Commissioning: Boiler tips (part 4 of 21)
Short, practical technician tips on commissioning for boiler. Check each one against the manual for your exact model before acting.
Achievable combustion efficiency
Viessmann · Weishaupt or Riello burners
Efficiency depends on the burner fitted.
- With a high-performance gas burner, combustion efficiency can reach up to 85%.
- With a #2 oil burner, efficiency can reach up to 88%.
Activate the filling function after commissioning
Viessmann · Vitodens 100-W B1HE/B1KE
Filling function ends automatically after 20 minutes or when OK is pressed.
- Press the two buttons shown on the control panel together with OK for about 4 seconds, then release.
- Select Basic settings and press OK.
- Select Commissioning assistant and press OK.
- Use Next until Filling appears, then press OK.
Activate the purging function after commissioning
Viessmann · Vitodens 100-W B1HE/B1KE
Purging function ends automatically after 20 minutes or when OK is pressed. An automatic air vent valve must be installed on site.
- Press the two buttons shown on the control panel together with OK for about 4 seconds, then release.
- Select Basic settings and press OK.
- Select Commissioning assistant and press OK.
- Use Next until Purging appears, then press OK.
Add external disconnect and fuel shut-off
Viessmann · Vitorond 200 VD2
Viessmann recommends extra isolation outside the mechanical room or enclosed installation area.
- Install an additional electrical disconnect switch outside the mechanical room if possible.
- Install a fuel shut-off valve outside the mechanical room if possible.
Adjust the adjustable high limit to 100 °C / 212 °F
Viessmann · Vitotronic 100 GC1 adjustable high limit
Factory setting is 95 °C / 203 °F. Note the coding address 06 setting after adjusting.
- Disconnect power to the control and burner.
- Using a suitable screwdriver, lever out and remove the selector knob R behind the hinged cover.
- Using pointed pliers, break off the cams marked in the figure from the stop dial.
- Fit the selector knob R so the marking is in the centre of the selected range (75 to 100 °C / 167 to 212 °F).
- Check and note the coding address 06 setting.
Adjust the differential pressure bypass valve
Viessmann · Vitotron 100 VLN2 hydronic piping
The bypass valve keeps a minimum flow through the boiler when zone valves close and reduces noise. It is set by finding the tipping point and then backing off one turn.
- Turn the bypass valve clockwise until it stops.
- Turn on all heating zones and let them run a couple of minutes.
- Slowly turn the valve counterclockwise until a temperature rise is felt on the outlet side. This is the tipping point.
- Turn the valve one further full turn.
- Set the thermostats to their normal temperatures.
- Piping can get hot quickly when the valve opens, so open it slowly.
Adjust the fixed high limit to 99 °C / 210 °F
Viessmann · Vitorond 200 VD2/VD2A, Vitocrossal 300 CT3, Vitocrossal 200 CM2 with Vitotronic 100 GC1
Used when the safety equipment and applicable codes call for it. Adjustment is permanent.
- Disconnect power to the control and burner.
- Unclip the fuse box and swing it upwards.
- Turn the slotted screw on the rear of the fixed high limit until the slot points to 99 °C / 210 °F.
- Refit the fuse box.
- If set to 99 °C / 210 °F, keep the adjustable high limit at 75 °C / 167 °F or below.
Adjusting the barometric draft regulator
Viessmann · Vitorond 100 VR1 22 to 33, 91 to 140 with barometric draft regulator
Set the barometric draft regulator so the draft readings are correct, and confirm it moves freely.
- Adjust the barometric draft regulator so the over-fire draft is 0.00 to +0.01 in w.c.
- With this setting, the breeching draft should be approximately -0.02 in w.c.
- Confirm the barometric draft regulator moves freely while the burner runs.
Air removal from the system
Viessmann · Vitodens 200-W B2HA 80-100, 285-352
Remove air through air vents in the system supply. Avoid restrictive piping where air could get trapped so the boiler can be fully purged.
- Install air vents in the system supply.
- Check that supply and return lines have no restrictive piping that can trap air.
Allocate heating circuits to a remote control
Viessmann · Vitotrol 200A and Vitotrol 300A
Heating circuit allocation must be set when commissioning a Vitotrol 200A or Vitotrol 300A. The Vitotrol 200A serves one heating circuit; the Vitotrol 300A serves up to three.
- Allocate the heating circuit to the remote control during commissioning.
- If the allocation is cancelled later, reset coding address A0 for that heating circuit to 0.
Allocate heating circuits to Vitotrol 200A / 300A remote control
Viessmann · Vitotrol 200A / 300A
The heating circuit allocation must be set during commissioning. The Vitotrol 200A serves one heating circuit; the Vitotrol 300A serves up to three. Up to two remote controls can be connected. The manual's column layout for the allocation table is unclear in this extraction, so confirm the mapping on the boiler.
- During commissioning, allocate the heating circuit to the Vitotrol 200A (one circuit) or Vitotrol 300A (up to three circuits).
- If the allocation is later cancelled, reset coding address A0 for that heating circuit to 0.
Allocating heating circuits to a Vitotrol remote control
Viessmann · Vitotrol 200A and 300A remote controls
Heating circuit allocation must be set when commissioning a Vitotrol 200A or 300A. One heating circuit can go to the 200A, up to three to the 300A, and up to two remote controls can be connected. The extract does not clearly map each Vitotrol column to its circuit, so check the full table in the manual.
- Configure heating circuit allocation at commissioning.
- If an allocation is later cancelled, set coding address A0 for that heating circuit back to 0.
Alternative DHW connection with low-loss header
Viessmann · System layouts 2, 5, 6 and 8
The alternative DHW piping applies to system layouts 2, 5, 6 and 8. The boiler control pump logic must be programmed in the Service Instructions. With a low-loss header, the DHW connections can be made downstream of the header.
- Program the boiler control pump logic in the Service Instructions.
- Set the applicable system coding at coding level 2 in the Service Instructions.
Alternative DHW tank connection
Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199 (system layouts 2, 5, 6, 8)
Alternative piping for the DHW tank only, used with system layouts 2, 5, 6 and 8. The boiler control pump logic must be programmed in the Service Instructions. With a low-loss header, the DHW connections can be made downstream of the header.
- Program the boiler control pump logic in the Service Instructions.
- If a low-loss header is used, the DHW connections can be made downstream of it.
- Set the system coding at coding level 2 as described in the Service Instructions.
- Refer to the Service Instructions for the coding values that apply to this layout.
Altitude derating
Viessmann · Vitocrossal 200 CM2 186 to 311
Derate the input capacity by 3% per 1000 ft up to 4,999 ft. From 5,000 to 10,000 ft with the electronic altitude adjustment made, derate by an additional 0.6% per 1000 ft, for a total derate of 18%.
- Up to 4,999 ft: derate input 3% per 1000 ft.
- 5,000 to 10,000 ft: make the electronic altitude adjustment, then derate an additional 0.6% per 1000 ft (18% total).
- Input capacity after electronic altitude adjustment is the value to check.
Ambient and mechanical room limits
Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199
Keep the boiler room within the listed temperature range and free of contaminants. Marine locations need room-air vent systems.
- Keep ambient temperature above 32°F (0°C) and no higher than 104°F (40°C).
- Do not install where combustion air contains halogenated hydrocarbons, paint solvents, cleaning fluids or heavy dust.
- Avoid constant high humidity (for example frequent laundry drying) and never close existing ventilation openings.
- In damp, salty coastal areas, do not use direct vent (outdoor air) systems; use room-air-dependent venting.
Antifreeze in heating system
Viessmann · Systems filled with glycol mix
Use only glycol made for hot water heating. Antifreeze may need a backflow preventer and can affect other components.
- Use no automotive silicate-based antifreeze.
- Check the system frequently after filling with antifreeze.
- Tell the owner the system is filled with glycol.
- Give the owner a material safety data sheet (MSDS) for the antifreeze used.
Antifreeze in the heating system
Viessmann · Hydronic heating system
Antifreeze may be used where freezing can occur. Use only antifreeze made for hot water heating systems.
- Use a 40% antifreeze content for freeze-up protection to -10°F (-23°C).
- Do not use automotive silicate-based antifreeze.
- Check the total system often when it is filled with antifreeze.
- Leave a copy of the Material Safety Data Sheet on site.
- Check whether a backflow preventer is needed in the automatic water feed.
Application 3: DHW timer and HC1 settings
Viessmann · Application 3 operational setup
Set the DHW timer to match when domestic hot water can be made. The HC1 settings remain available if an outdoor-reset zone is also connected.
- If DHW can be produced at any time, set the timer to 0:00 to 24:00.
- If an outdoor-reset zone is connected, use the HC1 settings.
- If mixing valve extension kits are used, adjust the outdoor reset settings as required.
Application 5 DHW timer setting
Viessmann · Vitodens 222-F, B2TB, Application 5
If domestic hot water should be available at any time, the DHW timer must be opened up for the full day.
- Set the timer schedule as the customer needs.
- For DHW available at any time, program the timer to 0:00 to 24:00.
Application 5 start-up wizard (zone circuit with fixed setpoint)
Viessmann · Vitodens 222-F, B2TB, Application 5
Start-up wizard for Application 5: one high temperature zone (ZC1) plus a low temperature heating circuit with a 3-way mixing valve (HC2). Simultaneous space heating and DHW is allowed, so size the boiler for both loads.
- Select the number of zone circuits to match the thermostats wired to the DE connections, then press OK.
- Confirm the fixed setpoint mode for zone calls, then press OK.
- Enter the target water temperature the boiler should hold on a call for heat, then press OK.
- Arrow to the 157 output to assign the zone pump, then press OK.
- Check the zone circuit output summary against the number of zones chosen, then press OK.
- Press OK to finish start-up. The boiler is then ready for operation.
Application 5: HC1 outdoor reset and mixing valve extension kits
Viessmann · Application 5 with outdoor reset or mixing valve extension kits
HC1 settings remain available if an outdoor reset zone is connected. If mixing valve extension kits are used, set the outdoor reset parameters to suit.
- If an outdoor reset zone is wired, check the HC1 settings.
- If mixing valve extension kits are fitted, review and adjust the outdoor reset settings.
Application 6 DHW timer setting
Viessmann · Vitodens 222-F, B2TB, Application 6
Same DHW timer rule as Application 5: for DHW at any time, the timer must run the full day.
- Set the timer schedule as the customer needs.
- For DHW available at any time, program the timer to 0:00 to 24:00.
Application 6 piping: no external check valves or primary/secondary loop
Viessmann · Application 6, code CU3I 3HC/ZC3ZP.02
External flow check valves are not needed when the circulators have them built in. Primary/secondary piping is not required because the CU3A is a high mass boiler. Application code CU3I 3HC/ZC3ZP.02 applies.
- Confirm the circulators have built-in flow check valves before leaving out external check valves.
- Do not add primary/secondary piping for the CU3A high mass boiler.
Application 6 start-up wizard (1 zone circuit, fixed setpoint, 157 pump output)
Viessmann · Vitodens 222-F, B2TB, Application 6
Start-up wizard for Application 6 with two mixing heat circuits (HC2, HC3) plus one unmixed high temperature circuit (ZC1). The ZC1 call runs the P3 pump through the 28/20 plug. ZC1 can run on fixed setpoint or weather compensation. HC2 and HC3 follow the boiler heating curves.
- Select 1 zone circuit to match the ZC thermostat wired to the DE connections, then press OK.
- Confirm the fixed setpoint mode for zone calls, then press OK.
- Enter the target water temperature the boiler should hold on a call for heat, then press OK.
- Arrow to the 157 output to assign the pump, then press OK.
- Check the zone circuit output summary against the zones selected, then press OK.
- Press OK to finish start-up. The boiler is then ready for operation.
Application 6: the mixing valves follow the boiler heating curves
Viessmann · Application 6 with two mixing valves and a high temperature zone
In this layout the HC2 and HC3 mixing valves run on heating curve settings stored in the boiler. The ZC1 circuit can be set to a fixed setpoint or to weather compensation. The ZC1 call switches the 28/20 output to pump P3.
- Set the heating curves for HC2 and HC3 in the boiler control.
- Choose fixed setpoint or weather compensated operation for ZC1 as the system requires.
Application 7: boiler target when several zones call for different temperatures
Viessmann · Application 7, code CU3I 3ZC9C.01
When several zones request different temperatures at the same time, the boiler targets the highest requested temperature.
- Expect the boiler to run to the highest zone setpoint when more than one zone is calling.
Application 7: jumper between the 40A plug and the 157 plug
Viessmann · Application 7, code CU3I 3ZC9C.01
A jumper must be installed between the 40A plug and the 157 plug in this application.
- Install the jumper between the 40A plug and the 157 plug before starting up Application 7.
Application 7: zone control wizard, ZC1 weather compensated with ZC2 and ZC3 fixed setpoint
Viessmann · Application 7, ZC1 weather compensated with ZC2 fixed setpoint
Three heating circuits: ZC1 gets a call from a Multizone Control and runs weather compensated, ZC2 gets a call from a second Multizone Control (two zone valves, fixed setpoint), ZC3 comes from a snow melt control and runs fixed setpoint with a pump on the 157 output. ZC1 has no pump in this layout.
- Select the number of zone circuit connections to match the controls wired to the DE connections, then press OK.
- For ZC1, arrow down to the weather compensated function and press OK.
- Adjust slope and shift to set the heating curve. The screen shows the curve moving as you change them.
- Press OK to continue. These settings can be changed later.
- For ZC2, select fixed setpoint, press OK, and set the zone target temperature.
- For ZC3, select fixed setpoint, set the zone target temperature, and select the 157 pump output.
Assembling PP(s) and stainless vent pipe
Viessmann · Vitocrossal 300 CA3B Dual Fuel venting
Keep the vent route short and direct with as few bends as possible. Pipe must slope back to the boiler so condensate drains from the flue to the boiler. Use only the vent maker's parts with PP(s) systems.
- Check that the gaskets are seated in the rigid pipe collars.
- Lubricate the pipe ends and collars with water, then slide the pieces together with a gentle twist.
- Slope the vent at least 2 to 3 degrees toward the boiler. For a 3 degree slope, use about 2 in. per 3.3 ft (50 mm per 1 m).
- Cut pipe square with a hacksaw or snips, file the edges smooth, and keep the pipe round.
- Deburr and clean the pipe after cutting.
- Follow the vent manufacturer's installation instructions alongside this manual.
- Keep elbows to a minimum, avoid back-to-back 90 degree elbows, and use 45 degree elbows where possible.
- Do not route the vent through or inside another vent or chimney, except a masonry flue used only by this boiler.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.