Amber STATUS or green COMM light not on on a Carrier heat pump: On the Carrier Infinity 18VS (25VNA8), two small lights on the outdoor AOC board tell you most of what you need to know before any meter comes out. In my experience, a dead amber STATUS light with power present nearly always means the board is bad. The green COMM light is more forgiving because on a non-communicating thermostat it is supposed to be off. So check what kind of control you have before you condemn anything. Wall control code 179 is the other clue.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Carrier Infinity 18VS variable speed heat pump 25VNA8

Common causes of amber status or green comm light not on

  • AOC board failure
  • No communication with the indoor unit or wall control
  • Non-communicating thermostat, where the COMM light is normally off
  • A and B communication wires open, shorted or swapped

How to fix amber status or green comm light not on: step by step

  1. With power to the outdoor unit the amber STATUS light must be on or flashing, if it is completely off, check that the unit has voltage, then replace the AOC board
  2. Communicating systems: the green COMM light should be on steady once the indoor unit and Infinity control talk to it, it goes off after 2 minutes without communication
  3. If the A and B wires are connected and the indoor unit communicates but COMM stays off, replace the AOC board
  4. Check the A and B wires at both ends for tight, correct connections
  5. Wall control code 179 means lost communication with the outdoor AOC, the AOC or inverter may need replacing
  6. Kill power at the disconnect before checking or changing wiring on the board
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Carrier Heat Pump codes

Models

Carrier 2-stage 24ANB/25HNB

25HNB62425HNB63625HNB64825HNB66025HNB92425HNB93625HNB94825HNB960

Carrier Infinity 18VS 25VNA8

25VNA81325VNA82425VNA82525VNA83625VNA83725VNA84825VNA860

D5FCFA

37MAHAQ37MARAQ37MGHAQ37MGRAQ

D5FUAA

37MUHA37MURAD5FUAAH18AAKD5FUAAH24AAKD5FUAAH30AAKD5FUAAH36AAKD5FUAAH48AAKD5FUAAH60AAK

D5CURA

D5CURA + D5MUWAD5CURAH18AAKD5CURAH24AAKD5CURAH30AAKD5CURAH36AAKD5CURAH48AAKD5CURAH60AAK

Source: Carrier 25VNA8 / 24VNA9 Service Manual, Communication and Status Function Lights p.8; LED tables p.27-28. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.