Commissioning: Air Handler tips (part 3 of 3)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on commissioning for air handler. Check each one against the manual for your exact model before acting.

Remove JR1 short connector for ON/OFF function

Carrier · Indoor main board

The JR1 short connector must be removed before the ON/OFF function can be used.

  1. Remove the short connector on JR1 when using the ON/OFF function.

Remove packing and accessories from air outlet

Carrier · All D5FUAA sizes

Remove all accessories and packing material from the air outlet before installing.

  1. Remove all packing and accessories from the air outlet before mounting.

Room size and duct outlet height for R454B

Carrier · Units with R454B refrigerant

R454B is a mildly flammable (A2L) refrigerant. The room area served and the total refrigerant charge are limited. The bottom of the duct air outlet in the room must be at the height stated on the page, 7.3 ft (2.2 m) above the floor. Table 2 (minimum room area) is not legible on these pages.

  1. Check the room area served against Table 2 and the charge limit.
  2. Set the duct outlet height to at least 7.3 ft (2.2 m) above the floor.
  3. Keep the room free of continuously operating open flames or other ignition sources if the room is below the minimum area.

Room size and outlet height for flammable refrigerant systems

Carrier · R454B systems, 18K to 60K

The air duct outlet serving the room must sit more than 7.3 ft (2.2 m) above the floor. R454B is classed as mildly flammable, so the room area served and the total refrigerant charge are limited by the room size. Compare the actual charge against the allowable charge for the room.

  1. Confirm the air outlet height is above 7.3 ft (2.2 m) from the floor.
  2. Check the total refrigerant charge is at or below the maximum allowed for the room area served.

Room ventilation and installation area

Carrier · D5FULA crossover evaporator coil with flammable refrigerant

Install in a well ventilated room that matches the room area stated for operation. Where mechanical ventilation is needed, keep the vents clear. In rooms smaller than the minimum area for the refrigerant charge, no open flames or hot surfaces may run.

  1. Keep ventilation openings free of obstruction.
  2. Check the room area against the minimum area table for the refrigerant charge.

Scenario 1: 24 V thermostat with RS485 to outdoor unit

Carrier · D5FUAA with 24 V thermostat (scenario 1)

Scenario 1 lets a 24 V thermostat work with RS485 communication between indoor and outdoor units. Figure 11 in the manual shows the wiring.

  1. Do not use the B and W terminals together.
  2. Use W only for a conventional thermostat heat demand.
  3. Treat DS as a reserve terminal.
  4. Do not use any outdoor 24 V terminals in scenario 1.

Scenario 2 (default): wired controller wiring

Carrier · D5FUAA with wired controller (scenario 2)

Scenario 2 is the default and lets the KSACN1401 or KSACN1701 wired controller work with RS485 between indoor and outdoor units.

  1. Do not use any 24 V terminals on the indoor or outdoor unit.
  2. Connect the Ha and Hb terminals on the wired controller to the Ha and Hb terminals on the indoor built-in 24 V interface (CN7) using 16 AWG shielded stranded wire.
  3. Follow the indoor and outdoor communication diagram (Figure 12).

Single zone performance check

Carrier · D5FSAA / D5FLAA single zone ductless system

Run the system and record operating temperatures for the start-up record.

  1. On a 1:1 single zone system, adjust the setpoint to create a cooling or heating call for the test.
  2. Let the system run for at least 10 minutes.
  3. Use the wireless remote Point Check function to read the sensors.
  4. Record the set-point, mode, T1 ambient space, T2 indoor coil, T3 outdoor coil, T4 outdoor ambient, Tb suction line at PMV, Tp discharge, Th IPM board and LA/Lr PMV temperature.

Start-up error code check

Carrier · D5FSAA / D5FLAA single zone ductless system

Check for any error codes during start-up and record them.

  1. Check whether any error codes were present at start-up.
  2. Record the indoor unit error code and the outdoor unit error code.
  3. Note the wall controller and 24V interface status in the comments.

Static pressure limit

Carrier · All sizes

Do not exceed 0.80 in.wc. (200 Pa) total external static pressure. Airflow falls sharply above this point.

  1. Measure total external static pressure during commissioning.
  2. Confirm it is 0.80 in.wc. (200 Pa) or less.

Use shielded cable in EMF areas

Carrier · Installations with communication interference

If installed in a high EMF area and communication problems occur, a 14/2 stranded shielded cable can replace the L(2) and S wires between the indoor and outdoor units.

  1. Use 14/2 stranded shielded cable to replace L(2) and S.
  2. Land the shield on ground at the outdoor unit only.

Voltage check points

Carrier · D5FUHA single zone wiring

The checklist calls for voltage readings at the outdoor disconnect, the outdoor terminal block, and at both units. The pages give no acceptable values.

  1. Measure 1(L1) to GND, 2(L2) to GND, and 1(L1) to 2(L2) at the outdoor unit disconnect.
  2. Repeat at the outdoor unit terminal block.
  3. Measure 1(L1) to GND, 2(L2) to GND, 1(L1) to 2(L2), and 2(L2) to 3(S) at the outdoor unit and the indoor unit.
  4. Record the readings and any notes on the checklist.

Voltage selection

Carrier · D5FUHA indoor units

The unit can use 115V or 208/230V automatically. The K-suffix models are rated 208/230-1-60 and may be configured for 115 V AC.

  1. Confirm the supply voltage at the indoor unit before power-up.
  2. If the site is 115 V, check the configuration per the installation instructions for the K-suffix model.

Wired controller and 24V thermostat cannot run together

Carrier · D5FUHA control wiring

The wired remote controller KSACN1401AAA (sold separately) and a 24V third-party heat pump thermostat cannot be connected at the same time. A 2 heat/1 cool thermostat is needed for electric heat applications.

  1. Connect either the wired controller or the 24V thermostat, not both.
  2. For electric heat, use a 2 heat/1 cool thermostat.

Set Furnace Model after replacing the control board

Rinnai · CAH050E, CAH050CE hydronic air handlers

After a control board replacement the System menu Furnace Model entry must be set to CAH050E.

  1. Open the Installer menu with the password: down, center, up, center.
  2. Go to System menu > Furnace Model.
  3. Set it to CAH050E.

24V interface compatibility

Viessmann · Size 58 and all other sizes

The 24V interface works with all sizes except 58. From serial V191410001, size 58 ships with the compatible control board.

  1. On size 58, check the serial number before ordering the 24V interface kit.
  2. On size 58 units before V191410001, confirm the control board is compatible before connecting a 24V interface.

Choose the control method

Viessmann · DLFSAB / DLFLAB

Scenario 1 uses the wired controller KSACN1001AAA (non-polarity, has an infrared receiver that works with the remote). The included wireless remote gives the same functions and can be used with the wired controller. Both need SW1-1 in the OFF position (default). Scenario 2 uses a third-party heat pump thermostat through the built-in 24V interface, which needs SW1-1 in the ON position.

  1. For wired or wireless controller control, set SW1-1 to OFF (default).
  2. For third-party 24V heat pump thermostat control, set SW1-1 to ON.
  3. Connect the wired controller KSACN1001AAA if used; it is non-polarity.

Condensate lift pump location by size

Viessmann · All indoor sizes

Sizes 09 to 18 ship with an external condensate lift pump. Sizes 24 to 58 have the lift pump built in.

  1. For 09 to 18, install the shipped external lift pump.
  2. For 24 to 58, use the built-in lift pump and the 1 in drain connection.

Remove J7 short connector for on/off remote function

Viessmann · Indoor unit mainboard with on/off remote

If the on/off remote control function is used, remove the short connector on J7 first.

  1. Remove the short connector on J7 on the indoor mainboard.
  2. Connect the external on/off switch to CN23.

Set the network address for central control

Viessmann · Vitocal IND-A DLFUAA indoor units with central controller

Use the micro-switch S1 and dial switch S2 to set the unit address when a central controller is used. Address range is 00 to 63.

  1. Set the address with S1 and S2 together; the range is 00 to 63.
  2. Use the dial positions 0 to F on S2 and the micro-switch on S1 to reach the address.
  3. Address groups: 0 to 15, 16 to 31, 32 to 47, 48 to 63.
  4. Check the factory setting in the figure before changing it; the figure values are not readable in this extract.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.