Carrier Air Handler: Purging with oxygen-free nitrogen
Purging with oxygen-free nitrogen on a Carrier air handler: Compressed air and oxygen must never be used to purge the system. Purge with oxygen-free nitrogen by breaking vacuum, filling to working pressure, venting to atmosphere, then pulling down to vacuum. Repeat until no refrigerant remains. Vent to atmospheric pressure before opening the circuit.
Applies to: Flammable refrigerant systems
How to fix purging with oxygen-free nitrogen: step by step
- Break the vacuum with oxygen-free nitrogen and fill to working pressure.
- Vent to atmosphere.
- Pull down to vacuum again.
- Repeat until no refrigerant remains.
- Vent to atmospheric pressure before work starts.
If the unit shows an error code, look it up: Carrier Air Handler codes
Models
D5FUHAH24AAKD5FUHAH36AAKD5FUHAH60AAKEHKMD05KNEHKMD08KNEHKMD10KNEHKMD15KNEHKMD20KNEHKMD25KN
More other tips for air handler
Source: Carrier D5FUHA service manual, p. 6. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.