Navien Air Conditioner: Refrigerant recovery, evacuation and purging
Refrigerant recovery, evacuation and purging on a Navien air conditioner: Follow this order when opening the refrigerant circuit. Recovered refrigerant goes into labeled recovery cylinders and is never mixed.
Applies to: NAA17V36-24K/36K and NAA17V60-48K/60K
How to fix refrigerant recovery, evacuation and purging: step by step
- Recover the refrigerant following local and national rules.
- Evacuate the system.
- Purge tubing and braze joints with inert gas while brazing.
- Keep purging with inert gas when a flame is used to open the system.
- Purge with oxygen-free nitrogen, never compressed air or oxygen, and repeat until no refrigerant remains.
- Vent to atmospheric pressure before working on the system.
- Keep the vacuum pump outlet away from ignition sources and in a well-ventilated area.
- Do not overfill recovery cylinders above 80% of their capacity, and do not exceed cylinder pressure rating.
- Weigh recovered refrigerant on calibrated scales.
If the unit shows an error code, look it up: Navien Air Conditioner codes
More other tips for air conditioner
Source: Navien NAA air conditioner service manual, p. 9. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.