Other: Boiler tips (part 5 of 45)
Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.
Do not run without front panel and watch burn hazard
Rinnai · All I-Series Plus models
Do not operate the boiler without the front panel installed. Exhaust, vent and supply/return/DHW pipes can be hot enough to cause serious burns. Keep children and animals away.
- Reinstall the front panel before operation. Remove it only for service or internal component replacement.
- Keep people and pets clear of the boiler and hot vent.
Domestic hot water expansion control
Rinnai · DHW piping
If the DHW system connects to a closed supply such as one with a backflow preventer, thermal expansion must be controlled.
- Ask the water supplier or local plumbing inspector how to control thermal expansion.
- Confirm the DHW relief valve is rated for 150 PSI (1,034 kPa).
Gas conversion safety precautions
Rinnai · I-Series Plus condensing combi boiler
Some PC board areas carry 120 V AC. Do not touch any area of the PC board other than the described buttons while power is on. Keep clear of the heat exchanger and hot water lines, which can cause burns. Conversion must be checked in operation before the job is complete.
- Shut off gas and disconnect power before opening the PC board for conversion.
- Check the converted appliance operates correctly as the kit instructions specify before handing over.
Gas pipe sizing worked example
Rinnai · Natural gas sizing worksheet
The manual example adds the boiler input (65,000 Btu/hr) to the additional appliance input (199,000 Btu/hr) for a total of 264,000 Btu/hr. Divide by the gas heating value (1,000 Btu/ft3) to get 264 CFH. At 264 CFH the pipe must be at least 3/4 in nominal size for 10 ft run.
- Add all gas input in Btu/hr: boiler plus other appliances.
- Divide total input by the gas heating value (Btu/ft3) to get CFH.
- Pick the table for your gas type and pipe type, then find the size that meets the CFH at your run length.
Gas supply pressure testing
Rinnai · Gas supply piping
Protect the boiler and its gas valve during gas line pressure tests.
- If the test pressure is above 1/2 PSI (3.5 kPa / 13.84 in. W.C.), disconnect the boiler and its main gas valve from the supply piping first.
- If the test pressure is at or below 1/2 PSI, close the boiler's individual manual shutoff valve to isolate it.
Hard water and DHW scale
Rinnai · Domestic hot water
Hard water or high setpoints increase scale and may need treatment and more frequent flushing.
- Treat the water where hard water or scale is known to occur.
- Consider a Scale Cutter filter and refill cartridge to reduce scale.
Installer qualifications and warranty
Rinnai · I-Series Plus condensing combi boiler
Only a trained and qualified installer should install, inspect and leak test the boiler. Improper installation voids the warranty.
- Before use, have the installer inspect the boiler and leak test it.
Isolate power, gas and water before maintenance
Rinnai · All I-Series Plus models
Before any maintenance, shut off electrical power, the gas supply and the incoming water. The boiler controller does not control electrical power.
- Unplug the power cord or turn off the electricity at the circuit breaker.
- Turn off the gas at the gas control, usually directly below the boiler.
- Turn off domestic cold water at the isolation valve below the boiler.
- Turn off central heating water at the system filling station shut-off valve or building main supply.
- Turn the manual gas control valve by hand only. Never use tools. If it will not turn by hand, call a trained professional and do not force it.
Keep corrosive compounds away from combustion air
Rinnai · Air supply and vent termination
Chemicals in the air can corrode internal parts and shorten boiler life.
- Keep aerosols, detergents, bleach, solvents, oil-based paints and refrigerants away from the air supply.
- In salons, spas, dry cleaners, photo labs and pool storage, prefer an outdoor or sealed direct-vent installation.
- Place the boiler and vent termination away from air inlets, exhaust hoods and dryer vents.
- In coastal areas, shelter the boiler from salt spray and sea breeze.
- Do not use room air where indoor air is corrosive. Use direct vent in a sealed closet instead.
MC-601 priority during technician work
Rinnai · MC-601 remote temperature controller
The MC-601 should not be used while a technician is servicing the unit. Pressing its Priority button switches priority back to the boiler's built-in controller.
- Do not use the MC-601 during maintenance.
- To return priority to the boiler controller, press the Priority button on the MC-601.
- To give priority back to the MC-601, press the Priority button again.
Overheating or gas shutoff failure
Rinnai · All I-Series Plus models
If overheating occurs or the gas supply does not shut off, close the manual gas control valve to the appliance.
- Close the manual gas control valve to the boiler.
- Call a trained and qualified professional.
Scald risk at domestic hot water temperatures
Rinnai · DHW temperature settings
Hot water can cause first-degree burns in as little as 3 seconds at 140 F (60 C), 20 seconds at 130 F (54 C), or 8 minutes at 120 F (49 C). Water over 125 F (52 C) can cause severe burns or death. Children, disabled and elderly people are most at risk.
- Check the DHW setting and warn occupants about scald risk.
- Have users feel the water before bathing or showering.
Substitute parts and electrical extension cords
Rinnai · All I-Series Plus models
Use only parts certified for the appliance. Do not use an extension cord or adapter plug with the boiler.
- Use only certified replacement parts.
- Plug the boiler directly into a suitable outlet without an extension cord or adapter.
Wall strength
Rinnai · Wall mounting
The wall must carry the boiler, piping and components.
- If the wall is not strong enough, reinforce it before mounting.
Water fill and flushing rules
Rinnai · Central heating system
Keep the heating system water clean and suitable for the boiler.
- Flush the system thoroughly before filling, with the boiler isolated.
- Do not add system cleaner to the boiler. Flush all cleaner out before filling.
- Do not fill the heating system with reverse osmosis, deionized or distilled water.
- Do not use oxygen-permeable or rubber tubing in the heating system unless a plate heat exchanger separates it from the boiler.
- Use only Rinnai-approved antifreeze, at no more than 40% concentration.
- Use only products on the approved cleaners, inhibitors and antifreezes list in the appendix.
30% LTP package strap-on sensor
Viessmann · VD2/VD2A with 30% LTP package
The 30% LTP package uses a strap-on sensor (1-17B) on the VD2/VD2A control.
aBJ programmable output function
Viessmann · Vitocrossal 300 CU3A 26 to 199, extension module EA1
The aBJ output is a programmable function output. It can be coded for only one function: alarm output, DHW recirculation pump, field pump or zone circuit pump. Maximum output is 2 FLA.
- Select one function for the aBJ output using the coding in the Service Instructions.
- Keep the load within 2 FLA.
- See the wiring diagram on page 57 for connection to the control base.
Access the control unit and connection area
Viessmann · Vitodens 200-W B2HB control unit
Opening the control unit requires removing the junction box cover and the external accessory connection box, then folding down the control unit.
- Remove both screws from the junction box cover and set them aside.
- Loosen both retaining screws (do not remove), pull the accessory connection box forward until the screws clear the guides, and swing it down.
- Tilt the bottom of the cover forward, lift it past the locating pins and remove it.
- Close the programming unit cover, release the hinged hooks on both sides of the control unit, and fold it down.
- Release the locking tabs and remove the control unit cover.
- Touch a grounded object (such as a heating or water pipe) before working to discharge static from electronic modules.
Accessing the control unit and wiring
Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199
Access the control unit through the external accessory connection box. Power requires a 120 VAC / 12 A supply.
- Remove both screws from the junction box cover and set them aside.
- Loosen both retaining screws (do not remove them).
- Pull the external accessory connection box forward until the screws clear the rail guides.
- Swing the connection box down.
- Tilt the bottom of the cover forward, lift it off the locating pins and set it aside.
- Close both sides of the programming unit cover.
- Release the hinged hooks on both sides of the control unit.
- Lift the control unit cover and fold the control unit down.
- Release the locking tabs and remove the cover.
- Route all connecting cables to their areas and secure them to the control base at the existing strain reliefs.
Accessory kit and closing the control cover
Viessmann · Vitodens 222-F, B2TB 19, 35, 68, 125
The mixing valve controller kit can be used as an alternative to a Vitotronic control, but the manual states it works only with wall-mounted boilers and a weather-responsive control, which conflicts with this floor-mounted model. Coding and connection details are in the Service Instructions.
- Install the control cover onto the control board.
- Flip the control console back into position.
- Secure the locking tabs as shown.
- Refer to the Service Instructions for coding and control connection.
- Refer to the accessory kit Installation Instructions for kit installation.
Accessory power supply and disconnect requirements
Viessmann · Vitodens 222-F, B2TB (19, 35, 68, 125)
Accessory power outputs at the control are switched by the system on/off switch. The Vitotronic 200-H, HK1B mixing valve control, the mixing valve accessory kit and the Solartrol control need their own 120 VAC supply from a wall receptacle. Install a disconnect switch that isolates all live conductors from the mains, and a GFCI receptacle is also recommended.
- Connect accessories that need 120 VAC from their own wall receptacle.
- Install a disconnect that isolates all live conductors.
- Use a GFCI receptacle as an additional measure.
- Only one accessory or switch contact per plug connection at a time.
Accessory power supply at the control
Viessmann · Vitocrossal 300 CU3A boiler accessories
Accessory power can be taken from the control. It switches on and off with the system on/off switch. The Vitotronic 200-H, the HK1B mixing valve control, the mixing valve accessory kit and the Solartrol control each need their own 120 VAC supply from a wall receptacle.
- Connect accessory power at the control so it follows the system on/off switch.
- Run a separate 120 VAC wall supply to the Vitotronic 200-H, HK1B, mixing valve kit and Solartrol control.
Acknowledge all pending messages
Viessmann · Vitodens 100-W B1HE/B1KE
Clears the acknowledge state of all pending messages.
- Call up the home screen.
- Open the menu and select Active messages, then tap OK.
- Select Acknowledge, then tap OK.
- Tap OK to acknowledge the information.
Acknowledge and review active faults
Viessmann · Active fault messages
A fault flashes the red fault indicator A and shows 2 and Fault on the display. Acknowledging moves the message to the standard menu and switches off any connected fault output. An unresolved fault comes back the next day and restarts the fault output.
- Follow the instructions on the display to acknowledge the fault.
- To review active faults later, select Fault in the standard menu.
Adjust display contrast
Viessmann · Vitotronic 200 KW2
Changes the display contrast.
- Press the two buttons together to darken the display.
- Press the two buttons together for the other direction to brighten the display.
Adjusting room temperature with an external thermostat
Viessmann · Vitodens 100-W WB1B
With an external room thermostat, set the room temperature on that device. If the room cannot reach the target in cold weather, raise the boiler water temperature with the tr dial. Thermostatic radiator valves in the control room must be fully open.
- Set the desired room temperature on the external room thermostat.
- Open any thermostatic radiator valves in the room where the control is installed.
- If the room stays too cool, increase the boiler water temperature with the tr dial.
Adjusting the adjustable high limit to 100 °C / 212 °F
Viessmann · Vitotronic 100 GC1 adjustable high limit
Changes the adjustable high limit from the factory 95 °C / 203 °F. Limit the DHW temperature when the system feeds a DHW tank.
- Disconnect power to the control and burner.
- Using a suitable screwdriver, lever out and remove selector knob R behind the hinged cover.
- With pointed pliers, break off the cams shaded in the figure from the stop dial.
- Refit selector knob R so the marking sits in the centre of the selected range.
- Note the coding address 06 setting.
Adjusting the fixed high limit to 99 °C / 210 °F (VD2 only)
Viessmann · Vitorond 200 VD2
Applies to Vitorond 200 VD2 where the factory fixed high limit is 110 °C / 230 °F. Not required for CT3 or CM2.
- Disconnect power to the control and burner.
- Unclip the fuse box and swing it upwards.
- Turn the slotted screw on the rear of the fixed high limit until the slot points to 99 °C / 210 °F.
- Refit the fuse box.
Air pressure switch LDW1 (fan) function
Viessmann · LDW1 air pressure switch (fan)
LDW1 is checked during all fan start-up phases and tested during modulation. It causes a fault shutdown if the cold-state checkup fails after about 5 minutes, if pre-aeration pressure is out of range for about 5 minutes, or if the switch fails or pressure is out of range in normal operation. Shown as F F5 or F F7, released with reset button R.
- Check the fan and the LDW1 switch and hose if F F5 or F F7 appears.
- Press reset button R to release the shutdown once the cause is cleared.
Air pressure switch LDW2 (combustion chamber) function
Viessmann · LDW2 air pressure switch (combustion chamber, non-adjustable)
LDW2 is checked in every operating phase except safety and stabilization times. It shuts the burner down if chamber pressure is out of range after two attempts during pre-aeration, normal operation or post-purge. The fault is shown as F Fb and is released with the reset button R.
- Check chamber pressure if F Fb appears.
- Press reset button R to release the shutdown once the cause is cleared.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.