Viessmann Boiler: Deleting the hours run meter
Deleting the hours run meter on a Viessmann boiler: Clears the resettable hours run meter from the information menu.
Applies to: Vitocrossal 200 CM2 burner control unit
How to fix deleting the hours run meter: step by step
- Press S for longer than 2 seconds until the menu item flashes.
- Scroll with Y until 2 shows under Service.
- Press S. 1 shows under Status.
- Scroll with Y until 6 shows under Status (hours run meter delete item).
- Press S to confirm. 1 under Service means deleted, 0 means it failed.
- Press S to return to the operating display.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
More reset & cancel tips for boiler
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 44. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.