Navien Air Conditioner: Leak detection for A2L refrigerant
Leak detection for A2L refrigerant on a Navien air conditioner: Open flames and halide torches must never be used to find leaks. Use only detectors rated for A2L refrigerant.
Applies to: NAA17V36-24K/36K, NAA17V60-48K/60K
How to fix leak detection for a2l refrigerant: step by step
- Use an electronic leak detector designed for A2L refrigerants and confirm it is non-sparking and calibrated in a refrigerant-free area.
- Remove or extinguish all flames if a leak is suspected.
- If brazing is needed at a leak, recover the refrigerant or isolate that section with shut-off valves first.
- Use leak detection fluid only if it does not contain chlorine; use the bubble or fluorescent method.
If the unit shows an error code, look it up: Navien Air Conditioner codes
More other tips for air conditioner
Source: Navien Air Conditioner NAA Series Service Manual, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.