Carrier Air Handler: Purging and breaking vacuum on flammable refrigerant systems

Updated · by Aurora Star Tech Inc.

Purging and breaking vacuum on flammable refrigerant systems on a Carrier air handler: Purging rules for systems with flammable refrigerant.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Flammable refrigerant systems

How to fix purging and breaking vacuum on flammable refrigerant systems: step by step

  1. Never use compressed air or oxygen to purge the system.
  2. Break the vacuum with oxygen-free nitrogen and fill to working pressure, then vent to atmosphere.
  3. Repeat until no refrigerant remains in the system.
  4. Vent the final nitrogen charge to atmospheric pressure before work starts.
  5. Keep the vacuum pump outlet away from ignition sources and make sure there is ventilation.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Carrier Air Handler codes

Models

45MUAAQ18XX345MUAAQ24XX345MUAAQ30XX345MUAAQ36XX345MUAAQ48XX345MUAAQ60XX3D5FUAA

More other tips for air handler

Source: D5FUAA Installation Instructions, p. 6. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.