Navien Air Conditioner: Repairing the refrigerant circuit (R-454B flammable refrigerant)
Repairing the refrigerant circuit (R-454B flammable refrigerant) on a Navien air conditioner: Follow this sequence before opening the refrigerant circuit for any repair. Use the required recovery equipment and handle the flammable refrigerant safely.
Applies to: NAA outdoor unit
How to fix repairing the refrigerant circuit (r-454b flammable refrigerant): step by step
- Recover the refrigerant with a recovery pump certified for flammable refrigerants.
- Purge the circuit with nitrogen.
- Evacuate the circuit to 1,500 microns.
- Open the circuit only by cutting or brazing.
- Break the vacuum with a nitrogen purge, keeping the vacuum pump outlet away from any ignition source.
- Replace the filter drier every time the refrigerant circuit is opened.
If the unit shows an error code, look it up: Navien Air Conditioner codes
More other tips for air conditioner
Source: Navien NAA air conditioner service manual, p. 19. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.