Icon
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

KeepRite Error Code 46: Brown-out (low voltage) (AC)

Updated · by Aurora Star Tech Inc.

KeepRite error code 46 on a air conditioner means: Brown-out (low voltage). It is also called KeepRite diagnostic code 46.

Medium severityAir ConditionerAlso Heat PumpKeepRite C4A3/CXA6 AC · KeepRite *SA/*SH Single-Stage Communicating · KeepRite *CA/*CH Two-Stage Communicating

Homeowner? What KeepRite code 46 means for you

Check, then call Your air conditioner is reporting: Brown-out (low voltage). This is often caused by something simple. Try the safe checks below; if the code returns, book a service call before it turns into a no-heat or no-hot-water emergency.

Safe things you can check yourself

  • Check the thermostat: right mode (Heat or Cool), set a few degrees past room temperature, and fresh batteries if it uses them.
  • Check both breakers and the outdoor disconnect box beside the outdoor unit; all should be ON.
  • Look at the air filter. If it is grey and clogged, replace it; a blocked filter causes many shutdowns.
  • Keep about 2 feet around the outdoor unit clear of leaves, grass and debris.
  • If you see ice on the pipes or the indoor coil, turn the system off and run only the fan for a few hours, then call a technician.
  • Try one reset: turn the power off for 30 seconds, then back on. If the code comes back, stop resetting and call a technician.

Call (647) 657-2977Book a service call

Licensed technicians serving Vaughan, Toronto and the GTA.

What does KeepRite error code 46 mean?

Single-stage boards (and C4A3/CXA6 board): 24 V control voltage below 15.5 V for 4 s; runs again at 17.5 V or more. Two-stage boards: line voltage below 187 V for 4 s; runs again above 190 V.

Applies to: KeepRite C4A3/CXA6 AC with outdoor control board; *SA5/*SA6 AC and *SH4/*SH5/*SH6 HP single-stage communicating; *CA7/*CA9 AC and *CH6/*CH9 HP two-stage communicating

Common causes of KeepRite code 46

  • Weak or overloaded 24 V transformer
  • Low utility line voltage
  • Loose power or control wiring
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

KeepRite models that use code 46

*CA624*CA636*CA648*CA660*CA924*CA936*CA948*CA960*SA5*SA6C4A3CXA6

Other KeepRite AC codes

CodeMeaning
9Comfort Alert 9 - low control voltage
16Lost communication with wall control
25Model plug missing or invalid
31High pressure switch open
32Low pressure switch open
45Outdoor control board failure
47No 230 V at the unit
53Outdoor air temperature sensor fault
55Outdoor coil sensor fault
56Air and coil sensors disagree
71Low stage thermal cutout
72Compressor thermal cutout (two-stage: high stage)

All KeepRite Air Conditioner error codes →

KeepRite code 46: homeowner questions

What does KeepRite code 46 mean?

Brown-out (low voltage). Single-stage boards (and C4A3/CXA6 board): 24 V control voltage below 15.5 V for 4 s; runs again at 17.5 V or more. Two-stage boards: line voltage below 187 V for 4 s; runs again above 190 V.

Is it safe to keep using my air conditioner with code 46?

It depends on the cause. This is often caused by something simple. Try the safe checks below; if the code returns, book a service call before it turns into a no-heat or no-hot-water emergency.

Can I reset KeepRite code 46 myself?

You can try one reset (power off for 30 seconds, then on). If KeepRite code 46 comes back, the cause is still there and a licensed technician should check it.

Who can fix KeepRite code 46 near me?

Aurora Star Tech Inc. repairs KeepRite air conditioners in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.

Homeowner help: AC Running But Not Cooling: What to Check

Troubleshooting guides

Source: KeepRite/ICP C4A3/H4A3/T4A3/CXA6 Installation Instructions 421 01 5103 05, Table 1 Status Codes, p.17; KeepRite_ICP_KeepRite_Tempstar_Heil_split_A_C_HP_R_410A_R_22_service_421_08_5400_04.txt - section Table 13 Status Codes (single-stage); KeepRite_ICP_KeepRite_Tempstar_Heil_split_A_C_HP_R_410A_R_22_service_421_08_5400_04.txt - section Table 17 Troubleshooting (two-stage). Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency HVAC Service

647-657-2977