Carrier Heat Pump: Power and communication wiring between outdoor and indoor unit
Power and communication wiring between outdoor and indoor unit on a Carrier heat pump: Wire size and wire type depend on unit size. Use the correct method for the size being installed.
Applies to: 18K to 58K
How to fix power and communication wiring between outdoor and indoor unit: step by step
- For 09K through 24K: run a 14/3 power and communication cable with four wires (two AC power, one communication, one ground) from outdoor to indoor unit.
- If there is high EMF interference and communication faults, a 14/2 stranded shielded cable can replace L2 and S; land the shield to ground at the outdoor unit only.
- For 36K through 58K: run a 14/2 stranded power cable with ground (three wires) from outdoor to indoor unit to limit voltage drop.
- For 36K through 58K: use a separate shielded stranded copper communication cable rated 600 V, double insulated; the manual calls for a shielded 16 GA stranded control wire.
- Provide a disconnect within sight of and readily accessible from the air conditioner.
- Tighten every terminal connection; loose wiring can overheat the terminal.
- Keep all wires clear of refrigerant tubing, the compressor and moving parts.
- Route the conduit cable through the hole in the conduit panel and follow local codes for the indoor-to-outdoor run.
If the unit shows an error code, look it up: Carrier Heat Pump codes
Models
More commissioning tips for heat pump
Source: D5FCFAH service manual, p. 9. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.