to pick Filling, Venting or Maximum output. End the function with OK or the back key.

  1. Press OK and the second key together for about 4 seconds.
  2. Select Service functions.
  3. Select Filling, Venting or Maximum output as needed.
  4. Press OK or the back key to end the function.

Enter service level and start test mode

Viessmann · Vitocrossal 200 CI2 programming unit

Service menu access and test mode. The button icons are missing from the text, so the tap sequence is partly unclear. Use the text items and confirm on the control.

  1. Tap the menu button (icon not shown in text).
  2. Tap Service.
  3. Enter password viservice.
  4. Confirm.
  5. Select Test mode.
  6. Confirm to start test mode.
  7. Exit test mode with the stop button (icon not shown in text).

Enter service menu and actuator test

Viessmann · Vitodens 200-W B2HA 80 to 100 and 285 to 352

The service menu actuator test forces the burner to base load (low fire) or full load (high fire) for combustion checks.

  1. Press OK and the key shown on the page at the same time for about 4 seconds to enter the service menu.
  2. Select Actuator test.
  3. Select Base load OFF / ON for low fire, or Full load OFF / ON for high fire.
  4. Select 'all actuators off' to end the test.
  5. Press the exit key to leave the actuator test.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.