Reset & cancel: Boiler tips (part 3 of 8)
Short, practical technician tips on reset & cancel for boiler. Check each one against the manual for your exact model before acting.
Changed value not saved if cover closed before Prog
Viessmann · Versatronik COMO OT
If the cover is closed while the warning triangle is still showing, the new value is discarded. The control shows a caution that the change was not saved.
- After changing a value, press Prog before closing the cover to keep it.
- If the caution message appears, reopen the cover and re-enter the value.
Clear a maintenance message on Vitocontrol-S
Viessmann · Vitocontrol-S VD2/CT3/CM2 acting as fault manager (coding 79: 1)
A maintenance message from a connected Vitotronic 100 GC1 is shown on the Vitocontrol-S display. Acknowledge it here, then clear it on the Vitotronic. Button symbols are not legible in the text layer, so the key names are left out.
- Open the maintenance display and scroll through the messages with the arrow keys.
- Select the acknowledge option and confirm that the display shows Acknowledge: Yes.
- Acknowledged messages can be shown again by holding the key for about 3 seconds.
- Acknowledge the maintenance message on the Vitotronic 100 GC1 (see page 107).
- If coding address 24 on the Vitotronic is not reset after maintenance, set it to 0 or the message returns the next Monday morning.
Clear a service reminder
Viessmann · Versatronik 200 service messages
Service reminders can be set by date or by operating hours. Clear them by setting the value back to Off or to 00.
- For a date reminder, set the year value to Off in the General/Service/Customer Service level.
- For an hours reminder, set the operating hours value to Off in the same level.
- To clear the displayed maintenance message, press F, set the repeat value to 00 and confirm with F button OK.
Clear fault memory
Viessmann · CA3B Series 2.5 to 6.0
Deletes all stored faults from the burner control unit.
- Hold the S button for more than 2 seconds until the indicator flashes.
- Turn the dial until 4 shows under Service.
- Press S. A 4 shows under Status.
- Turn the dial until 3 shows under Service.
- Press S. A 1 shows under Status and dEL under Service.
- Press S to confirm. A 1 under Service means deleted, 0 means it failed.
- Press S to return to the operating display.
Clear the burner fault memory
Viessmann · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0
Deletes all stored faults from the fault memory.
- Hold S for more than 2 seconds until the indicator flashes.
- Press Y until '4' shows under Service.
- Press S. '4' shows under Status.
- Press Y until '3' shows under Service.
- Press S. '1' shows under Status and 'dEL' under Service.
- Press S to confirm the deletion. '1' under Service means success, '0' means it failed.
- Press S to return to the operating display.
Clear the service message (P.1 / P.8)
Viessmann · Vitodens 200-W B2HE 85, 120, 150, 199
A service message you acknowledge without resetting comes back the next Monday. Reset it through parameter 1411.0.
- Service menu > System configuration > Boiler
- Set parameter 1411.0 Clear maintenance messages to ON
- Set the next interval in 521.0 (burner hours) or 522.3 (months)
Clearing a service required status (code 0F)
Viessmann · Vitodens 200-W B2HA 112/150/399/530
Code 0F means service is required. After servicing, enter code 24:0 to clear it.
- After servicing the boiler, select coding code 24:0.
Comfort mode end conditions
Viessmann · Vitocrossal 300 CA3B
Comfort mode ends automatically when the system returns to standard heating per the time program, or after 8 hours. Ask the local heating contractor before changing this.
Delete a central heating time phase
Viessmann · Vitotronic 300-K, MW1B and Vitotronic 100, GC1B
Removes a time phase by making its end time equal to its start time.
- Select the time phase to delete in the central heating time program.
- Set the end time to the same time as the start time.
- The display shows "- - : - -" for the removed phase.
Delete a DHW time phase
Viessmann · Vitotronic 200 and 300-K DHW time program
To remove a time phase, set its end time equal to its start time. The display then shows the phase as empty.
- Set the end time of the phase to the same time as the start time.
- Confirm that the display shows the phase as "- - : - -".
Delete a holiday program
Viessmann · Vitotronic 300-K, MW1B
Clears the stored holiday period so the normal time program applies again.
- Open the extended menu.
- Select "Heating".
- Select "Holiday program".
- Select "Delete program".
Delete hours run meter reading
Viessmann · Vitocrossal 300 CA3B Dual Fuel burner control units
Use the information menu item 2 to clear the resettable hours run meter. Status 6 is the deletion item. 1 under Service means it worked, 0 means it failed.
- Press and hold button S for more than 2 seconds until it flashes.
- Press button Y until 2 shows under Service.
- Press button S. 1 shows under Status.
- Press button Y until 6 shows under Status.
- Press button S to confirm the deletion.
- Press button S to return to the operating display.
Delete the message history list
Viessmann · Vitodens 100-W B1HE/B1KE
Clears the saved message list.
- Enter the service menu.
- Select Message history, then OK.
- Select Delete message list, then OK.
- Confirm the prompt with OK.
Deleting a heating time phase
Viessmann · Heating and DHW time programs
Set the end time equal to the start time. The display then shows the phase as empty.
- Select the time phase to remove.
- Set its end time to match its start time.
- Confirm the display shows the phase as empty.
Deleting the hours run meter
Viessmann · Vitocrossal 200 CM2 burner control unit
Clears the resettable hours run meter from the information menu.
- Press S for longer than 2 seconds until the menu item flashes.
- Scroll with Y until 2 shows under Service.
- Press S. 1 shows under Status.
- Scroll with Y until 6 shows under Status (hours run meter delete item).
- Press S to confirm. 1 under Service means deleted, 0 means it failed.
- Press S to return to the operating display.
Economy mode (setback)
Viessmann · Energy saving function
Lowers the room temperature during standard heating mode to save energy. It ends automatically when the time program switches to reduced heating, or when set to OFF.
- Open the extended menu and select Setback mode (Economy mode).
- Select the heating circuit if needed.
- To end early, set Setback mode to OFF.
Economy mode: start and end
Viessmann · Central heating for each heating circuit
Economy mode is an energy saving function that can only be enabled while the system is in standard heating mode. It ends automatically when the time program switches to reduced heating mode.
- Start: Menu, Heating, Heating circuit 1/2/3, Economy mode, select the white frame, tap OK.
- End: Menu, Heating, Heating circuit 1/2/3, Economy mode, the white frame resets, tap OK.
End economy mode
Viessmann · Vitotronic 300-K, MW1B
Economy mode ends automatically at the next reduced heating phase, or it can be turned off manually.
- Open the extended menu.
- Select "Economy mode".
- Set "Economy mode" to "OFF".
End emissions test mode early
Viessmann · Vitotronic 200 on Vitodens 200-W B2HA
Manual shutdown of the emissions test mode from the settings menu. It also ends by itself after 30 minutes.
- Open settings; the settings indicator starts flashing.
- Scroll until the "S" entry flashes.
- Confirm with OK; "OFF" flashes.
- Confirm again with OK to finish.
End party mode
Viessmann · Vitotronic 300-K, MW1B
Party mode ends automatically when the system returns to standard heating mode per the time program, or it can be turned off by hand.
- Open the extended menu.
- Select "Party mode".
- Set "Party mode" to "OFF".
Ending Economy mode
Viessmann · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0
Economy mode can only be enabled in standard heating mode. It ends manually or automatically when the time program switches to reduced heating mode.
- Go to Menu > Heating > required heating circuit > Economy mode > Economy mode.
- Press OK to confirm.
- Economy mode also ends automatically at the reduced heating time in the time program.
Energy saving mode: lower the room temperature briefly
Viessmann · Vitocontrol-S, VD2/CT3/CM2
Energy saving mode lowers the preset room temperature for a short time. It is possible only in the rw heating program.
- Select the heating circuit.
- Press the energy saving key so the button lights and the mode display shows briefly.
- To cancel, press the heating circuit selector and the energy saving key again. Mode ends automatically at the next switch to reduced room temperature.
Erase central heating time phases
Viessmann · Central heating time program
Clears a central heating phase by setting its finishing time to blank.
- Open the hinged cover on the programming unit.
- Press the heating circuit selector button until it lights up.
- Press the time program button; the central heating time program display appears.
- Press until the required 'Central heating phase OFF' shows.
- Press until the finishing time shows '– – : – –'.
- Confirm until the display returns to the boiler temperature.
- Close the hinged cover.
Erase DHW time cycles
Viessmann · DHW time program
Clears a chosen DHW cycle by setting its finish time to blank.
- Open the programming unit cover and press the heating circuit selector until it lights up.
- Press the time program button until the required 'DHW cycle OFF' appears.
- Press until the finish time shows '– – : – –'.
- Confirm until the display returns to the boiler temperature.
- Close the cover.
Erase DHW time phases
Viessmann · DHW time program
Clears a DHW phase by setting its finishing time to blank. Scanning uses the same display procedure without the adjust buttons.
- Open the hinged cover on the programming unit.
- Press the heating circuit selector button until it lights up.
- Press the time program button; the DHW time program display appears.
- Press until the required 'DHW phase OFF' shows.
- Press until the finishing time shows '– – : – –'.
- Confirm until the display returns to the boiler temperature.
- Close the hinged cover.
Erasing time phases
Viessmann · HK1S and HK3S
Clears one or more heating phases so that no switching occurs in that window.
- Open the hinged cover on the programming unit.
- Press the heating time program button until the display shows the required 'Heating phase OFF'.
- Press to step to the finishing time until the display shows '-- : --'.
- Confirm until the basic display returns.
- Close the hinged cover.
Exit a settings level
Viessmann · Versatronik 200 expert settings
Use the F button marked Cancel to leave the current level.
- Press the F button [Cancel] to exit the level.
Exit expert level on Lago FB
Viessmann · Lago FB remote control
Leave expert level when done.
- Use the mode dial to select Entry/Return. The display shows PL.
- Use the value dial to exit expert level.
Exit the service level
Viessmann · Vitotronic 200 and Vitotronic 300-K
Leave service mode through the Terminate service option, or wait for the automatic exit after 30 minutes.
- Select Terminate service? in the menu.
- Select Yes.
- Confirm with OK.
Exit the time program setting mode
Viessmann · Time program setting mode
Leave the setting mode at any time without changing the rest of the program.
- Press the exit button; the display shows 'Exit? Yes'.
- Press confirm; the display returns to the boiler temperature.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.