Carrier Air Handler: Use shielded cable in EMF areas
Use shielded cable in EMF areas on a Carrier air handler: If installed in a high EMF area and communication problems occur, a 14/2 stranded shielded cable can replace the L(2) and S wires between the indoor and outdoor units.
Applies to: Installations with communication interference
How to fix use shielded cable in emf areas: step by step
- Use 14/2 stranded shielded cable to replace L(2) and S.
- Land the shield on ground at the outdoor unit only.
If the unit shows an error code, look it up: Carrier Air Handler codes
More commissioning tips for air handler
Source: D5FSAA Product Data, p. 11. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.