Carrier Heat Pump: Delay before the compressor restarts
Delay before the compressor restarts on a Carrier heat pump: Before you chase a fault, confirm whether the wait is just normal protection. On the Carrier Infinity 18VS (25VNA8) the outdoor unit deliberately holds off before the compressor starts again, and in most cases nothing is broken. The delay comes from the pressure equalizer valve cycle, from a warm-up period after power is restored, or from a fault code delay. Check the STATUS light before you tell the customer anything. Do not try to defeat protection delays beyond what the manual allows.
Applies to: Carrier Infinity 18VS variable speed heat pump 25VNA8
Common causes of delay before the compressor restarts
- Pressure equalizer valve cycle after every compressor stop
- 10-minute warm-up after high voltage power-up
- Protection delays from fault codes
- Brown-out recovery delay after a low voltage event
How to fix delay before the compressor restarts: step by step
- After every compressor stop the pressure equalizer valve opens for 150 s, then 15 s off before the next start, this cannot be bypassed
- After power-up the compressor sump warms for 10 minutes (code 68)
- Check the STATUS light for any other fault delay and look the code up
- The brown-out recovery delay can be cleared using the Forced Defrost pins as the manual describes, confirm line voltage is good and follow the unit literature exactly
- If the delays keep repeating, check supply voltage at the unit for dips
- Explain the normal wait to the homeowner so it is not mistaken for a fault
If the unit shows an error code, look it up: Carrier Heat Pump codes
Models
Carrier 2-stage 24ANB/25HNB
25HNB62425HNB63625HNB64825HNB66025HNB92425HNB93625HNB94825HNB960
Carrier Infinity 18VS 25VNA8
25VNA81325VNA82425VNA82525VNA83625VNA83725VNA84825VNA860
D5FCFA
D5FUAA
37MUHA37MURAD5FUAAH18AAKD5FUAAH24AAKD5FUAAH30AAKD5FUAAH36AAKD5FUAAH48AAKD5FUAAH60AAK
D5CURA
D5CURA + D5MUWAD5CURAH18AAKD5CURAH24AAKD5CURAH30AAKD5CURAH36AAKD5CURAH48AAKD5CURAH60AAK
Source: Carrier 25VNA8 / 24VNA9 Service Manual, Timing / delays p.8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.