Carrier Air Handler: Room size and duct outlet height for R454B
Room size and duct outlet height for R454B on a Carrier air handler: R454B is a mildly flammable (A2L) refrigerant. The room area served and the total refrigerant charge are limited. The bottom of the duct air outlet in the room must be at the height stated on the page, 7.3 ft (2.2 m) above the floor. Table 2 (minimum room area) is not legible on these pages.
Applies to: Units with R454B refrigerant
How to fix room size and duct outlet height for r454b: step by step
- Check the room area served against Table 2 and the charge limit.
- Set the duct outlet height to at least 7.3 ft (2.2 m) above the floor.
- Keep the room free of continuously operating open flames or other ignition sources if the room is below the minimum area.
If the unit shows an error code, look it up: Carrier Air Handler codes
Models
D5FUHAH24AAKD5FUHAH36AAKD5FUHAH60AAKEHKMD05KNEHKMD08KNEHKMD10KNEHKMD15KNEHKMD20KNEHKMD25KN
More commissioning tips for air handler
Source: D5FUHA Installation Instructions, p. 5. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.