Carrier Air Handler: Scenario 2 (default): wired controller wiring
Scenario 2 (default): wired controller wiring on a Carrier air handler: Scenario 2 is the default and lets the KSACN1401 or KSACN1701 wired controller work with RS485 between indoor and outdoor units.
Applies to: D5FUAA with wired controller (scenario 2)
How to fix scenario 2 (default): wired controller wiring: step by step
- Do not use any 24 V terminals on the indoor or outdoor unit.
- Connect the Ha and Hb terminals on the wired controller to the Ha and Hb terminals on the indoor built-in 24 V interface (CN7) using 16 AWG shielded stranded wire.
- Follow the indoor and outdoor communication diagram (Figure 12).
If the unit shows an error code, look it up: Carrier Air Handler codes
Models
45MUAAQ18XX345MUAAQ24XX345MUAAQ30XX345MUAAQ36XX345MUAAQ48XX345MUAAQ60XX3D5FUAA
More commissioning tips for air handler
Source: D5FUAA Crossover Air Handler product data, p. 12. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.