Allied Furnace: Exhaust pipe transitions and sizing

Updated · by Aurora Star Tech Inc.

Exhaust pipe transitions and sizing on a Allied furnace: Pipe size comes from table 5, and exhaust and intake must be the same diameter. Step-ups should be kept as short as possible. Getting this wrong shows up as pressure switch trips or poor combustion.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Upflow and horizontal, direct and non-direct vent exhaust and intake piping

Common causes of exhaust pipe transitions and sizing

  • Pipe diameter not matching table 5 for the model and venting length
  • Intake and exhaust of different diameters
  • Step-up in pipe size placed in a horizontal exhaust run, where condensate can pool
  • Long step-up transition section
  • Loose intake pipe at the inlet air connector

How to fix exhaust pipe transitions and sizing: step by step

  1. Size the exhaust pipe using table 5 for the model and venting length, because undersized pipe restricts flow.
  2. Use the same diameter for intake and exhaust pipe.
  3. Do not step up from a smaller to a larger pipe in a horizontal run of exhaust pipe, since condensate collects at the step.
  4. If the pipe must step up in size, use the shortest possible length of 2 in. PVC for that transition.
  5. Use transition solvent cement or a sheet metal screw to secure the intake pipe to the inlet air connector.
  6. After assembly, check every joint for gaps and confirm the run slopes back toward the furnace as the manual requires.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Allied Furnace codes

Models

92G1UH92G1UH0450892G1UH0451292G1UH0700892G1UH0701292G1UH0901292G1UH0901692G1UH1101692G1UH1102092G1UH1352095G1UHA93UHA95UH

Source: Allied 92G1UH installation instructions manual, p. 24. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.