Rinnai Boiler: Gas supply pressure testing

Updated · by Aurora Star Tech Inc.

Gas supply pressure testing on a Rinnai boiler: Protect the boiler and its gas valve during gas line pressure tests.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Gas supply piping

How to fix gas supply pressure testing: step by step

  1. If the test pressure is above 1/2 PSI (3.5 kPa / 13.84 in. W.C.), disconnect the boiler and its main gas valve from the supply piping first.
  2. If the test pressure is at or below 1/2 PSI, close the boiler's individual manual shutoff valve to isolate it.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Rinnai Boiler codes

More other tips for boiler

Source: Rinnai I-Series Plus IP060160C installation manual, p. 14. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.