Navien Air Conditioner: Temperature sensor replacement (T3, T4, T5/TP, T7)
Temperature sensor replacement (T3, T4, T5/TP, T7) on a Navien air conditioner: The sensors are removed from the thermistor holder after the covers come off. If the display reading is wrong but the resistance matches the temperature, the PCB is the likely fault.
Applies to: NAA17V36-24K/36K, NAA17V60-48K/60K
How to fix temperature sensor replacement (t3, t4, t5/tp, t7): step by step
- Turn off the respective circuit breaker.
- Remove the 10 screws from the top cover and the 18 screws from the bottom cover, then remove the upper covers and side panels.
- Pull the clip that holds the thermistor.
- Remove the thermistor from the thermistor holder.
- Disconnect the thermistor connector from the PCB and remove the thermistor.
- If resistance matches temperature but the display is wrong, replace the PCB.
If the unit shows an error code, look it up: Navien Air Conditioner codes
More other tips for air conditioner
Source: Navien NAA air conditioner service manual, p. 48. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.