Daikin Error Code F8: Compressor temperature abnormality (discharge pipe) (Heat Pump)
Daikin error code F8 on a heat pump means: Compressor temperature abnormality (discharge pipe). It is also called Daikin diagnostic code F8.
Homeowner? What Daikin code F8 means for you
Call a technician Your heat pump is reporting: Compressor temperature abnormality (discharge pipe). The heat pump has locked out or cannot run properly. One reset is fine; if the code comes back, it needs a licensed technician to find the cause.
Safe things you can check yourself
- Check the thermostat: right mode (Heat or Cool), set a few degrees past room temperature, and fresh batteries if it uses them.
- Check both breakers and the outdoor disconnect box beside the outdoor unit; all should be ON.
- Look at the air filter. If it is grey and clogged, replace it; a blocked filter causes many shutdowns.
- In winter, keep snow and ice off and away from the outdoor unit. A short defrost cycle with steam is normal.
- Try one reset: turn the power off for 30 seconds, then back on. If the code comes back, stop resetting and call a technician.
Call (647) 657-2977Book a service call
Licensed technicians serving Vaughan, Toronto and the GTA.
What does Daikin error code F8 mean?
Operation halts when the discharge pipe thermistor exceeds its limit. The detection threshold is 127.5°C / 261.5°F during forced cooling operation.
Applies to: FTXM-W/V outdoor unit, forced cooling
Common causes of Daikin code F8
- Air intrusion into the refrigerant circuit
- Defective discharge pipe thermistor
Other Daikin Heat Pump codes
All Daikin Heat Pump error codes →
Daikin code F8: homeowner questions
What does Daikin code F8 mean?
Compressor temperature abnormality (discharge pipe). Operation halts when the discharge pipe thermistor exceeds its limit. The detection threshold is 127.5°C / 261.5°F during forced cooling operation.
Is it safe to keep using my heat pump with code F8?
It depends on the cause. The heat pump has locked out or cannot run properly. One reset is fine; if the code comes back, it needs a licensed technician to find the cause.
Can I reset Daikin code F8 myself?
You can try one reset (power off for 30 seconds, then on). If Daikin code F8 comes back, the cause is still there and a licensed technician should check it.
Who can fix Daikin code F8 near me?
Aurora Star Tech Inc. repairs Daikin heat pumps in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.
Homeowner help: AC Running But Not Cooling: What to Check · Heat Pump Not Heating or Blowing Cold Air
Troubleshooting guides
- 2 flashes: HPS open ≥6 s; 3: discharge >263°F; 4: discharge <90°F after 1 h; 5: defrost failure; 6: discharge sensor short; 7: outdoor sensor open/short; 9: bonnet sensor fail All brands · Heat Pump
- Auxiliary heat indicator light is on All brands · Heat Pump
- Cleaning the outdoor unit finish All brands · Heat Pump
- Excess ice on outdoor coil All brands · Heat Pump
- Extremely high head pressure in heating (dual fuel) All brands · Heat Pump
- Insufficient heat in cold weather All brands · Heat Pump
- Liquid slugging / compressor damage in heating All brands · Heat Pump
- No mode change / wrong mode All brands · Heat Pump
Source: SiUS042113EA service manual, p. 131. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.