Viessmann Boiler: Altitude derating
Altitude derating on a Viessmann boiler: Derate the input capacity by 3% per 1000 ft up to 4,999 ft. From 5,000 to 10,000 ft with the electronic altitude adjustment made, derate by an additional 0.6% per 1000 ft, for a total derate of 18%.
Applies to: Vitocrossal 200 CM2 186 to 311
How to fix altitude derating: step by step
- Up to 4,999 ft: derate input 3% per 1000 ft.
- 5,000 to 10,000 ft: make the electronic altitude adjustment, then derate an additional 0.6% per 1000 ft (18% total).
- Input capacity after electronic altitude adjustment is the value to check.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
More commissioning tips for boiler
Source: Vitocrossal 200 CM2 186 to 311 service instructions, p. 60. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.